Carrier 30XW150-400 Condenser Water System Check, C. Unit Start-Up, Start and Operate Machine

Models: 30XW150-400

1 148
Download 148 pages 52.93 Kb
Page 142
Image 142

Condenser Water System Check

1.All condenser water valves are open.

2.All piping is connected properly.

3.All air has been purged from the system.

4.Condenser water pump is operating with the correct rotation.

5.Condenser water pump starter interlocked with chiller.

6.Condenser water flow switch operational.

7.Inlet piping to condenser includes a 20 mesh strainer within 10 ft.

8.Outdoor piping wrapped with electric heater tape.

9.Is system equipped with head pressure control?

(Required for entering condenser water below 68 F (20 C).)

C. UNIT START-UP

1.All liquid line service valves are open.

2.All discharge service valves are open.

3.All suction service valves are open.

4.Economizer service valves open.

5.Oil service valves open.

6.Leak check unit. Locate, repair and report any refrigerant leaks.

7.Voltage at terminal block is within unit nameplate range.

Check voltage imbalance: A-B______ A-C______B-C______

Average voltage = __________ (A-B + A-C + B-C)/3

Maximum deviation from average voltage = _______

Voltage imbalance = ______% (max. deviation / average voltage) X 100

Is voltage imbalance less than 2%.

(DO NOT start chiller if voltage imbalance is greater than 2%. Contact local utility for assistance.)

8. Verify evaporator flow rate

 

Pressure entering evaporator

_____ psig

Pressure leaving evaporator

_____ psig

Evaporator pressure drop

_____ psig

psig x 2.31 ft./psi =

_____ ft of water

kpa x 0.334 m/psi =

_____ mm of water

Evaporator flow rate _____ gpm (l/s) (See Evaporator Pressure Drop Curve)

9. Verify condenser flow rate

 

Pressure entering condenser

_____ psig

Pressure leaving condenser

_____ psig

Condenser pressure drop

_____ psig

psig x 2.31 ft./psi =

_____ ft of water

kpa x 0.334 m/psi =

_____ mm of water

Condenser flow rate _____ gpm (l/s) (See Condenser Pressure Drop Curve)

Start and Operate Machine

1.Complete component test utilizing Quick Test Mode

2.Check refrigerant and oil charge. Record charge information.

3.Record compressor motor current.

4.Record operating data.

5.Provide operating instructions to owner’s personnel.

 

Circuit A

Circuit B

Refrigerant Charge

 

 

Additional charge required

__________

___________

Oil Charge

 

 

Additional charge required

__________

___________

CL-2

Yes

No

Yes

No

Yes

No

Yes

No

Yes

No

Yes

No

Yes

No

Yes

No

Yes

No

Yes

No

Yes

No

Yes

No

Yes

No

Yes

No

Yes

No

Yes

No

Yes No

- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - - CUT ALONG DOTTED LINECUT ALONG DOTTED LINE

Page 142
Image 142
Carrier 30XW150-400 Condenser Water System Check, C. Unit Start-Up, Start and Operate Machine, Refrigerant Charge