Carrier 30XW150-400 Control Module Communication, Energy Management Module EMM Inputs and Outputs

Models: 30XW150-400

1 148
Download 148 pages 52.93 Kb
Page 17
Image 17
Table 9 — Energy Management Module (EMM) Inputs and Outputs

Table 9 — Energy Management Module (EMM) Inputs and Outputs

INPUT/OUTPUT

DESCRIPTION

I/O TYPE

DISPLAY MODULE POINT NAME

CONNECTION POINT

4-20 mA Demand Limit

4-20 mA Demand Limit

4-20 mA*

Limit 4-20 mA Signal, DMD

EMM-J7B-CH6

4-20 mA Temperature

4-20 mA Temperature Reset/

4-20 mA*

Reset/Setpnt 4-20 mA Signal, RSET

EMM-J7A-CH5

Reset/Cooling Setpoint

Cooling Set point

 

 

 

 

 

Demand Limit SW2

Demand Limit Step 2

Switch Input

Switch Limit Setpoint 2, DLS2

EMM-J4-CH9

Ice Done

Ice Done Switch

Switch Input

Ice Done Storage Switch, ICE.D

EMM-J4-CH11A

Occupancy Override

Occupied Schedule Override

Switch Input

Occupied Override Switch, OCCS

EMM-J4-CH8

Remote Lockout Switch

Chiller Lockout

Switch Input

Remote Interlock Switch, RLOC

EMM-J4-CH10

SPT

Space Temperature Thermistor

10k Thermistor

Optional Space Temp, SPT

EMM-J6-CH2

% Total Capacity

Percent Total Capacity Output

0-10 vdc

Chiller Capacity Signal, CATO

EMM-J8-CH7

RUN R

Run Relay

Relay

Running Status, RUN

EMM-J3-CH25

SHD R

Shutdown Relay

Relay

Shutdown Indicator State, SHUT

EMM-J3-CH24

CA_S

Run Status for Circuit A

Relay

Compressor A Run Status, Q_RUN_A

EMM-J2A-CH17

CB_S

Run Status for Circuit B

Relay

Compressor B Run Status, Q_RUN_B

EMM-J2A-CH18

* A field-supplied 1/2 watt 250 ohm resistor is required across terminals TB6-1,2 (CH6) and/or TB6-3, 4 (CH5).

Local Equipment Network — Information is trans- mitted between modules via a 3-wire communication bus or LEN (Local Equipment Network). External connection to the LEN bus is made at TB3.

Board Addresses — All boards (except the Main Base Board and Energy Management Module Board) have 8-position DIP switches.

Touch Pilot™ Display — The Touch Pilot display port connections are shown in Table 10. Wiring is shown in Fig. 13.

Control Module Communication

RED LED — Proper operation of the control boards can be visually checked by looking at the red status LEDs (light- emitting diodes). When operating correctly, the red status LEDs will blink in unison at a rate of once every 2 seconds. If the red LEDs are not blinking in unison, verify that correct power is being supplied to all modules. Be sure that the Main Base Board (MBB) is supplied with the current software. If necessary, reload current software. If the problem still persists, replace the MBB. A red LED that is lit continuously or blink- ing at a rate of once per second or faster indicates that the board should be replaced.

GREEN LED — All boards have a green LEN (SIO) LED which should be blinking whenever power is on. If the LEDs are not blinking as described check LEN connections for

potential communication errors at the board connectors. See input/output Tables 3-10 for LEN connector designations. A 3-wire bus accomplishes communication between modules. These 3 wires run in parallel from module to module. The J9A connector on the MBB provides communication directly to the Navigator™ display module.

YELLOW LED — The MBB has one yellow LED. The Carrier Comfort Network® (CCN) LED will blink during times of network communication.

Table 10 — Touch Pilot™ Display Port

Connections

CONNECTOR

PIN

FUNCTION

 

 

1

24VAC +

J1

(Power)

2

24VAC -

 

 

3

Earth Ground

 

 

1

RS485 Port (D+)

J2

(COM1)

2

RS485 Port (GND)

 

 

3

RS485 Port (D-)

 

 

1

24VAC (+)

 

 

2

RS485 Port (D+)

J3

(RJ11)

3

RS485 Port (GND)

4

Unused (no connect)

 

 

 

 

5

RS485 Port (D-)

 

 

6

24VAC(-)

Fig. 13 — Touch Pilot™ Display Wiring

17

Page 17
Image 17
Carrier 30XW150-400 specifications Control Module Communication, Energy Management Module EMM Inputs and Outputs