Carrier 30XW150-400 specifications Alarm Codes cont, A1, B1

Models: 30XW150-400

1 148
Download 148 pages 52.93 Kb
Page 72
Image 72

Table 49 — Alarm Codes (cont)

PREFIX

SUFFIX

ALARM

ALARM DESCRIPTION

REASON FOR ALARM

 

ACTION TAKEN

RESET

PROBABLE CAUSE

CODE

CODE

NUMBER

 

BY CONTROL

TYPE

 

 

 

 

 

 

P

 

40

108

Circuit A — Repeated low

Multiple capacity

 

Circuit shut down

Automatic

Inaccurate

 

 

 

 

suction temp overrides

 

overrides due to low satu-

 

 

 

transducer, faulty EXV,

 

 

 

 

 

 

 

rated suction temperature

 

 

 

low refrigerant charge,

 

 

41

109

Circuit B — Repeated low

 

 

 

 

 

 

 

 

 

plugged or restricted

 

 

 

 

suction temp overrides

 

 

 

 

 

 

 

 

 

 

 

 

 

 

liquid line filter drier.

 

 

 

 

 

 

 

 

 

 

 

 

 

43

111

Low entering water tempera-

Not supported

 

 

 

 

 

ture in heating

 

 

 

 

 

 

 

 

 

73

112

Condenser pump #1 default

 

None

Manual

Faulty contacts, wiring

 

 

74

113

Condenser pump #2 default

 

 

 

 

error or low control

 

 

 

 

 

 

voltage. Configuration

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

error.

 

 

78

114

Circuit A High Discharge

Discharge gas tempera-

 

Circuit shut down

Manual

Faulty transducer/high

 

 

 

 

Temperature

 

 

ture is higher than 212 F

 

 

 

pressure switch, low/

 

 

 

 

 

 

 

for more than 90 seconds

 

 

 

restricted condenser

 

 

79

115

Circuit B High Discharge

 

 

 

 

 

 

 

 

 

flow

 

 

 

 

Temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

81

117

Circuit A Low Economizer

The economizer pressure

 

Circuit shut down

Manual

Faulty transducer,

 

 

 

 

Pressure

 

 

is below the suction pres-

 

 

 

faulty main base board,

 

 

82

118

Circuit B Low Economizer

sure more than 14.5 psi

 

 

 

faulty wiring, closed

 

 

for more than 10 seconds

 

 

 

suction service valve,

 

 

 

 

Pressure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

faulty EXV

 

 

 

 

 

 

 

 

 

 

 

 

 

87

120

Circuit A Slide Valve Control

If 100% load current is

 

None

Manual

Slide valve stuck, inac-

 

 

 

 

Unverifiable

 

 

less than 1.1 times of

 

 

 

curate initial current

 

 

 

 

 

 

 

30% load current, or for

 

 

 

reading

 

 

88

121

Circuit B Slide Valve Control

 

 

 

 

 

1 minute when active

 

 

 

 

 

 

 

 

Unverifiable

 

 

 

 

 

 

 

 

 

 

 

 

cooling setpoint is

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

greater than 32 F.

 

 

 

 

 

 

90

123

Cooler flow switch set point

 

None

Manual

Configuration error

 

 

 

 

configuration failure

 

 

 

 

 

 

 

 

91

124

Cooler flow switch failure

Flow switch open

 

Unit shut down

Manual if unit

Faulty flow switch, low

 

 

 

 

 

 

 

 

 

 

is running,

cooler flow, faulty

 

 

 

 

 

 

 

 

 

 

automatic

wiring, faulty cooler

 

 

 

 

 

 

 

 

 

 

otherwise

pump, faulty main base

 

 

 

 

 

 

 

 

 

 

 

board

Sr

 

nn

128

Service maintenance alert

Field programmed

 

None

Manual

Maintenance required

 

 

 

 

Number # nn

 

 

elapsed time has expired

 

