APPENDIX B — NAVIGATOR™ DISPLAY TABLES

MODE — RUN STATUS

ITEM

EXPANSION

UNITS

RANGE

COMMENT

WRITE

CCN TABLE

CCN POINT

PAGE

STATUS

NO.

 

 

 

 

 

 

 

VIEW

AUTO DISPLAY

 

 

 

 

 

 

 

EWT

Entering Fluid Temp

XXXX.X

0-100

 

 

STATEGEN

COOL_EWT

44

LWT

 

(deg F/deg C)

 

 

 

 

 

 

Leaving Fluid Temp

XXX.X

0-100

 

 

STATEGEN

COOL_LWT

44

SETP

 

(deg F/deg C)

 

 

 

 

 

 

Active Setpoint

XXX.X

0-100

 

 

GENUNIT

SP

35, 55

CTPT

 

(deg F/deg C)

 

 

 

 

 

 

Control Point

XXX.X

0-100

 

 

GENUNIT

CTRL_PNT

35

STAT

Unit Run Status

(deg F/deg C)

Off

 

 

GENUNIT

STATUS

22-25

 

 

 

 

 

 

Running

 

 

 

 

 

 

 

 

Stopping

 

 

 

 

 

OCC

 

 

Delay

 

 

 

 

 

Occupied

 

NO/YES

 

 

GENUNIT

CHIL_OCC

22-25

CTRL

Status Unit Control Type

 

Local Off

 

 

GENUNIT

ctr_type

22-25

 

 

 

Local On

 

 

 

 

 

 

 

 

CCN

 

 

 

 

 

CAP

 

 

Remote

 

 

 

 

 

Percent Total Capacity

XXX (%)

0-100

 

 

GENUNIT

CAP_T

 

CAP. A

Percent Capacity Cir A

XXX (%)

0-100

 

 

GENUNIT

CAPA_T

 

CAP. B

Percent Capacity Cir B

XXX (%)

0-100

 

 

GENUNIT

CAPB_T

 

CAP. C

Percent Capacity Cir C

XXX (%)

0-100

 

 

GENUNIT

CAPC_T

 

CAP. S

Capacity Indicator

XX

0-32

 

 

MAINT

OVER_CAP

43

LIM

Active Demand Limit Val

XXX (%)

0-100

 

 

GENUNIT

DEM-LIM

 

CURR

Actual Chiller Current

XXX (amps)

0-4000

 

 

GENUNIT

TOT_CURR

 

CUR.L

Chiller Current Limit

XXX (amps)

0-4000

 

 

GENUNIT

CURR_LIM

 

ALRM

Alarm State

 

0=Normal

 

 

GENUNIT

ALM

68

 

 

 

1=Partial

 

 

 

 

 

EMGY

 

 

2=Shutdown

 

 

 

 

 

Emergency Stop

 

DSBL/ENBL

 

 

GENUNIT

EMSTOP

 

CH.SS

CCN Chiller Start Stop

 

DSBL/ENBL

 

 

GENUNIT

CHILL_S_S

 

HC.ST

Heat Cool Status

 

0=Cooling

Heating and

 

GENUNIT

HEATCOOL

45

 

 

 

1=Heating

Standby not

 

 

 

 

RC.ST

 

 

2=Standby

supported.

 

 

 

 

Reclaim Select Status

 

NO/YES

Not supported.

 

GENUNIT

reclaim_sel

 

TIME

Time of Day

XX.XX

00:00-23:59

 

 

N/A

TIME

 

MNTH

Month of Year

 

1=January

 

 

N/A

moy

 

 

 

 

2=February

 

 

 

 

 

 

 

 

3=March

 

 

 

 

 

 

 

 

4=April

 

 

 

 

 

 

 

 

6=May

 

 

 

 

 

 

 

 

6=June

 

 

 

 

 

 

 

 

7=July

 

 

 

 

 

 

 

 

8=August

 

 

 

 

 

 

 

 

9=September

 

 

 

 

 

 

 

 

10=October

 

 

 

 

 

 

 

 

11=November

 

 

 

 

 

DATE

 

 

12=December

 

 

 

 

 

Day of Month

XX

1-31

 

 

N/A

dom

 

YEAR

Year of Century

XX

00-99

 

 

N/A

yoc

 

RUN

MACHINE STARTS/HOURS

 

 

 

 

 

 

 

HRS.U

Machine Operating Hours

XXXX (hours)

0-999000*

 

forcible

 

hr_mach

 

STR.U

Machine Starts

XXXX

0-9999*

 

forcible

STRTHOUR

st_mach

 

HR.P1

Water Pump 1 Run Hours

XXXX (hours)

0-999000*

Not supported.

forcible

FANHOURS

hr_cpum1

 

HR.P2

Water Pump 2 Run Hours

XXXX (hours)

0-999000*

Not supported.

forcible

FANHOURS

hr_cpum2

 

HR.P3

Condenser Pump 1 Hours

XXXX (hours)

0-999999*

Not supported.

forcible

FANHOURS

hr_hpump1

 

HOUR

COMPRESSOR RUN HOURS

 

 

 

 

 

 

 

HR.A

Compressor A Run Hours

XXXX (hours)

0-999000*

 

forcible

STRTHOUR

hr_cp_a

 

HR.B

Compressor B Run Hours

XXXX (hours)

0-999000*

 

forcible

STRTHOUR

hr_cp_b

 

HR.C

Compressor C Run Hours

XXXX (hours)

0-999000*

 

forcible

STRTHOUR

hr_cp_c

 

STRT

COMPRESSOR STARTS

 

 

 

 

 

 

 

ST.A

Compressor A Starts

XXXX

0-999000*

 

forcible

STRTHOUR

st_cp_a

 

ST.B

Compressor B Starts

XXXX

0-999000*

 

forcible

STRTHOUR

st_cp_b

 

ST.C

Compressor C Starts

XXXX

0-999000*

 

forcible

STRTHOUR

st_cp_c

 

*As data in all of these categories can exceed 9999 the following display strategy is used: From 0-9999 display as 4 digits.

From 9999-99999 display xx.xK From 99900-999999 display as xxxK.