Carrier 30XW150-400 specifications APPENDIX B - NAVIGATOR DISPLAY TABLES cont, Mode - Service Test

Models: 30XW150-400

1 148
Download 148 pages 52.93 Kb
Page 107
Image 107

APPENDIX B — NAVIGATOR™ DISPLAY TABLES (cont)

MODE — SERVICE TEST

ITEM

EXPANSION

UNITS

RANGE

COMMENT

WRITE

CCN TABLE

CCN POINT

PAGE

STATUS

NO.

 

 

 

 

 

 

 

TEST

MANUAL TEST MODE

 

 

Remote-Off-

 

N/A

 

 

T.REQ

Manual Sequence

 

OFF/ON

Enable Switch

forcible

N/A

service_test

61, 83

CP.A

Compressor A Output

 

 

must be set to

forcible

N/A

comp_serv_a

64

 

 

 

 

OFF Position

 

 

 

 

SLI.A

 

 

OFF/ON

Remote-Off-

 

 

 

 

Slide Valve Capacity A

 

unchanged

Enable Switch

forcible

 

comp_ser_sid_a

 

 

 

 

increase

must be set to

 

 

 

 

CP.B

 

 

decrease

ENABLE

 

 

 

 

Compressor B Output

 

OFF/ON

Position

forcible

N/A

comp_serv_b

64

SLI.B

Slide Valve Capacity B

 

unchanged

 

forcible

 

comp_ser_sid_b

 

 

 

 

increase

 

 

 

 

 

CP.C

 

 

decrease

 

 

 

 

 

Compressor C Output

 

OFF/ON

 

forcible

N/A

comp_serv_c

64

SLI.C

Slide Valve Capacity C

 

unchanged

 

forcible

 

comp_ser_sid_c

 

 

 

 

increase

 

 

 

 

 

 

 

 

decrease

 

 

 

 

 

QUIC

QUICK TEST MODE

 

 

Remote-Off-

 

N/A

 

 

Q.REQ

 

 

OFF/ON

Enable Switch

forcible

N/A

 

61

EXV.A

Circuit A EXV % Open

XXX (%)

0-100

must be set to

forcible

N/A

 

61

EXV.B

Circuit B EXV % Open

XXX (%)

0-100

OFF Position

forcible

N/A

 

61

EXV.C

Circuit C EXV % Open

XXX (%)

0-100

 

forcible

N/A

 

 

ECO.A

Circ A ECO EXV %

XXX (%)

0-100

 

forcible

 

 

 

ECO.B

Circ B ECO EXV %

XXX (%)

0-100

 

forcible

 

 

 

ECO.C

Circ C ECO EXV %

XXX (%)

0-100

 

forcible

 

 

 

FAN.A

Circuit A Fan Stages

X

0-8

 

forcible

N/A

 

 

FAN.B

Circuit B Fan Stages

X

0-8

 

forcible

N/A

 

 

FAN.C

Circuit C Fan Stages

X

0-8

 

forcible

N/A

 

 

SPD.A

Cir A Varifan position

XXX (%)

0-100

 

forcible

N/A

 

 

SPD.B

Cir B Varifan position

XXX (%)

0-100

 

forcible

N/A

 

 

SPD.C

Cir C Varifan position

XXX (%)

0-100

 

forcible

N/A

 

 

HT.A

Oil Heater Circuit A

 

OFF/ON

 

forcible

 

 

 

SL1.A

Slide Valve 1 Cir A

 

OFF/ON

 

forcible

 

 

 

SL2.A

Slide Valve 2 Cir B

 

OFF/ON

 

forcible

 

 

 

HGP.A

Hot Gas Bypass A Output

 

OFF/ON

 

forcible

 

 

 

OLS.A

Oil Solenoid Cir A

 

OFF/ON

 

forcible

 

 

 

DGT.A

DGT Cool Solenoid A

 

OFF/ON

 

forcible

 

 

 

HT.B

Oil Heater Circuit B

 

OFF/ON

 

forcible

 

 

 

SL1.B

Slide Valve 1 Cir B

 

OFF/ON

 

forcible

 

 

 

SL2.B

Slide Valve 2 Cir B

 

OFF/ON

 

forcible

 

 

 

HGP.B

Hot Gas Bypass B Output

 

OFF/ON

 

forcible

 

 

 

OLS.B

Oil Solenoid Cir A

 

OFF/ON

 

forcible

 

 

 

DGT.B

DGT Cool Solenoid B

 

OFF/ON

 

forcible

 

 

 

HT.C

Oil Heater Circuit C

 

OFF/ON

 

forcible

 

 

 

SL1.C

Slide Valve 1 Cir C

 

OFF/ON

 

forcible

 

 

 

SL2.C

Slide Valve 2 Cir C

 

OFF/ON

 

forcible

 

 

 

HGP.C

Hot Gas Bypass C Output

 

OFF/ON

 

forcible

 

 

 

OLS.C

Oil Solenoid Cir A

 

OFF/ON

 

forcible

 

 

 

DGT.C

DGT Cool Solenoid C

 

OFF/ON

 

forcible

 

 

 

PMP.1

Water Exchanger Pump 1

 

OFF/ON

Not supported.

forcible

N/A

 

 

PMP.2

Water Exchanger Pump 2

 

OFF/ON

Not supported.

forcible

N/A

 

 

PMP.3

Condenser Pump 1

 

OFF/ON

Not supported.

forcible

 

 

 

CL.HT

Cooler Heater Output

 

OFF/ON

 

 

N/A

 

 

BVL.A

Ball Valve Position A

 

OPEN/CLSE

 

 

 

 

 

BVL.B

Ball Valve Position B

 

OPEN/CLSE

 

 

 

 

 

BVL.C

Ball Valve Position C

 

OPEN/CLSE

 

 

 

 

 

Q.RDY

Chiller Ready Status

 

OFF/ON

 

forcible

N/A

 

 

Q.RUN

Chiller Running Status

 

OFF/ON

 

forcible

N/A

 

 

SHUT

Customer Shutdown Stat

 

OFF/ON

 

forcible

N/A

 

 

CATO

Chiller Capacity in 0-10v

XX.X (vdc)

 

 

forcible

N/A

 

 

ALRM

Alarm Relay

 

OFF/ON

 

forcible

N/A

 

68

ALRT

Alert Relay

 

OFF/ON

 

forcible

N/A

 

 

107