Carrier 30XW150-400 APPENDIX B - NAVIGATOR DISPLAY TABLES cont, Mode - Operating Mode

Models: 30XW150-400

1 148
Download 148 pages 52.93 Kb
Page 117
Image 117

APPENDIX B — NAVIGATOR™ DISPLAY TABLES (cont)

MODE — OPERATING MODE

ITEM

EXPANSION*

UNITS

RANGE

COMMENT

WRITE

CCN TABLE

CCN POINT

PAGE

STATUS

NO.

 

 

 

 

 

 

 

SLCT

OPERATING CONTROL TYPE

 

 

 

 

 

 

 

OPER

Operating Control Type

 

Switch Ctrl

Default = Switch

forcible

N/A

N/A

24, 25

 

 

 

Time Sched

Ctrl

 

 

 

 

SP.SE

 

 

CCN Control

 

 

 

 

 

Setpoint Select

 

Setpoint Occ

Default =

forcible

N/A

N/A

25-27,

 

 

 

Setpoint1

Setpoint Occ

 

 

 

32

 

 

 

Setpoint2

 

 

 

 

 

 

 

 

4-20mA Setp

 

 

 

 

 

HC.SE

 

 

Dual Setp Sw

 

 

 

 

 

Heat Cool Select

 

Cooling

Default = Cooling

forcible

GENUNIT

HC_SEL

25

 

 

 

Heating

Not supported.

 

 

 

 

 

 

 

Auto Chgover

Not supported.

 

 

 

 

 

 

 

Heat Cool Sw

Not supported.

 

 

 

 

MODE*

OPERATING MODES

 

 

 

 

 

 

 

MD01

First Active Mode

 

0-32

 

 

MODES

 

 

MD02

Second Active Mode

 

0-32

 

 

MODES

 

 

MD03

Third Active Mode

 

0-32

 

 

MODES

 

 

MD04

Fourth Active Mode

 

0-32

 

 

MODES

 

 

MD05

Fifth Active Mode

 

0-32

 

 

MODES

 

 

MD06

Sixth Active Mode

 

0-32

 

 

MODES

 

 

*Up to six current operating modes will be displayed.

NOTE: See Operating Modes starting on page 54.

MODE — ALARMS

ITEM

EXPANSION*

UNITS

RANGE

COMMENT

WRITE

CCN TABLE

CCN POINT

PAGE

STATUS

NO.

 

 

 

 

 

 

 

R.ALM

RESET ALL CURRENT ALARM

 

NO/YES

 

forcible

N/A

N/A

 

ALRM†

CURRENTLY ACTIVE ALARMS

 

 

 

 

 

 

 

 

Current Alarm 1

 

 

 

 

GENUNIT

alarm_1

 

 

Current Alarm 2

 

 

 

 

GENUNIT

alarm_2

 

 

Current Alarm 3

 

 

 

 

GENUNIT

alarm_3

 

 

Current Alarm 4

 

 

 

 

GENUNIT

alarm_4

 

 

Current Alarm 5

 

 

 

 

GENUNIT

alarm_5

 

H.ALM**

ALARM HISTORY

 

 

 

 

 

 

 

 

Alarm History #1

 

 

 

 

ALRMHIST

alm_history_01

 

 

Alarm History #2

 

 

 

 

ALRMHIST

alm_history_02

 

 

Alarm History #49

 

 

 

 

ALRMHIST

alm_history_49

 

 

Alarm History #50

 

 

 

 

ALRMHIST

alm_history_50

 

*Expanded display will be actual alarm description. †History of up to five past alarms will be displayed. **History of fifty past alarms will be displayed.