Carrier 30XW150-400 specifications APPENDIX B - NAVIGATOR DISPLAY TABLES cont, Mode - Set Points

Models: 30XW150-400

1 148
Download 148 pages 52.93 Kb
Page 109
Image 109

APPENDIX B — NAVIGATOR™ DISPLAY TABLES (cont)

MODE — SET POINTS

ITEM

EXPANSION

UNITS

RANGE

COMMENT

WRITE

CCN TABLE

CCN POINT

PAGE

STATUS

NO.

 

 

 

 

 

 

 

COOL

COOLING SETPOINTS

 

 

 

 

 

 

 

CSP.1

Cooling Setpoint 1

XXXX.X

–20-70 F

 

forcible

SETPOINT

csp1

25, 41,

 

 

(deg F/deg C)

(–29-21 C),

 

 

 

 

55

CSP.2

 

 

Default = 44.0

 

 

 

 

 

Cooing Setpoint 2

XXXX.X

–20-70 F

 

forcible

SETPOINT

csp2

25, 41,

 

 

(deg F/deg C)

(–29-21 C),

 

 

 

 

55

CSP.3

 

 

Default = 44.0

 

 

 

 

 

Ice Setpoint

XXXX.X

–20-70 F

 

forcible

SETPOINT

ice_sp

25, 41,

 

 

(deg F/deg C)

(–29-21 C),

 

 

 

 

55

CRV1

 

 

Default = 44.0

 

 

 

 

 

Current No Reset Val

XX.X (mA)

0-20,

 

forcible

SETPOINT

v_cr_no

36

CRV2

 

 

Default = 0

 

 

 

 

 

Current Full Reset Val

XX.X (mA)

0-20,

 

forcible

SETPOINT

v_cr_fu

36

CRT1

 

XXX.X (ΔF/ΔC)

Default = 0

 

 

 

 

 

Delta T No Reset Temp

0-125 F

 

forcible

SETPOINT

dt_cr_no

35, 36

 

 

 

(0-69.4 C),

 

 

 

 

 

CRT2

 

XXX.X (ΔF/ΔC)

Default = 0

 

 

 

 

 

Delta T Full Reset Temp

0-125 F

 

forcible

SETPOINT

dt_cr_fu

35, 36

 

 

 

(0-69.4 C),

 

 

 

 

 

CRO1

 

 

Default = 0

 

 

 

 

 

OAT No Reset Temp

XXX.X

0-125 F

 

forcible

SETPOINT

oatcr_no

 

 

 

(deg F/deg C)

(–18-52 C),

 

 

 

 

 

CRO2

 

 

Default = 14.0

 

 

 

 

 

OAT Full Reset Temp

XXX.X

0-25 F

 

forcible

SETPOINT

oatcr_fu

 

 

 

(deg F/deg C)

(–18-52 C),

 

 

 

 

 

CRS1

 

 

Default = 14.0

 

 

 

 

 

Space T No Reset Temp

XXX.X

0-125 F

 

forcible

SETPOINT

spacr_no

36

 

 

(deg F/deg C)

(–18-52 C),

 

 

 

 

 

CRS2

 

 

Default = 14.0

 

 

 

 

 

Space T Full Reset Temp

XXX.X

0-125 F

 

forcible

SETPOINT

spacr_fu

36

 

 

(deg F/deg C)

(–18-52 C),

 

 

 

 

 

DGRC

 

XX.X (ΔF/ΔC)

Default = 14.0

 

 

 

 

 

Degrees Cool Reset

–30-30 F

 

forcible

SETPOINT

cr_deg

35, 36

 

 

 

(–16.7-16.7 C),

 

 

 

 

 

CAUT

 

 

Default = 0

 

 

 

 

 

Cool Changeover Setpt

XX.X

Default = 75.0

Not supported.

forcible

SETPOINT

cauto_sp

 

CRMP

 

(deg F/deg C)

0.2-2.0 ΔF

 

 

 

 

 

Cool Ramp Loading

X.X

 

forcible

SETPOINT

cramp_sp

35

 

 

 

(0.1-1.1 ΔC),

 

 

 

 

 

 

 

 

Default = 1.0

 

 

 

 

 

HEAT

HEATING SETPOINTS

 

 

 

 

 

 

 

HSP.1

Heating Setpoint 1

XXX.X

Default = 100

Not supported.

forcible

SETPOINT

HSP.1

 

HSP.2

 

(deg F/deg C)

 

 

 

 

 

 

Heating Setpoint 2

XXX.X

Default = 100

Not supported.

forcible

SETPOINT

HSP.2

 

HRV1

 

(deg F/deg C)

 

 

 

 

 

 

Current to Reset Val

XX.X (mA)

Default = 0

Not supported.

forcible

SETPOINT

v_hr_no

 

HRV2

Current Full Reset Val

XX.X (mA)

Default = 0

Not supported.

forcible

SETPOINT

v_hr_fu

 

HRT1

Delta T No Reset Temp

XXX.X (ΔF/ΔC)

Default = 0

Not supported.

forcible

SETPOINT

dt_hr_no

 

HRT2

Delta T Full Reset Temp

XXX.X (ΔF/ΔC)

Default = 0

Not supported.

forcible

SETPOINT

dt_hr_fu

 

HRO1

OAT No Reset Temp

XXX.X

Default = 14.0

Not supported.

forcible

SETPOINT

oathr_no

 

HRO2

 

(deg F/deg C)

 

 

 

 

 

 

OAT Full Reset Temp

XXX.X

Default = 14.0

Not supported.

forcible

SETPOINT

oathr_fu

 

DGRH

 

(deg F/deg C)

 

 

 

 

 

 

Degrees Heat Reset

XX.X (ΔF/ΔC)

Default = 0

Not supported.

forcible

SETPOINT

DGRH

 

HAUT

Heat Changeover Setpt

XX.X

Default = 64

Not supported.

forcible

SETPOINT

hauto_sp

 

HRMP

 

(deg F/deg C)

 

 

 

 

 

 

Heat Ramp Loading

X.X

Default = 1.0

Not supported.

forcible

SETPOINT

hramp_sp

 

MISC

MISC SETPOINTS

 

 

 

 

 

 

 

DLS1

Switch Limit Setpoint 1

XXX (%)

0-100,

 

forcible

SETPOINT

lim_sp1

39, 40

DLS2

 

 

Default = 100

 

 

 

 

 

Switch Limit Setpoint 2

XXX (%)

0-100,

 

forcible

SETPOINT

lim_sp2

39, 40

DLS3

 

 

Default = 100

 

 

 

 

 

Switch Limit Setpoint 3

XXX (%)

0-100,

 

forcible

SETPOINT

lim_sp3

 

W.SCT

 

 

Default = 100

 

 

 

 

 

Water Val Cond Stp

XXX.X

80-140 F

Not supported.

 

SETPOINT

w_sct_sp

46

 

 

(deg F/deg C)

(26.7-60 C)

 

 

 

 

 

109

Page 109
Image 109
Carrier 30XW150-400 specifications APPENDIX B - NAVIGATOR DISPLAY TABLES cont, Mode - Set Points