Carrier 30XW150-400 specifications APPENDIX A - TOUCH PILOT DISPLAY TABLES cont

Models: 30XW150-400

1 148
Download 148 pages 52.93 Kb
Page 99
Image 99

APPENDIX A — TOUCH PILOT™ DISPLAY TABLES (cont)

99

TOUCH PILOT DESCRIPTION

TOUCH PILOT

TOUCH PILOT PATH

LINE

READ/

CCN TABLE NAME

POINT NAME

WRITE

 

 

 

 

Pump Inlet Pressure

 

 

 

 

 

Circuit A

fc_inp_a

MAIN MENU\Status\FREECOOL

17

RO

Status Display Tables\FREECOOL

Circuit B

fc_inp_b

MAIN MENU\Status\FREECOOL

27

RO

Status Display Tables\FREECOOL

Circuit C

fc_inp_c

MAIN MENU\Status\FREECOOL

37

RO

Status Display Tables\FREECOOL

Pump Outlet Pressure

 

 

 

 

 

Circuit A

fc_oup_a

MAIN MENU\Status\FREECOOL

18

RO

Status Display Tables\FREECOOL

Circuit B

fc_oup_b

MAIN MENU\Status\FREECOOL

28

RO

Status Display Tables\FREECOOL

Circuit C

fc_oup_c

MAIN MENU\Status\FREECOOL

38

RO

Status Display Tables\FREECOOL

NB Fans on Varifan Cir A

varfan_a

MAIN MENU\Service\FACTORY

5

RW

Service Configuration Tables\FACTORY

NB Fans on Varifan Cir B

varfan_b

MAIN MENU\Service\FACTORY

6

RW

Service Configuration Tables\FACTORY

NB Fans on Varifan Cir C

varfan_c

MAIN MENU\Service\FACTORY

7

RW

Service Configuration Tables\FACTORY

Next Occupied Day

NXTOCDAY

MAIN MENU\Maint\OCCDEFCM\OCC1PO1S

7

RO

Maintenance Display Tables\OCCDEFCM\OCC1PO1S

Next Occupied Day

NXTOCDAY

MAIN MENU\Maint\OCCDEFCM\OCC2PO2S

7

RO

Maintenance Display Tables\OCCDEFCM\OCC2PO2S

Next Occupied Time

NXTOCTIM

MAIN MENU\Maint\OCCDEFCM\OCC1PO1S

8

RO

Maintenance Display Tables\OCCDEFCM\OCC1PO1S

Next Occupied Time

NXTOCTIM

MAIN MENU\Maint\OCCDEFCM\OCC2PO2S

8

RO

Maintenance Display Tables\OCCDEFCM\OCC2PO2S

Next Session Allowed In

fc_next

MAIN MENU\Status\FREECOOL

6

RO

Status Display Tables\FREECOOL

Next Unoccupied Day

NXTUNDAY

MAIN MENU\Maint\OCCDEFCM\OCC1PO1S

9

RO

Maintenance Display Tables\OCCDEFCM\OCC1PO1S

Next Unoccupied Day

NXTUNDAY

MAIN MENU\Maint\OCCDEFCM\OCC2PO2S

9

RO

Maintenance Display Tables\OCCDEFCM\OCC2PO2S

Next Unoccupied Time

NXTUNTIM

MAIN MENU\Maint\OCCDEFCM\OCC1PO1S

10

RO

Maintenance Display Tables\OCCDEFCM\OCC1PO1S

Next Unoccupied Time

NXTUNTIM

MAIN MENU\Maint\OCCDEFCM\OCC2PO2S

10

RO

Maintenance Display Tables\OCCDEFCM\OCC2PO2S

Night Control Capacity Limit

nh_limit

MAIN MENU\Config\USER

41

RW

Configuration Tables\USER

Night Control End Hour

nh_end

MAIN MENU\Config\USER

40

RW

Configuration Tables\USER

Night Control Start Hour

nh_start

MAIN MENU\Config\USER

39

RW

Configuration Tables\USER

Night Low Noise Active

Mode_09

MAIN MENU\Status\MODES

10

RO

Status Display Tables\MODES

OAT Broadcast Bus #

oatbusnm

MAIN MENU\Config\BRODEFS

4

RW

Configuration Tables\BRODEFS\BROCASTS

OAT Broadcast Element #

oatlocad

MAIN MENU\Config\BRODEFS

5

RW

Configuration Tables\BRODEFS\BROCASTS

OAT Full Reset Value

oatcr_fu

MAIN MENU\Setpoint\SETPOINT

6

RW

Setpoint Configuration Tables\SETPOINT

OAT Full Reset Value

oathr_fu

MAIN MENU\Setpoint\SETPOINT

20

RW

Setpoint Configuration Tables\SETPOINT

OAT No Reset Value

oatcr_no

MAIN MENU\Setpoint\SETPOINT

5

RW

Setpoint Configuration Tables\SETPOINT

OAT No Reset Value

oathr_no

MAIN MENU\Setpoint\SETPOINT

19

RW

Setpoint Configuration Tables\SETPOINT

LEGEND

RO — Read Only

RW — Read/Write

Page 99
Image 99
Carrier 30XW150-400 specifications APPENDIX A - TOUCH PILOT DISPLAY TABLES cont