Action to be Taken — The compressor will be stopped.
Reset Method — Manual
Possible Causes — If this condition is encountered, check the following items:
•power failure
•blown fuse or tripped circuit breaker
•deenergized contactor
•faulty current toroid
•high pressure switch (HPS) trip (when auto reset HPS is used)
Compressor
Alarm
Alarm
Criteria for Trip — The alarm criterion is checked during compressor
Action to be Taken — The compressor will be stopped.
Reset Method — Manual
Possible Causes — If this condition is encountered, check the following items:
•power supply failure to the delta contactor
•faulty wiring to the delta contactor
•faulty CPM board
•faulty current toroid
Compressor Contactor Failure
Alarm
Alarm
Criteria for Trip — The alarm criterion is checked during compressor
Action to be Taken — The compressor will be stopped.
Reset Method — Manual
Possible Causes — If this condition is encountered, check the following items:
•faulty or welded contactor
•faulty wiring
•faulty CPM board
Compressor Unable to Stop Motor
Alarm
Alarm
Criteria for Trip — The alarm criterion is checked during compressor
Action to be Taken — The compressor will be stopped.
Reset Method — Manual
Possible Causes — If this condition is encountered, check the following items:
•faulty or welded contactor
•faulty wiring
Compressor Phase Reversal
Alarm
Alarm
Criteria for Trip — The alarm criterion is checked during compressor
Action to be Taken — The compressor will be stopped.
Reset Method — Manual
Possible Causes — If this condition is encountered, check the following items:
•if power supply lead at the terminal block is not operating at the correct phase
•if power supply is crossed when going through the current toroid
Compressor MTA Configuration Fault
Alarm
Alarm
Criteria for Trip — The alarm criterion is checked whether the compressor is ON or OFF. This alarm will be generated if the MTA setting is out of the allowed MTA range.
Action to be Taken — The compressor will be stopped.
Reset Method — Manual
Possible Causes — If this condition is encountered, check the following items:
•incorrect MTA settings
•faulty CPM board
Compressor Configuration Switch Mismatch
Alarm
Alarm
Criteria for Trip — The alarm criterion is checked whether the compressor is ON or OFF. This alarm will be generated if the CPM board S1 and S2 setting does not match software configuration.
Action to be Taken — The compressor will be stopped.
Reset Method — Manual
Possible Causes — If this condition is encountered, check the following items:
•incorrect CPM board settings
•faulty CPM board
Compressor Unexpected Switch Setting Change
Alarm
Alarm
Criteria for Trip — The alarm criterion is checked when the compressor is ON. This alarm will be generated if the CPM board S1 setting has changed.
Action to be Taken — The compressor will be stopped.
Reset Method — Manual
Possible Causes — If this condition is encountered, check the following items:
•incorrect CPM board settings
•faulty CPM board
Compressor Power on Reset
Alarm
Alarm
Criteria for Trip — The alarm criterion is checked when the compressor is ON. This alarm will be generated if the CPM board detects a power failure.
Action to be Taken — The compressor will be stopped.
Reset Method — Manual
Possible Causes — If this condition is encountered, check for power interruptions.
Compressor UL 1998 Critical Section Software Error
Alarm
Alarm
Criteria for Trip — The alarm criterion is checked when the compressor is ON. This alarm will be generated if the CPM board detects a software error.
Action to be Taken — The compressor will be stopped.
Reset Method — Manual
82