APPENDIX F — GLOBAL TIME SCHEDULE CONFIGURATION FOR i-Vu®DEVICE

AND CSM CONTROLLER

The following is intended to assist a Carrier technician in configuring a 30XW chiller so either the i-Vu®4.0 or 4.2 de- vice, CCN Global Schedule Master, or a CSM controller can Start and Stop the chiller. The 30XW chiller has unique table naming convention for its Time Schedules that are different than what is used today in CCN. The five steps outlined in the procedures below must be followed in order to have the i-Vu device and CCN products control the chiller.

Step 1 — Chiller Configuration

1.Make sure the chiller is shut down and that the Emergen- cy On/Off Switch (SW2) is in the Off Position and the Enable-Off-Remote (SW1) is in the Disable position.

2.Next, UPLOAD the chiller to assure the configuration is current.

NOTE: This must be done in both NSTV and CVIEW.

3.Change the chiller’s Time Schedule Table Name from OCCyP0xx to OCCPC0xx. See descriptions below.

LOCAL AND NETWORK TIME SCHEDULE DESCRIPTIONS

OCCPC01S — The i-Vu 4.2 device will write to this Time Schedule Table.

OCC2P02S — This is for Dual Setpoint Control and MUST be Configured for 24/7 Occupied when the i-Vu device is writ- ing to OCCPC01S.

OCCPC65E — Used with the i-Vu device or another CCN Global Schedule Master with Single Setpoint Control.

OCC2P02E — This will only be used with Dual Setpoint Con- trol. This is not applicable in this application.

TIME SCHEDULE TABLE NAME CHANGE

NSTV — When using NSTV to edit a Time Schedule Name, the process is the same for both Local (S) or Network (E) Time Schedules.

1.Highlight the chiller, then (at the top menu bar) click on Configure Names…

2.When the dialog box opens, scroll down to find the four time schedules (as seen in Fig. A for Local Schedule or Fig. B for Network Time Schedule). Highlight the desired Time Schedule to edit.

3.At the bottom where it says New name, double click on OCC1P01x and rename it with OCCPC01x click Save click OK.

4.Download the new configuration to the chiller.

5.Cycle power to the MBB (main base board) using SW2 emergency stop.

CVIEW — If using CVIEW to edit a Time Schedule Name, the process is the same for both Local (S) or Network (E) Time Schedules.

1.Highlight the chiller and click Configure Table Names.

2.When the dialog box opens, scroll down to find the six OCC tables.

NOTE: Only the "S" and "E" Schedules are editable.

3.Highlight the Time Schedule OCC1P01x then click Mod- ify…

4.In the new dialog box, rename the schedule OCCPC01x (as seen in Fig. C for Local Schedule or Fig. D for Net- work Time Schedule) then click OK to close this dialog box.

5.Click Close to close the Table Names dialog box.

6.Download the new configuration to the chiller.

7.Cycle power to the MBB (main base board) using SW2 emergency stop.

A30-4851

Fig. A — NTSV Table Name (Local Schedule)

30-4852

Fig. B — NTSV Table Name (Network Schedule)

-4853

Fig. C — CVIEW Table Name (Local Schedule)

0-4854

Fig. D — CVIEW Table Name (Network Schedule)

137

Page 137
Image 137
Carrier 30XW150-400 specifications CSM Controller, Chiller Configuration, 137

30XW150-400 specifications

The Carrier 30XW150-400 series is a line of water-cooled chillers that exemplifies innovation, efficiency, and reliability in commercial cooling solutions. Designed for medium to large-scale applications, this series is ideal for a variety of settings, including commercial buildings, industrial processes, and chilled water systems.

One of the standout features of the Carrier 30XW series is its efficiency. The chillers utilize advanced variable-speed compressor technology, which allows the units to adapt to varying cooling loads while minimizing energy consumption. This technology not only reduces operational costs but also contributes to better environmental sustainability by lowering greenhouse gas emissions.

The 30XW series chillers are equipped with high-efficiency, scroll compressors that operate quietly and provide significant energy savings. By utilizing enhanced economizer controls, these units can achieve higher efficiency ratings, especially in part-load conditions. The result is an impressive Energy Efficiency Ratio (EER) and Seasonal Energy Efficiency Ratio (SEER), making these units a smart choice for energy-conscious businesses.

In terms of reliability, the Carrier 30XW150-400 series features robust construction and an array of safety and monitoring systems. The units come with advanced diagnostics that help in quickly identifying and addressing any operational issues. This proactive approach ensures reliability and minimizes downtime, which is crucial for maintaining optimal temperature controls in critical environments.

Additionally, the chillers incorporate environmentally friendly refrigerants that comply with the latest regulations, making them a sustainable choice for modern commercial applications. Their compact design allows for flexible installation options, and the integrated control systems provide the ability to optimize performance based on specific building management demands.

User-friendly interfaces and remote monitoring capabilities further enhance the ease of operation, allowing facility managers to have real-time insight into performance metrics and system health. This level of control contributes to better maintenance planning and maximizes the lifespan of the equipment.

In summary, the Carrier 30XW150-400 series of water-cooled chillers combines advanced technology, energy efficiency, and reliable performance, making it an ideal solution for various commercial and industrial cooling needs. With its commitment to innovation and sustainability, Carrier continues to set the standard in the HVAC industry.