Carrier 30XW150-400 specifications Default 1.0 F

Models: 30XW150-400

1 148
Download 148 pages 52.93 Kb
Page 35
Image 35

Table 31 — Dual Slave Chiller Control Parameters for Series Applications with Navigator Display

ITEM

ITEM EXPANSION

PATH

VALUE

MSSL

Master/Slave Select

ConfigurationRSET

Slave

Default: Disable

 

 

 

 

 

 

Must be set to the Slave Chiller’s address.

SLVA

 

ConfigurationRSET

The master and slave chiller must have

Slave Address

different addresses and be on the same

 

 

 

Bus Number

 

 

 

Default: 2

LLBL

 

ConfigurationRSET

Range: Always Lead, Lag if Fail,

Master Lead Lag Select

Runtime Sel

 

 

 

Default: Always Lead

LLBD

Lead/Lag Balance Delta

ConfigurationRSET

Range: 40 to 400 hours

Default: 168 hours

 

 

 

LLDY

Lag Start Delay

ConfigurationRSET

Range: 2 to 30 minutes

Default: 10 minutes

 

 

 

LL.ER

Start If Error Higher

ConfigurationRSET

Range: 3.0 to 18 ΔF (1.7 to 10.0 ΔC)

Default: 4.0 ΔF (2.2 ΔC)

 

 

 

LAG.M

Lag Unit Pump Select

ConfigurationRSET

Range: Off If U Stp, On If U Stop

Default: Off If U Stp

 

 

 

LPUL

Lead Pulldown Time

ConfigurationRSET

Range: 0 to 60 minutes

Default: 0 minutes

 

 

 

SERI

Chillers in Series

ConfigurationRSET

YES

Default: NO

 

 

 

OPER

Operating Control Type

Operating ModesSLCT

CCN Control

DUAL CHILLER PUMP CONTROL FOR SERIES CHILLER APPLICATIONS — Pump control for series chill- er applications is controlled by the master chiller only. The control of the slave chiller is directed through commands emit- ted by the master chiller. The slave chiller has no action in master/slave operations. The slave chiller only verifies that CCN communication with the master chiller is present. See the Dual Chiller Sequence of Operation section on page 54.

Ramp Loading — Ramp Loading limits the rate of change of the leaving fluid temperature. If the unit is in a Cool- ing mode and configured for Ramp Loading Select (Ramp Loading Select, RL.S), the control makes two comparisons before deciding to increase capacity. First, the control calcu- lates the temperature difference between the control point and leaving fluid temperature. If the difference is greater than 4° F (2.2° C) and the rate of change (°F or °C per minute) is more than the configured Cool Ramp Loading rate (Cooling Ramp Loading, CRMP), then the control does not allow any increase of capacity.

To configure this option with the Touch Pilot display:

DISPLAY NAME

PATH

LINE NO.

VALUE

 

Ramp Loading

Main Menu

5

Yes

 

Select

ConfigUSER

 

 

 

 

Cooling Ramp

Main Menu

 

Range: 0.2 to 2.0 °F

14

(0.1 to 1.1

°C)

Loading

Setpoint

 

Default: 1.0 °F (0.5

°C)

 

 

 

To configure this option with the Navigator display:

ITEM

ITEM

PATH

 

VALUE

EXPANSION

 

 

 

 

 

RL.S

Ramp Load

ConfigurationOPTN

Yes

 

Select

 

 

 

 

 

CRMP

Cool Ramp

SetpointsCOOL

Range:

0.2 to 2.0 °F

 

(0.1 to 1.1 °C)

 

Loading

 

Default:

1.0 °F (0.5 °C)

 

 

 

Temperature Reset — Temperature reset is a value added to the basic leaving fluid temperature set point and the resulting sum of these values is the new control point. When a non-zero temperature reset is applied, the chiller controls to the new control point, not the set point. The type of temperature re- set is configured with the Cooling Reset Type (Cooling Reset Select, CRST) variable. Types of temperature reset are avail- able: Return Water Reset, Space Temperature Reset, and 4-20 mA Temperature Reset.

Under normal operation, the chiller will maintain a constant entering or leaving fluid temperature, based on the configura- tion, approximately equal to the chilled fluid set point. As the cooler load varies, the cooler fluid temperature difference will change in proportion to the load. For example, if the chiller was selected for a Entering to Leaving Water Temperature difference of 10 F (5.5 C) at full load, at 50% load the tempera- ture difference would be 5 F (2.2 C). See Fig. 19. Because the change in temperature through the cooler is a measure of the building load, the temperature difference reset is the average building load. Usually the chiller size and fluid temperature set point are selected based on a full-load condition. At part load, the fluid temperature set point may be lower than required. If the fluid temperature were allowed to increase at part load, the efficiency of the machine would increase. The chiller can also be set for return water temperature control. See Fig. 20.

Other indirect means of estimating building load and con- trolling temperature reset are also available and are discussed below.

To verify that reset is functioning correctly, subtract the Set- point Select (Current Setpoint, SETP) from the Control Point (Control Point, CTPT) to determine the degrees reset.

RETURN WATER RESET — The control system is capable of performing fluid temperature reset based on cooler fluid temperature difference. Because the change in temperature through the cooler is a measure of the building load, the tem- perature difference reset is, in effect, an average building load reset method.

Return Water Temperature Reset allows for the chilled water temperature set point to be reset upward as a function of the fluid temperature difference (building load).

NOTE: Return Water Temperature Reset should not be used with variable cooler flow rate systems.

To use Return Water Temperature Reset, four variables must be configured. Cooling Reset Type (Cooling Reset Select, CRST) must be enabled. The variable Delta T No Reset Temp (Delta T No Reset Value, CRT1) should be set to the cooler temperature difference (T) where no chilled water tem- perature reset should occur. The variable Delta T Full Reset Temp (Delta T Full Reset Value, CRT2) should be set to the cooler temperature difference where the maximum chilled water temperature reset should occur. The variable Degrees Cool Reset (Cooling Reset Deg. Value, DGRC) should be set to the maximum amount of reset desired.

35

Page 35
Image 35
Carrier 30XW150-400 specifications Default 1.0 F