Carrier 30XW150-400 specifications Drop, Pressure, Evaporator Flow Rate

Models: 30XW150-400

1 148
Download 148 pages 52.93 Kb
Page 48
Image 48
Drop

process applications. Refer to application information in Prod- uct Data literature for details.

FLOW RATE REQUIREMENTS — Standard chillers should be applied with nominal flow rates within those listed in the Evaporator and Condenser Flow Rates table. Higher or lower flow rates are permissible to obtain lower or higher tempera- ture rises. Minimum flow rates must be exceeded to assure turbulent flow and proper heat transfer in the cooler. See Table 36. See Fig. 27-37 for cooler pressure drop curves.

Pressure CAUTION

Operation below minimum flow rate could generate alarms, which could result in damage to the cooler.

Consult application data section in the Product Data literature and job design requirements to determine flow rate requirements for a particular installation.

Table 36 — Evaporator and Condenser Flow Rates

 

 

 

 

EVAPORATOR

 

 

 

CONDENSER

 

 

NOMINAL

 

 

 

 

Leaving Fluid/Entering Fluid

 

Leaving Fluid/Entering Fluid

 

 

 

 

 

 

Minimum

Maximum

Minimum

Maximum*

Evaporator

Condenser

30XW UNIT

40 F (4.4 C)/

60 F (15.6 C)/

70 F (21.1 C)/

118 F (47.8 C)/

 

 

 

 

 

 

45 F (7.2 C)

70 F (21.1 C)

65

F (18.3 C)

110 F (43.3 C)

 

 

 

 

 

 

Minimum

Maximum

Minimum

Maximum

Nominal

Nominal

 

 

Flow Rate

Flow Rate

Flow Rate

Flow Rate

Flow Rate

Flow Rate

 

 

GPM

 

L/s

GPM

L/s

GPM

 

L/s

GPM

L/s

GPM

L/s

GPM

L/s

 

Two pass

200

 

12.6

720

45.4

240

 

15.1

960

60.6

384

24.2

480

30.3

150

One pass

384

 

24.2

1520

95.9

480

 

30.3

1600

100.9

384

24.2

480

30.3

 

Three pass

120

 

7.6

480

30.3

 

384

24.2

 

Two pass

213

 

13.4

765

48.3

255

 

16.1

1020

64.4

408

25.7

510

32.2

175

One pass

408

 

25.7

1615

101.9

510

 

32.2

1700

107.3

408

25.7

510

32.2

 

Three pass

128

 

8.0

510

32.2

 

408

25.7

 

Two pass

241

 

15.2

869

54.8

290

 

18.3

1158

731.0

463

29.2

579

36.5

200

One pass

463

 

29.2

1834

115.7

579

 

36.5

1930

121.8

463

29.2

579

36.5

 

Three pass

145

 

9.1

579

36.5

 

463

29.2

 

Two pass

403

 

25.4

1149

91.4

483

 

30.5

1932

121.9

773

48.8

966

60.9

325

One pass

773

 

48.8

3059

193.0

966

 

60.9

3220

203.2

773

48.8

966

60.9

 

Three pass

242

 

15.2

966

60.9

 

773

48.8

 

Two pass

429

 

27.0

1544

97.4

515

 

32.5

2058

129.8

823

51.9

1029

64.9

350

One pass

823

 

51.9

3259

205.6

1029

 

64.9

3430

216.4

823

51.9

1029

64.9

 

Three pass

257

 

16.2

1029

64.9

 

823

51.9

 

Two pass

481

 

30.4

1733

109.3

578

 

36.4

2310

145.7

924

58.3

1155

72.9

400

One pass

924

 

58.3

3658

230.8

1155

 

72.9

3850

242.9

924

58.3

1155

72.9

 

Three pass

289

 

18.2

1155

72.9

 

924

58.3

*Maximum condenser fluid temperature shown for standard condensing option. High condensing or heat machine option may have leaving fluid tem- peratures up to 140 F (60 C) and entering up to 128 F (53.3 C).

 

(kPa)

ft wg

 

 

 

 

 

 

(119.4)

40.00

 

 

 

 

 

 

(104.4)

35.00

3 pass

 

1 pass

 

 

 

 

 

 

 

 

Drop

(89.5)

30.00

 

2 pass

 

 

 

 

 

 

 

 

 

(74.6)

25.00

 

 

 

 

 

 

 

 

 

 

 

 

Pressure

(59.7)

20.00

 

 

 

 

 

(44.8)

15.00

 

 

 

 

 

(29.8)

10.00

 

 

 

 

 

 

 

 

 

 

 

 

(14.9)

5.00

 

 

 

 

 

 

(0)

0.00

 

 

 

 

 

 

 

0

500

1000

1500

2000

gpm

 

 

(0)

(31.5)

(63.1)

(94.6)

(126.2)

(L/s)

Evaporator Flow Rate

NOTE: The table above represents pressure drops only. The table does not imply that the chiller can be properly applied over the entire range of evaporator water flow rates represented.

Fig. 27 — 30XW150-200 Evaporator Marine Waterbox

a30-4833

48