Carrier 30XW150-400 specifications APPENDIX C - CCN TABLES cont, CONFIGURATION TABLES cont

Models: 30XW150-400

1 148
Download 148 pages 52.93 Kb
Page 125
Image 125

APPENDIX C — CCN TABLES (cont)

CONFIGURATION TABLES (cont)

TABLE

DISPLAY NAME

RANGE

DEFAULT

UNITS

POINT NAME

CFG_TABn

Display x table number 1

 

85

 

tab_nb_1

(n = 1 to 8)

Display n var number 1

 

4

 

var_nb_1

 

Display n table number 2

 

85

 

tab_nb_2

 

Display n var number 2

 

20

 

var_nb_2

 

Display n table number 3

 

85

 

tab_nb_3

 

Display n var number 3

 

21

 

var_nb_3

 

Display n table number 4

 

85

 

tab_nb_4

 

Display n var number 4

 

28

 

var_nb_4

 

Display n table number 5

 

85

 

tab_nb_5

 

Display n var number 5

 

29

 

var_nb_5

 

Display n table number 6

 

85

 

tab_nb_6

 

Display n var number 6

 

30

 

var_nb_6

 

Display n table number 7

 

92

 

tab_nb_7

 

Display n var number 7

 

33

 

var_nb_7

 

Display n table number 8

 

92

 

tab_nb_8

 

Display n var number 8

 

34

 

var_nb_8

 

Display n table number 9

 

0

 

tab_nb_9

 

Display n var number 9

 

0

 

var_nb_9

DISPCONF

Metric Display on STDU

Yes/No

No

 

DISPUNIT

 

Language Selection

0=English

0

 

LANGUAGE

 

 

1=Espanol

 

 

 

 

 

2=Francais

 

 

 

 

 

3=Portugues

 

 

 

 

 

4=Translated

 

 

 

MST_SLV

MASTER SLAVE CONTROL

 

 

 

 

 

Master/Slave Select

0=Disable

0

 

ms_sel

 

 

1=Master

 

 

 

 

 

2=Slave

 

 

 

 

Master Control Type

1=Local Control

1

 

ms_ctrl

 

 

2=Remote Control

 

 

 

 

 

3=CCN Control

 

 

 

 

Slave Address

1 to 236

2

 

slv_addr

 

Lead Lag Select

0=Always Lead

0

 

lead_sel

 

 

1=Lag Once

 

 

 

 

 

Failed Only

 

 

 

 

 

2=Lead/Lag

 

 

 

 

 

Runtime Sel

 

 

 

 

Lead/Lag Balance Delta

40 to 400

168

hours

ll_bal_d

 

Lag Start Timer

2 to 30

10

min

lstr_tim

 

Lead Pulldown Time

0 to 60

0

min

lead_pul

 

Start if Error Higher

 

4

^F

start_dt

 

Lag Minimum Running Time

 

0

min

lag_mini

 

Lag Unit Pump Control

0=Stop if Unit Stops

0

 

lag_pump

 

 

1=Run if Unit Stops

 

 

 

 

Chiller in Series

Yes/No

No

 

II_serie

125

Page 125