APPENDIX F — GLOBAL TIME SCHEDULE CONFIGURATION FOR i-Vu®DEVICE

APPENDIX F — GLOBAL TIME SCHEDULE CONFIGURATION FOR i-Vu®DEVICE

AND CSM CONTROLLER

The following is intended to assist a Carrier technician in configuring a 30XW chiller so either the i-Vu®4.0 or 4.2 de- vice, CCN Global Schedule Master, or a CSM controller can Start and Stop the chiller. The 30XW chiller has unique table naming convention for its Time Schedules that are different than what is used today in CCN. The five steps outlined in the procedures below must be followed in order to have the i-Vu device and CCN products control the chiller.

Step 1 — Chiller Configuration

1.Make sure the chiller is shut down and that the Emergen- cy On/Off Switch (SW2) is in the Off Position and the Enable-Off-Remote (SW1) is in the Disable position.

2.Next, UPLOAD the chiller to assure the configuration is current.

NOTE: This must be done in both NSTV and CVIEW.

3.Change the chiller’s Time Schedule Table Name from OCCyP0xx to OCCPC0xx. See descriptions below.

LOCAL AND NETWORK TIME SCHEDULE DESCRIPTIONS

OCCPC01S — The i-Vu 4.2 device will write to this Time Schedule Table.

OCC2P02S — This is for Dual Setpoint Control and MUST be Configured for 24/7 Occupied when the i-Vu device is writ- ing to OCCPC01S.

OCCPC65E — Used with the i-Vu device or another CCN Global Schedule Master with Single Setpoint Control.

OCC2P02E — This will only be used with Dual Setpoint Con- trol. This is not applicable in this application.

TIME SCHEDULE TABLE NAME CHANGE

NSTV — When using NSTV to edit a Time Schedule Name, the process is the same for both Local (S) or Network (E) Time Schedules.

1.Highlight the chiller, then (at the top menu bar) click on Configure Names…

2.When the dialog box opens, scroll down to find the four time schedules (as seen in Fig. A for Local Schedule or Fig. B for Network Time Schedule). Highlight the desired Time Schedule to edit.

3.At the bottom where it says New name, double click on OCC1P01x and rename it with OCCPC01x click Save click OK.

4.Download the new configuration to the chiller.

5.Cycle power to the MBB (main base board) using SW2 emergency stop.

CVIEW — If using CVIEW to edit a Time Schedule Name, the process is the same for both Local (S) or Network (E) Time Schedules.

1.Highlight the chiller and click Configure Table Names.

2.When the dialog box opens, scroll down to find the six OCC tables.

NOTE: Only the "S" and "E" Schedules are editable.

3.Highlight the Time Schedule OCC1P01x then click Mod- ify…

4.In the new dialog box, rename the schedule OCCPC01x (as seen in Fig. C for Local Schedule or Fig. D for Net- work Time Schedule) then click OK to close this dialog box.

5.Click Close to close the Table Names dialog box.

6.Download the new configuration to the chiller.

7.Cycle power to the MBB (main base board) using SW2 emergency stop.

A30-4851

Fig. A — NTSV Table Name (Local Schedule)

30-4852

Fig. B — NTSV Table Name (Network Schedule)

-4853

Fig. C — CVIEW Table Name (Local Schedule)

0-4854

Fig. D — CVIEW Table Name (Network Schedule)