Table 22 — Cooling Set Point Selection Touch Pilot™ Parameters

SET POINT

ICE MODE

DUAL SET

ICE DONE INPUT

TIME

ACTIVE

CONFIGURATION

ENABLE

POINT INPUT

(ICE_SW)

SCHEDULE 2

SET POINT

(Setpoint Select)

(ice_cnfg)

(SETP_SW)

 

 

 

 

NO

Occupied

Cooling Setpoint 1

0

Unoccupied

Cooling Setpoint 2

 

 

Open

Unoccupied

Cooling Ice Setpoint

(Auto)

 

YES

Closed

Unoccupied

Cooling Setpoint 2

 

 

 

Occupied

Cooling Setpoint 1

1 (Setp 1)

Cooling Setpoint 1

2 (Setp 2)

Cooling Setpoint 2

3 (4-20 mA)

4 to 20 mA Input

 

NO

Open

Cooling Setpoint 1

 

Closed

Cooling Setpoint 2

 

 

4 (Setp Sw)

 

Open

Cooling Setpoint 1

 

YES

Closed

Open

Cooling Ice Setpoint

 

 

Closed

Closed

Cooling Setpoint 2

Table 23 — Cooling Set Point Selection Navigator™ Parameters

 

 

PARAMETER STATUS

 

 

 

 

Control Method

Heat/Cool

Setpoint

Ice Mode

Ice Done

Dual Setpoint

Setpoint

ACTIVE

Occupied

SET POINT

(OPER)

Select (HC.SE)

Select (SP.SE)

Enable (ICE.M)

(ICE.D)

Switch (DUAL)

(SP.OC)

 

 

 

 

 

 

 

 

 

 

Setpoint Occ

Occupied

CSP.1

 

 

Setpoint Occ

Unoccupied

CSP.2

 

 

Setpoint Occ

Enable

Open

Unoccupied

CSP.3

 

 

Setpoint 1

CSP.1

LOCAL

COOL

Setpoint 2

CSP.2

4-20mA Setp

4_20mA

 

 

 

 

Enable

Open

Closed

CSP.3

 

 

Enable

Closed

Closed

CSP.2

 

 

Open

CSP.1

 

 

Dual Setp Sw

Closed

CSP.2

CCN

COOL

Occupied

CSP.1

 

 

 

 

 

 

Unoccupied

CSP.2

 

 

Set Point 1 — When Set Point Select (Setpoint Select, SP.SE) is configured to 1 (Setpoint 1), the unit’s active set point is based on Cooling Set Point 1 (Cooling Setpoint 1, CSP.1).

To configure this option with the Touch Pilot display:

DISPLAY NAME

PATH

LINE

VALUE

NO.

 

 

 

Setpoint Select

StatusGENUNIT

25

1 (Set Point 1)

To change this value, a Control Point Force must be applied. When configured correctly, Setpoint Control will indicate Setp 1.

To configure this option with the Navigator™ display:

ITEM

ITEM EXPANSION

PATH

VALUE

SP.SE

Setpoint Select

Operating ModesSLCT

Setpoint 1

Set Point 2 — When Set Point Select (Setpoint Select, SP.SE) is configured to 2 (Setpoint 2), the unit’s active set point is based on Cooling Set Point 2 (Cooling Setpoint 2, CSP.2).

To configure this option with the Touch Pilot™ display:

DISPLAY NAME

PATH

LINE

VALUE

NO.

 

 

 

Setpoint Select

StatusGENUNIT

25

2 (Set Point 2)

To change this value, a Control Point Force must be applied. When configured correctly, Setpoint Control (StatusGENUNIT) will indicate Setp 2.

To configure this option with the Navigator display:

ITEM

ITEM EXPANSION

PATH

VALUE

SP.SE

Setpoint Select

Operating ModesSLCT

Setpoint 2

4 to 20 mA Input — When Set Point Select (Setpoint Select, SP.SE) is configured to 3 (4-20 mA Setp), the unit’s active set point is based on an field supplied, external 4 to 20 mA signal input to the Energy Management Module (EMM). Care should be taken when interfacing with other manufacturer’s control systems, due to power supply differences of full wave bridge versus half wave rectification. The two different power sup- plies cannot be mixed. ComfortLink™ controls use half wave rectification. A signal isolation device should be utilized if a full wave bridge signal generating device is used.

The following equation is used to control the set point. See Fig. 18.

Fahrenheit Set Point = 10 + 70(mA – 4)/16 (deg F) Celsius Set Point = –12.2 + 38.9(mA – 4)/16 (deg C)

To configure this option while using a Touch Pilot display:

DISPLAY NAME

PATH

LINE

VALUE

NO.

 

 

 

Setpoint Select

StatusGENUNIT

25

3 (4-20 mA Input)

To change this value, a Control Point Force must be applied. When configured correctly, Setpoint Control will indicate 4-20 mA.

26

Page 26
Image 26
Carrier 30XW150-400 Cooling Set Point Selection Touch Pilot Parameters, Cooling Set Point Selection Navigator Parameters

30XW150-400 specifications

The Carrier 30XW150-400 series is a line of water-cooled chillers that exemplifies innovation, efficiency, and reliability in commercial cooling solutions. Designed for medium to large-scale applications, this series is ideal for a variety of settings, including commercial buildings, industrial processes, and chilled water systems.

One of the standout features of the Carrier 30XW series is its efficiency. The chillers utilize advanced variable-speed compressor technology, which allows the units to adapt to varying cooling loads while minimizing energy consumption. This technology not only reduces operational costs but also contributes to better environmental sustainability by lowering greenhouse gas emissions.

The 30XW series chillers are equipped with high-efficiency, scroll compressors that operate quietly and provide significant energy savings. By utilizing enhanced economizer controls, these units can achieve higher efficiency ratings, especially in part-load conditions. The result is an impressive Energy Efficiency Ratio (EER) and Seasonal Energy Efficiency Ratio (SEER), making these units a smart choice for energy-conscious businesses.

In terms of reliability, the Carrier 30XW150-400 series features robust construction and an array of safety and monitoring systems. The units come with advanced diagnostics that help in quickly identifying and addressing any operational issues. This proactive approach ensures reliability and minimizes downtime, which is crucial for maintaining optimal temperature controls in critical environments.

Additionally, the chillers incorporate environmentally friendly refrigerants that comply with the latest regulations, making them a sustainable choice for modern commercial applications. Their compact design allows for flexible installation options, and the integrated control systems provide the ability to optimize performance based on specific building management demands.

User-friendly interfaces and remote monitoring capabilities further enhance the ease of operation, allowing facility managers to have real-time insight into performance metrics and system health. This level of control contributes to better maintenance planning and maximizes the lifespan of the equipment.

In summary, the Carrier 30XW150-400 series of water-cooled chillers combines advanced technology, energy efficiency, and reliable performance, making it an ideal solution for various commercial and industrial cooling needs. With its commitment to innovation and sustainability, Carrier continues to set the standard in the HVAC industry.