Carrier 30XW150-400 specifications

Models: 30XW150-400

1 148
Download 148 pages 52.93 Kb
Page 34
Image 34

Table 29 — Dual Master Chiller Control Parameters for Series Applications with Navigator™ Display

ITEM

ITEM EXPANSION

PATH

VALUE

MSSL

Master/Slave Select

ConfigurationRSET

Master

Default: Disable

 

 

 

 

 

 

Must be set to the Slave Chiller’s address.

SLVA

 

ConfigurationRSET

The master and slave chiller must have

Slave Address

different addresses and be on the same

 

 

 

Bus Number

 

 

 

Default: 2

LLBL

Master Lead Lag Select

ConfigurationRSET

Range: Always Lead, Lag if Fail, Runtime Sel

Default: Always Lead

 

 

 

LLBD

Lead/Lag Balance Delta

ConfigurationRSET

Range: 40 to 400 hours

Default: 168 hours

 

 

 

LLDY

Lag Start Delay

ConfigurationRSET

Range: 2 to 30 minutes

Default: 10 minutes

 

 

 

LL.ER

Start If Error Higher

ConfigurationRSET

Range: 3.0 to 18 ΔF (1.7 to 10.0 ΔC)

Default: 4.0 ΔF (2.2 ΔC)

 

 

 

LAG.M

Lag Unit Pump Select

ConfigurationRSET

Range: Off If U Stp, On If U Stop

Default: Off If U Stp

 

 

 

LPUL

Lead Pulldown Time

ConfigurationRSET

Range: 0 to 60 minutes

Default: 0 minutes

 

 

 

SERI

Chillers in Series

ConfigurationRSET

YES

Default: NO

 

 

 

OPER

Operating Control Type

Operating ModesSLCT

Set to desired value

Table 30 — Dual Slave Chiller Control Parameters for Series Applications with Touch Pilot™ Display

DISPLAY NAME

PATH

LINE NO.

 

VALUE

Master/Slave Select

Main MenuConfigMST_SLV

3

2

(Slave)

Default: 0 (Disable)

 

 

 

 

 

 

1

(Local Control)

Master Control Type

Main MenuConfigMST_SLV

 

2

(Remote Control)

7

3

(CCN Control)

 

 

 

Default: 1 (Local Control)

 

 

 

Value: Configure for proper control type.

 

 

 

Must be set to the Slave Chiller’s address.

Slave Address

Main MenuConfigMST_SLV

 

The master and slave chiller must have

11

different addresses and be on the same

 

 

 

Bus Number

 

 

 

Default: 2

 

 

 

0

(Master Always Leads)

Lead Lag Select

Main MenuConfigMST_SLV

12

1

(Lag Once Failed Only)

2

(Lead/Lag Runtime Select)

 

 

 

 

 

 

Default: 0 (Master Always Leads)

Lead/Lag Balance Delta

Main MenuConfigMST_SLV

16

Range: 40 to 400 hours

Default: 168 hours

 

 

 

Lag Start Timer

Main MenuConfigMST_SLV

17

Range: 2 to 30 minutes

Default: 10 minutes

 

 

 

Lead Pulldown Time

Main MenuConfigMST_SLV

18

Range: 0 to 60 minutes

Default: 0 minutes

 

 

 

Start If Error Higher

Main MenuConfigMST_SLV

19

Range: 3.0 to 18 ΔF (1.7 to 10.0 ΔC)

Default: 4.0 ΔF (2.2 ΔC)

 

 

 

Lag Minimum Running Time

Main MenuConfigMST_SLV

20

Range: 0 to 150 minutes

Default: 0 minutes

 

 

 

Lag Unit Pump Control

Main MenuConfigMST_SLV

 

0

(Stop If Unit Stops)

21

1

(Run If Unit Stops)

 

 

 

Default: 0 (Stop If Unit Stops)

Chiller In Series

Main MenuConfigMST_SLV

22

Yes

Default: No

 

 

 

34

Page 34
Image 34
Carrier 30XW150-400 specifications Dual Master Chiller Control Parameters for Series Applications with Navigator Display