Carrier 30XW150-400 Equipment Stop Screen, Navigator Start/Stop Control, Operating Control, Type

Models: 30XW150-400

1 148
Download 148 pages 52.93 Kb
Page 23
Image 23
Fig. 17 — Equipment Stop Screen

commands, except the Emergency Stop Command will be ignored. The Run Status variable will indicate the current sta- tus of the machine (OFF, RUNNING, DELAY, or READY), depending on the position of the Remote/Off/Enable Switch closure. The Chiller Occupied? variable will change to YES. The Control Type variable will change to Remote. The Oper- ating Type variable will change to Remote.

Master Mode — To activate Dual Chiller Control, each ma- chine must be individually configured for Dual Chiller Control. To operate the machines in Dual Chiller Mode, one machine must be designated as the master unit and one machine as the slave unit. On the master unit, press the Start/Stop button on the Touch Pilot display. The Equipment Start screen will be dis- played. Select Master Mode. Failure to start the Master unit in this manner will cause both machines to operate in local mode.

The Master Unit Control can be done locally, remotely or through CCN commands per the master/slave configuration (Master Control Type). The control will ignore the position of Enable/Off/Remote Contact switch if the Master Control Type is configured for Local Control or CCN Control. The Run Status variable, Chiller Occupied? variable, and Con- trol Type variable will change based on the Master Control Type configured above and the Machine On/Off Control de- fined above. The Operating Type variable will change to Master.

To Turn Machine Off — To turn the machine off, press the Start/Stop button on the Touch Pilot display. See Fig. 17. The machine will shut down. While the unit is in Local Off, it will remain shut down and ignore all CCN commands as well as the position of Enable/Off/Remote Contact switch. The Run Status variable, indicating the current status of the machine, will change to OFF. The Chiller Occupied? variable will change to NO. The Control Type variable will indicate Local. The Operating Type variable will change to L-OFF (Local Off).

Fig. 17 — Equipment Stop Screen

NAVIGATOR™ DISPLAY MACHINE CONTROL — Ma- chine On/Off control with the Navigator display is determined by the configuration of the Operating Type Control (OPER). Options to control the machine locally via a switch, from a lo- cal Time Schedule, or via a Carrier Comfort Network® com- mand are offered. See Table 17.

The schedules consist of 8 user-configurable occupied time periods. The control supports time schedules for local control, remote control, and ice building. These time periods can be flagged to be in effect or not in effect on each day of the week. The day begins at 00.00 and ends at 24.00. The machine is in unoccupied mode unless a scheduled time period is in effect. If an occupied period is to extend past midnight, the occupied period must end at 24:00 hours (midnight) and a new occupied period must be programmed to begin at 00:00 hours.

In the following example, a early morning pulldown time period is scheduled for Monday morning from 12:00 AM to 3:00 AM. The occupied period starts at 7:00 AM, Monday through Saturday. The occupied time ends at 6:00 PM on Mon- day and Tuesday, 9:30 PM on Wednesday, 5:00 PM on Thurs- day and Friday, and 12:00 PM on Saturday.

NOTE: This schedule was designed to illustrate the program- ming of the schedule function and is not intended as a recom- mended schedule for chiller operation.

Switch Control — In the Switch Control operating type, the Enable/Off/Remote Contact switch controls the machine local- ly. All models are factory configured with Operating Type Control (OPER) set to SWITCH CTRL (Switch Control). With SWITCH CTRL, switching the Enable/Off/Remote Contact switch to the Enable or Remote Contact position (ex- ternal contacts closed) will put the chiller in an occupied state. The Unit Run Status (STAT) will indicate the current status of the machine and will change from OFF to RUNNING or DELAY. The unit Occupied Status (OCC) will change from NO to YES. The Status Unit Control Type (CTRL) will change from LOCAL OFF when the switch is Off to LOCAL ON when in the Enable position or in the Remote Contact position with external contacts closed.

ITEM

ITEM EXPANSION

PATH

VALUE

OPER

Operating Control

Operating

SWITCH

Type

ModesSLCTOPER

CTRL

Table 17 — Navigator Start/Stop Control

CONTROL

ACTIVE

REMOTE/OFF/ENABLE

REMOTE ON/OFF

 

CCN CHILLER

EMERGENCY

 

REMOTE

UNIT

METHOD

OPERATING

TIME SCHEDULE 1

START/STOP

STOP

ALARM

LOCKOUT

(OPER)

TYPE

SWITCH

SWITCH

 

(CHIL_S_S)

(EMSTOP)

 

SWITCH

STATUS

 

 

 

 

 

 

 

Off

Off

 

 

Remote

Open

Off

All

Local Off

Enable

Off

 

 

Yes

Off

 

 

Closed

Off

Switch

Local On

Enable

Disable

On

Control

Remote

Closed

Disable

On

 

Time

Local

Enable

Occupied

Disable

On

Remote

Closed

Occupied

Disable

On

Schedule

Schedule

Unoccupied

Disable

Off

 

 

 

 

Remote

Closed

Enable

Disable

On

CCN

CCN

Remote

Closed

Disable

Disable

Off

Control

Enable

Enable

Disable

On

 

 

 

Enable

Disable

Disable

Off

23

Page 23
Image 23
Carrier 30XW150-400 Equipment Stop Screen, Navigator Start/Stop Control, Operating Control, Switch, Type, Ctrl