Carrier 30XW150-400 APPENDIX C - CCN TABLES cont, Configuration Tables, chiller. Daylight savings

Models: 30XW150-400

1 148
Download 148 pages 52.93 Kb
Page 124
Image 124

APPENDIX C — CCN TABLES (cont)

CONFIGURATION TABLES

TABLE

DISPLAY NAME

RANGE

DEFAULT

UNITS

POINT NAME

!CtlrID/PD5_XAXQ

Device Name

8 chars

30XW

 

 

 

Description

24 chars

PRO-DIALOG 5

 

DevDesc

 

Location

24 chars

30XA XQ XW

 

Location

 

 

 

 

Software Part Number

16 chars

CSA-SR-20C47nnnn

 

PartNum

 

Model Number

20 chars

 

 

ModelNum

 

Serial Number

12 chars

 

 

SerialNo

 

Reference Number

24 chars

 

 

RefNum

 

CCN Bus Number

0-239

0

 

CCNB

 

CCN Element Number

1-239

1

 

CCNA

 

CCN Baud Rate

9600

9600

 

BAUD

 

 

19200

 

 

 

 

 

38400

 

 

 

ALARMDEF/

Alarm Routing Control

0-11111111

00000000

 

ALRM_CNT

ALARMS01

Alarm Equipment Priority

0-7

4

 

EQP_TYP

 

Comm Failure Retry Time

1-240

10

min

RETRY_TM

 

Realarm Time

1-255

30

min

RE_ALARM

 

Alarm System Name

8 chars

PRO_XAXQ

 

ALRM_NAM

BRODEFS/

Activate

0=Unused

2

ccnbroad

BROCASTS

 

1=Broadcast time,

 

 

 

 

 

date, holiday flag and

 

 

 

 

 

OAT.

 

 

 

 

 

2=For Standalone

 

 

 

 

 

chiller. Daylight savings

 

 

 

 

 

time & holiday determi-

 

 

 

 

 

nation will be done

 

 

 

 

 

without broadcasting

 

 

 

 

OAT Broadcast

through the bus.

 

 

 

 

 

 

 

 

 

Bus #

0 to 239

0

 

oatbusnm

 

Element #

0 to 239

0

 

oatlocad

 

 

 

 

 

 

 

DAYLIGHT SAVING SELECT

Disable/Enable

Disable

 

dayl_sel

 

ENTERING

 

 

 

 

 

Month

1 to 12

3

 

startmon

 

Day of week* (1=Monday)

1 to 7

7

 

startdow

 

Week Number of Month†

1 to 5

5

 

startwom

 

LEAVING

 

 

 

 

 

Month

1 to 12

10

 

Stopmon

 

Day of week* (1=Monday)

1 to 7

7

 

Stoptdow

 

Week Number of Month†

1 to 5

5

 

stopwom

HOLIDAY/HOLDY_nn

Holiday Start Month

0-12

0

 

HOL_MON

nn = 01 to 16

Start Day

0-31

0

 

HOL_DAY

 

Duration (days)

0-99

0

 

HOL_LEN

OCCDEFCS/

Timed Override Hours

0-4

0

 

OVR_EXT

OCCnP0nS

Period 1 DOW (MTWTFSSH)

0/1

11111111

 

DOW1

n = 1 or 2

Occupied From

00:00-24:00

00:00

 

OCCTOD1

 

Occupied To

00:00-24:00

24:00

 

UNOCTOD1

 

Period 2 DOW (MTWTFSSH)

0/1

11111111

 

DOW2

 

Occupied From

00:00-24:00

00:00

 

OCCTOD2

 

Occupied To

00:00-24:00

00:00

 

UNOCTOD2

 

Period 3 DOW (MTWTFSSH)

0/1

00000000

 

DOW3

 

Occupied From

00:00-24:00

00:00

 

OCCTOD3

 

Occupied To

00:00-24:00

00:00

 

UNOCTOD3

 

Period 4 DOW (MTWTFSSH)

0/1

00000000

 

DOW4

 

Occupied From

00:00-24:00

00:00

 

OCCTOD4

 

Occupied To

00:00-24:00

00:00

 

UNOCTOD4

 

Period 5 DOW (MTWTFSSH)

0/1

00000000

 

DOW5

 

Occupied From

00:00-24:00

00:00

 

OCCTOD5

 

Occupied To

00:00-24:00

00:00

 

UNOCTOD5

 

Period 6 DOW (MTWTFSSH)

0/1

00000000

 

DOW6

 

Occupied From

00:00-24:00

00:00

 

OCCTOD6

 

Occupied To

00:00-24:00

00:00

 

UNOCTOD6

 

Period 7 DOW (MTWTFSSH)

0/1

00000000

 

DOW7

 

Occupied From

00:00-24:00

00:00

 

OCCTOD7

 

Occupied To

00:00-24:00

00:00

 

UNOCTOD7

 

Period 8 DOW (MTWTFSSH)

0/1

00000000

 

DOW8

 

Occupied From

00:00-24:00

00:00

 

OCCTOD8

 

Occupied To

00:00-24:00

00:00

 

UNOCTOD8

*Day of week where daylight savings time will occur in the morning (at 2:00 am). Daylight savings time occurs on Sunday (7) morning, 1 hour shall be added when entering and 1 hour subtracted when leaving.

†Date once selected (from 1) shall occur in the week number entered. 1: If day of week selected is 7 (Sunday) time change will occur the first Sunday (week number 1) in the month. 5: If day of week selected is 7 (Sunday) time change will occur the last Sunday of the month (week number 4 or 5).

NOTE: nn is software version.

124

Page 124
Image 124
Carrier 30XW150-400 specifications APPENDIX C - CCN TABLES cont, Configuration Tables, chiller. Daylight savings