Carrier 30XW150-400 Disassembly and Assembly of EXV Motor, EXV Modes and Submodes, A30-4072ef

Models: 30XW150-400

1 148
Download 148 pages 52.93 Kb
Page 62
Image 62
DISASSEMBLY

DISASSEMBLY

ASSEMBLY CLOSED A30-4072ef

Fig. 44 — Disassembly and Assembly of EXV Motor 27mm / 11/16''

Table 40 — EXV Modes and Submodes OPEN

NOTE: Open valve in Quick Test sub-mode before disassembling.

OPEN VALVE IN QUICK TEST SUB-MODE BEFORE DISASSEMBLING

ASSEMBLY

CLOSED

50Nm (36 ft-lb)+ 30°

Table 41 — Color Indicators whenManual background OPEN

EF05BD271 NV 32.5mm Manual background

EF05BD331 NV 36mm

NOTES:

1.Push down on valve piston to close valve before assembling.

2.After valve is assembled close valve in Quick Test sub-mode or cycle power before opening service valve.

Manual background 27mm / 11/16''

GASKET

A30-4072ef

Fig. 44 — Disassembly and Assembly of EXV Motor

Table 40 — EXV Modes and Submodes

EXV TYPE AND CIRCUIT

TOUCH PILOT™ PATH

NAVIGATOR™ PATH

EXV, Circuit A

Main MenuStatusQCK_TST1Q_EXVA

Service Test ModeQUICEXV.A

EXV, Circuit B

Main MenuStatusQCK_TST1Q_EXVB

Service Test ModeQUICEXV.B

Economizer EXV, Circuit A

Main MenuStatusQCK_TST1Q_ECO_A

Service Test ModeQUICECO.A

Economizer EXV, Circuit B

Main MenuStatusQCK_TST1Q_ECO_B

Service Test ModeQUICECO.B

Table 41 — Color Indicators when

Moisture is Present in Refrigerant

 

R-134a,

R-134a,

COLOR INDICATOR

75 F (24 C)

125 F (52 C)

 

(ppm)

(ppm)

Green — Dry

<30

<45

Yellow-green — Caution

30-100

45-170

Yellow — Wet

>100

>170

Liquid Line Service Valve — This valve is located immediately ahead of filter drier, and has a 1/4-in. access connection for field charging. In combination with compressor discharge service valve, each circuit can be pumped down into the high side for servicing.

62

Page 62
Image 62
Carrier 30XW150-400 specifications Disassembly and Assembly of EXV Motor, EXV Modes and Submodes, A30-4072ef