Carrier 30XW150-400 specifications Alarm Codes cont, valve stuck, faulty oil

Models: 30XW150-400

1 148
Download 148 pages 52.93 Kb
Page 71
Image 71

Table 49 — Alarm Codes (cont)

PREFIX

SUFFIX

ALARM

ALARM DESCRIPTION

REASON FOR ALARM

ACTION TAKEN

RESET

PROBABLE CAUSE

CODE

CODE

NUMBER

BY CONTROL

TYPE

 

 

 

 

 

P

 

11

77

Circuit A Low Suction

 

EXV<5% and either the

Circuit shut down

Manual

Faulty transducer,

 

 

 

 

Superheat

 

 

suction superheat is less

 

 

faulty wiring, faulty

 

 

 

 

 

 

 

than the set point by at

 

 

thermistor, faulty EXV,

 

 

12

78

Circuit B Low Suction

 

 

 

 

 

 

least 5 F or the suction

 

 

or incorrect

 

 

 

 

Superheat

 

 

 

 

 

 

 

 

 

 

temperature is greater

 

 

configuration

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

than MOP set point for

 

 

 

 

 

 

 

 

 

 

more than 5 minutes

 

 

 

 

 

14

80

Interlock Failure

 

 

Lockout Switch Closed

Unit shut down or

Automatic

Lockout Switch Closed

 

 

 

 

 

 

 

 

not allowed to start

 

on EMM board

 

 

28

81

Electrical Box Thermostat

External pump interlock

Unit shut down or

Automatic

External pump off.

 

 

 

 

Failure/Reverse Rotation

open

not allowed to start

 

Faulty jumper wiring

 

 

 

 

 

 

 

 

 

 

when channel not used

 

 

29

82

Loss of communication with

Loss of communication

Unit change to

Automatic

Faulty communication

 

 

 

 

System Manager

 

with an external control

stand-alone

 

wiring, no power

 

 

 

 

 

 

 

device for more than

operation

 

supply to the external

 

 

 

 

 

 

 

2 minutes

 

 

controller

 

 

30

83

Master/Slave communication

Communication between

Unit change to

Automatic

Faulty communication

 

 

 

 

Failure

 

 

the master and slave

stand-alone

 

wiring, no power or

 

 

 

 

 

 

 

machines lost

operation

 

control power to the

 

 

 

 

 

 

 

 

 

 

main base board of

 

 

 

 

 

 

 

 

 

 

either module

 

 

67

84

Circuit A Low Oil Pressure

Oil pressure and suction

Circuit shut down

Automatic, first

Plugged oil filter, faulty

 

 

68

85

Circuit B Low Oil Pressure

pressure differential is

 

occurrence in

oil transducer, oil check

 

 

less than the set point

 

24 hours;

valve stuck, plugged oil

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

manual if

strainer

 

 

 

 

 

 

 

 

 

multiple alarms

 

 

 

 

 

 

 

 

 

 

within 24 hours

 

 

 

70

87

Circuit A Max Oil Filter Differ-

Difference between dis-

Circuit shut down

Manual

Plugged oil filter,

 

 

 

 

ential Pressure

 

 

charge pressure and oil

 

 

closed oil valve, bad oil

 

 

 

 

 

 

 

pressure is greater than

 

 

solenoid, oil check

 

 

71

88

Circuit B Max Oil Filter Differ-

 

 

 

 

50 psi for more than

 

 

valve stuck, faulty oil

 

 

 

 

ential Pressure

 

 

 

 

 

 

 

 

 

 

30 seconds

 

 

pressure transducer

 

 

 

 

 

 

 

 

 

 

 

84

90

Circuit A High Oil Filter Drop

Difference between dis-

Alert generated

Manual

Plugged oil filter

 

 

 

 

Pressure

 

 

charge pressure and oil

 

 

 

 

 

 

 

 

 

 

pressure is greater than

 

 

 

 

 

85

91

Circuit B High Oil Filter Drop

 

 

 

 

 

30 psi for more than

 

 

 

 

 

 

 

Pressure

 

 

 

 

 

 

 

 

 

 

 

5 minutes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75

93

Circuit A Low Oil Level

 

Oil level switch open

Circuit shut down or

Automatic, first

Low oil level, faulty

 

 

76

94

Circuit B Low Oil Level

 

 

not allowed to start

occurrence in

switch, wiring error,

 

 

 

 

 

24 hours;

failed CPM board, oil

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

manual if

solenoid stuck open

 

 

 

 

 

 

 

 

 

multiple alarms

 

 

 

 

 

 

 

 

 

 

within 24 hours

 

MC

 

nn

96

Master chiller configuration

Wrong or incompatible

Unit not allowed to

Automatic

Configuration error

 

 

 

 

error Number 01 to nn

 

configuration data

start in Master-slave

 

 

 

 

 

 

 

 

 

 

control

 

 

FC

 

n0

97

No factory configuration

No Configuration

Unit not allowed to

Automatic

Configuration error

 

 

 

 

 

 

 

 

start

 

 

 

 

nn

98

Illegal factory configuration

Wrong or incompatible

Unit not allowed to

Automatic

Configuration error

 

 

 

 

Number 01 to 04

 

configuration data

start

 

 

P

 

31

99

Unit is in CCN emergency

Emergency stop com-

Unit shut down or

Automatic

Carrier Comfort

 

 

 

 

stop

 

 

mand has been received

not allowed to start

 

Network® Emergency

 

 

 

 

 

 

 

 

 

 

Stop command

 

 

 

 

 

 

 

 

 

 

received

 

 

32

100

Cooler pump #1 fault

 

Pump interlock status

Unit shuts down, if

Manual

Faulty contacts, wiring

 

 

 

 

 

 

 

does not match pump

available, another

 

error or low control

 

 

33

101

Cooler pump #2 fault

 

 

 

 

 

status

pump will start

 

voltage. Configuration

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

error.

 

 

15

102

Condenser Flow Switch

None

Manual

Configuration error,

 

 

 

 

Failure

 

 

 

 

 

faulty wiring or external

 

 

 

 

 

 

 

 

 

 

pump off

 

 

34

103

Circuit A Reclaim Operation

None

Manual

Configuration error

 

 

 

 

Failure

 

 

 

 

 

 

 

 

35

104

Circuit B Reclaim Operation

 

 

 

 

 

 

 

 

Failure

 

 

 

 

 

 

 

 

37

105

Circuit A — High condensing

Multiple capacity over-

Circuit shut down

Automatic

Low or restricted

 

 

 

 

temperature out of compres-

rides due to high

 

 

condenser water flow.

 

 

 

 

sor envelope

 

 

saturated discharge

 

 

Fouled condenser

 

 

38

106

Circuit B — High condensing

temperature

 

 

tubes.

 

 

 

 

temperature out of compres-

 

 

 

 

 

 

 

 

sor envelope

 

 

 

 

 

 

 

 

 

 

LEGEND

 

 

 

 

 

 

CCN

Carrier Comfort Network®

MLV

Minimum Load Valve

 

 

 

CPM

Compressor Protection Module

MOP

Maximum Operating Pressure

 

 

 

EMM

Energy Management Module

MTA

Must Trip Amps

 

 

 

EWT

Entering Water Temperature

SST

Saturated Suction Temperature

 

 

EXV

Electronic Expansion Valve

UL

Underwriters Laboratories

 

 

 

HPS

High Pressure Switch

 

 

 

 

 

 

 

71

Page 71
Image 71
Carrier 30XW150-400 specifications Alarm Codes cont, valve stuck, faulty oil