Carrier 30XW150-400 specifications Service Maintenance Alert Codes, Action to be Taken - None

Models: 30XW150-400

1 148
Download 148 pages 52.93 Kb
Page 81
Image 81

generated if the one of the following configuration errors is detected by the control. The “nn” refers to the error code listed in Table 52.

Table 52 — Service Maintenance Alert Codes

CODE

DESCRIPTION

Sr.01

Circuit A Loss of Refrigerant Charge

Sr.02

Circuit B Loss of Refrigerant Charge

Sr.04

Water Loop Size Warning

Sr.05

Air Exchanger Cleanliness Warning

Sr.06

Cooler Pump 1 Servicing Required

Sr.07

Cooler Pump 2 Servicing Required

Sr.08

Condenser Pump 1 Servicing Required

Sr.09

Condenser Pump 2 Servicing Required

Sr.10

Water Filter Servicing Required

Sr.11

Compressor A Oil Filter Servicing Required

Sr.12

Compressor B Oil Filter Servicing Required

Action to be Taken — None.

Reset Method — Manual, after the service has been completed.

Possible Causes — If the Sr-01, 02, or 03 conditions are encountered, check the following items:

sensor wiring to the Main Base Board

sensor for accuracy

Compressor Motor Temperature Too High

Alarm 132-01 — Circuit A (A1.01)

Alarm 133-01 — Circuit B (B1.01)

Criteria for Trip — The alarm criteria are checked when the compressor is ON. This alarm will be generated if:

The temperature is greater than 245 F (118 C) and it has been greater than 212 F (100 C) for 10 consecutive seconds.

The compressor temperature is greater than 232 F (111 C) for 90 seconds (but less than 250 F [120 C]).

Action to be Taken — The circuit shuts down immediately.

Reset Method — Manual

Possible Causes — If this condition is encountered, check the following items:

faulty wiring and loose plugs

faulty CPM board

Compressor Motor Temperature Out of Range

Alarm 132-02 — Circuit A (A1.02)

Alarm 133-02 — Circuit B (B1.02)

Criteria for Trip — The alarm criterion is checked when the compressor is ON. This alarm will be generated if: the temper- ature is greater than 245 F (118 C) and it has NOT been greater than 212 F (100 C) for 10 consecutive seconds.

Action to be Taken — The compressor will be stopped.

Reset Method — Manual

Possible Causes — If this condition is encountered, check the following items:

faulty compressor temperature thermistor

faulty wiring and loose plugs

faulty CPM board

Compressor High Pressure Switch Protection

Alarm 132-03 — Circuit A (A1.03)

Alarm 133-03 — Circuit B (B1.03)

Criteria for Trip — The alarm criterion is checked when the compressor is ON. This alarm will be generated if the circuit high-pressure switch (HPS) opens for more than 2 seconds. The CPM board monitors the HPS switch.

Action to be Taken — The compressor will be stopped. Reset Method — Manual (reset button on switch)

Possible Causes — If this condition is encountered, check the following items:

loss of condenser water flow

condenser pump failure

compressor operating beyond the operation envelope

faulty high pressure switch or wiring

faulty CPM board

Compressor Overcurrent

Alarm 132-04 — Circuit A (A1.04)

Alarm 133-04 — Circuit B (B1.04)

Criteria for Trip — The alarm criterion is checked when the compressor is ON. This alarm will be generated if the CPM board detects a motor current greater than 93% MTA (must trip amps) and less than 2 times that for more than 1.7 seconds. Action to be Taken — The compressor will be stopped.

Reset Method — Manual

Possible Causes — If this condition is encountered, check the following items:

Compressor operating beyond the operation envelope.

Incorrect MTA setting.

Compressor Locked Rotor

Alarm 132-05 — Circuit A (A1.05)

Alarm 133-05 — Circuit B (B1.05)

Criteria for Trip — The alarm criterion is checked during start-up when the compressor is ON. This alarm will be gener- ated if the CPM board detects a high motor current compared with the MTA (must trip amps) setting for more than 450 ms.

Action to be Taken — The compressor will be stopped.

Reset Method — Manual

Possible Causes — If this condition is encountered, check the following items:

compressor mechanical failure

unloader slide valve failure

compressor motor failure

Compressor Phase Loss

Alarm 132-06 — Circuit A L1 (A1.06)

Alarm 133-06 — Circuit B L1 (B1.06)

Alarm 132-07 — Circuit A L2 (A1.07)

Alarm 133-07 — Circuit B L2 (B1.07)

Alarm 132-08 — Circuit A L3 (A1.08)

Alarm 133-08 — Circuit B L3 (B1.08)

Criteria for Trip — The alarm criteria are checked during startup when the compressor is ON. This alarm will be gener- ated if:

The current unbalance on any of the 3 phases is greater than 48% for more than 1 second continuously during start-up.

The current unbalance on any of the 3 phases is greater than 48% for more than 2 seconds continuously during runtime.

Action to be Taken — The compressor will be stopped.

Reset Method — Manual

Possible Causes — If this condition is encountered, check the following items:

power failure

blown fuse or tripped circuit breaker

power wiring errors or loose terminals

Compressor Low Current

Alarm 132-09 — Circuit A (A1.09)

Alarm 133-09 — Circuit B (B1.09)

Criteria for Trip — The alarm criteria are checked when the compressor is ON. This alarm will be generated if:

The current is less than 15% MTA on all three legs for more than 1 second for Wye-Delta start units.

If the current is less than 15% of MTA on all three legs for more than 1 second for direct start units.

81

Page 81
Image 81
Carrier 30XW150-400 specifications Service Maintenance Alert Codes, Action to be Taken - None, Reset Method - Manual