 

 

 

 

 

 

 

 

 

 

for maintenance time

 

 

 

 

A1, B1

01

132-01,

Compressor Motor tempera-

Compressor temperature

 

Circuit shut down

Manual

Economizer EXV fail-

 

 

 

133-01

ture too high

 

 

higher than 232 F for

 

 

 

ure (350,400 only),

 

 

 

 

 

 

 

more than 90 seconds

 

 

 

faulty CPM board,

 

 

 

 

 

 

 

 

 

 

 

low refrigerant charge

 

 

02

132-02,

Compressor Motor tempera-

Compressor temperature

 

Circuit shut down

Manual

Faulty thermistor, faulty

 

 

 

133-02

ture out of range

 

reading out of the range of

 

 

 

wiring, faulty CPM

 

 

 

 

 

 

 

–40 F to 245 F

 

 

 

board

 

 

03

132-03,

Compressor High pressure

HPS input on CPM board

 

Circuit shut down

Manual, press

Loss of condenser air

 

 

 

133-03

switch protection

 

open

 

 

reset button on

flow, operation beyond

 

 

 

 

 

 

 

 

 

 

HPS

compressor envelope,

 

 

 

 

 

 

 

 

 

 

 

faulty high pressure

 

 

 

 

 

 

 

 

 

 

 

switch, faulty wiring,

 

 

 

 

 

 

 

 

 

 

 

faulty CPM board

 

 

04

132-04,

Compressor Over current

CPM board detects high

 

Circuit shut down

Manual

Operating beyond

 

 

 

133-04

 

 

 

motor current compared

 

 

 

compressor envelope,

 

 

 

 

 

 

 

with MTA setting

 

 

 

incorrect configuration

 

 

05

132-05,

Compressor Locked rotor

CPM board detects locked

 

Circuit shut down

Manual

Compressor motor fail-

 

 

 

133-05

 

 

 

rotor current compared

 

 

 

ure, unloader slide

 

 

 

 

 

 

 

with MTA setting

 

 

 

valve failure, compres-

 

 

 

 

 

 

 

 

 

 

 

sor mechanical failure

 

 

06

132-06,

Compressor Phase loss L1

CPM board detects cur-

 

Circuit shut down

Manual

Blown fuse, wiring

 

 

 

133-06

 

 

 

rent unbalance greater

 

 

 

error, loose terminals

 

 

 

 

 

 

 

than 65% for more than

 

 

 

 

 

 

07

132-07,

Compressor Phase loss L2

 

 

 

 

 

 

1 second

 

 

 

 

 

 

 

133-07

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

08

132-08,

Compressor Phase loss L3

 

 

 

 

 

 

 

 

133-08

 

 

 

 

 

 

 

 

 

 

09

132-09,

Compressor Low current

CPM detects motor cur-

 

Circuit shut down

Manual

Power supply discon-

 

 

 

133-09

alarm

 

 

rent less than a certain

 

 

 

nected, blown fuse,

 

 

 

 

 

 

 

percentage of the MTA

 

 

 

wiring error, contact

 

 

 

 

 

 

 

setting, compressor not

 

 

 

deenergized, faulty

 

 

 

 

 

 

 

operating

 

 

 

current toroid high

 

 

 

 

 

 

 

 

 

 

 

pressure switch trip.

 

 

 

 

LEGEND

 

 

 

 

 

 

 

CCN

Carrier Comfort Network®

MLV

Minimum Load Valve

 

 

 

CPM

Compressor Protection Module

MOP

Maximum Operating Pressure

 

 

 

EMM

Energy Management Module

MTA

Must Trip Amps

 

 

 

EWT

Entering Water Temperature

SST

Saturated Suction Temperature

 

 

 

EXV

Electronic Expansion Valve

UL

Underwriters Laboratories

 

 

 

HPS

High Pressure Switch

 

 

 

 

 

 

 

 