Carrier 30XW150-400 APPENDIX B - NAVIGATOR DISPLAY TABLES cont, MODE - CONFIGURATION cont

Models: 30XW150-400

1 148
Download 148 pages 52.93 Kb
Page 113
Image 113

APPENDIX B — NAVIGATOR™ DISPLAY TABLES (cont)

MODE — CONFIGURATION (cont)

ITEM

EXPANSION

UNITS

RANGE

COMMENT

DEFAULT

CCN TABLE

CCN POINT

PAGE NO.

OPTN

OPTIONS CONFIGURATION

 

 

 

 

 

 

 

CCNA

CCN Address

XXX

1-239

 

1

N/A

CCNA

 

CCNB

CCN Bus Number

XXX

0-239

 

0

N/A

CCNB

 

BAUD

CCN Baud Rate

 

2400

 

9600

N/A

BAUD

 

 

 

 

4800

 

 

 

 

 

 

 

 

9600

 

 

 

 

 

 

 

 

19200

 

 

 

 

 

LOAD

 

 

38400

 

 

 

 

 

Loading Sequence Select

 

Equal

 

EQUAL

USER

lead_cir

29

LLCS

 

 

Staged

 

 

 

 

 

Lead/Lag Circuit Select

 

Automatic

 

AUTOMATIC

USER

seq_typ

29, 55

 

 

 

Cir A Leads

 

 

 

 

 

 

 

 

Cir B Leads

 

 

 

 

 

RL.S

 

 

Cir C Leads

 

 

 

 

 

Ramp Load Select

 

ENBL/DSBL

 

DSBL

USER

ramp_sel

35

DELY

Minutes Off Time

XX (Minutes)

1 to 15

 

1

USER

off_on_d

29

ICE.M

Ice Mode Enable

 

ENBL/DSBL

 

DSBL

USER

ice_cnfg

41

HPUM

Condenser Pumps Sequence

X

No Pump

Not supported.

NO PUMP

 

hpum_seq

47

 

 

 

1 Pump Only

 

 

 

 

 

 

 

 

2 Pumps Auto

 

 

 

 

 

 

 

 

PMP 1 Manual

 

 

 

 

 

PUMP

 

 

PMP 2 Manual

 

NO PUMP

USER

pump_seq

28, 47

Cooler Pumps Sequence

 

No Pump

 

 

 

 

1 Pump Only

 

 

 

 

 

 

 

 

2 Pumps Auto

 

 

 

 

 

 

 

 

PMP 1 Manual

 

 

 

 

 

ROT.P

 

 

PMP 2 Manual

 

 

 

 

 

Pump Rotation Delay

XXXX (hours)

24 to 3000

Not supported.

48

USER

pump_del

28, 55

PM.PS

Periodic Pump Start

 

NO-YES

Not supported.

NO

USER

pump_per

28, 55

P.SBY

Stop Pump In Standby

 

NO-YES

Not supported.

NO

USER

pump_sby

 

P.LOC

Flow Checked if Pmp Off

 

NO-YES

Not supported.

YES

USER

pump_loc

28

LS.ST

Night Low Noise Start

XX.XX

00.00-23.59

 

00.00

USER

nh_start

 

LS.ND

Night Low Noise End

XX.XX

00-00-23.59

 

00.00

USER

nh_end

 

LS.LT

Low Noise Capacity Lim

XXX (%)

0-100

 

100

USER

nh_limit

55

RV.AL

Reverse Alarms Relay

 

NO-YES

 

NO

USER

al_rever

 

OA.TH

Heat Mode OAT Threshold

XX.X

 

Not supported.

5 F

USER

heat_th

 

FREE

 

(deg F/deg C)

 

 

 

 

 

 

Free Cooling OAT Limit

XX.X

 

Not supported.

32.0

USER

free_oat

 

CUR.S

Current Limit Select

(deg F/deg C)

NO/YES

 

NO

 

curr_sel

39-41

 

 

 

CUR.F

Current Limit at 100%

XXXX

0 to 5000

 

2000

 

curr_ful

40-41

RSET

RESET, DEMAND LIMIT, MASTER/SLAVE

 

 

 

 

 

 

CRST

Cooling Reset Type

 

No Reset

 

NO RESET

USER

cr_sel

33, 36, 55

 

 

 

 

 

Out Air Temp

 

 

 

 

 

 

 

 

Delta T Temp

 

 

 

 

 

 

 

 

4-20 mA Input

 

 

 

 

 

HRST

 

 

Space Temp

 

 

 

 

 

Heating Reset Type

 

No Reset

Not supported.

NO RESET

USER

hr_sel

 

 

 

 

Out Air Temp

 

 

 

 

 

 

 

 

Delta T Temp

 

 

 

 

 

DMDC

 

 

4-20 mA Input

 

 

 

 

 

Demand Limit Select

 

None

 

NONE

USER

lim_sel

39-41, 55

 

 

 

Switch

 

 

 

 

 

DMMX

mA for 100% Demand Limit

XX.X (mA)

4-20 mA Input

 

0.0

USER

lim_mx

40, 41

 

 

DMZE

mA for 0% Demand Limit

XX.X (mA)

 

 

0.0

USER

lim_ze

40, 41

MSSL

Master/Slave Select

 

Disable

 

DISABLE

MST_SLV

ms_sel

32-35, 55

 

 

 

Master

 

 

 

 

 

SLVA

 

 

Slave

 

 

 

 

 

Slave Address

XXX

1-236

 

2

MST_SLV

slv_addr

29, 32-35

LLBL

Lead/Lag Balance Select

 

Always Lead

 

Always

MST_SLV

ll_bal

29, 32-35,

 

 

 

Lag if Fail

 

Lead

 

 

54

LLBD

 

 

Runtime Sel

 

 

 

 

 

Lead/Lag Balance Delta

XXX (hours)

40-400

 

168

MST_SLV

ll_bal_d

29, 32-35

LLDY

Lead/Lag Delay

XX (minutes)

2-30

 

10

MST_SLV

lsrt_tim

30, 32-35,

LL.ER

 

 

 

 

 

 

 

54

Start if Error Higher

XX.X

3-18

 

4

MST_SLV

start_dt

30, 32-35

LAG.M

 

(deg F/deg C)

 

 

 

 

 

 

Lag Minimum Running Time

XXX

0-150

 

0

MST_SLV

lag_mini

30, 32-35

LAGP

Lag Unit Pump Select

(min)

OFF if U stp

 

OFF if U stp

MST_SLV

lag_pump

30, 32-35,

 

 

LPUL

 

 

ON if U stp

 

 

 

 

54

Lead Pulldown Time

XX (minutes)

0-60

 

0

MST_SLV

lead_pul

30, 32-35,

SERI

 

 

 

 

 

 

 

54

Chillers in Series

 

NO/YES

 

 

 

ll_serie

29, 32-35

113

Page 113