Table 24 — Dual Master Chiller Control Parameters for Parallel Applications with Touch Pilot™ Display

DISPLAY NAME

PATH

LINE NO.

VALUE

Master/Slave Select

Main MenuConfigMST_SLV

3

1 (Master)

Default: 0 (Disable)

 

 

 

 

 

 

1=Local Control

Master Control Type

Main MenuConfigMST_SLV

 

2=Remote Control

7

3=CCN Control

 

 

 

Default: 1

 

 

 

Configure for proper control type.

 

 

 

Must be set to the Slave Chiller’s address.

Slave Address

Main MenuConfigMST_SLV

 

The master and slave chiller must have

11

different addresses and be on the same

 

 

 

Bus Number

 

 

 

Default: 2

 

 

 

0 (Master Always Leads)

Lead Lag Select

Main MenuConfigMST_SLV

12

1 (Lag Once Failed Only)

2 (Lead/Lag Runtime Select)

 

 

 

 

 

 

Default: 0 (Master Always Leads)

Lead/Lag Balance Delta

Main MenuConfigMST_SLV

16

Range: 40 to 400 hours

Default: 168 hours

 

 

 

Lag Start Timer

Main MenuConfigMST_SLV

17

Range: 2 to 30 minutes

Default: 10 minutes

 

 

 

Lead Pulldown Time

Main MenuConfigMST_SLV

18

Range: 0 to 60 minutes

Default: 0 minutes

 

 

 

Start If Error Higher

Main MenuConfigMST_SLV

19

Range: 3.0 to 18 ΔF (1.7 to 10.0 ΔC)

Default: 4.0 ΔF (2.2 ΔC)

 

 

 

Lag Minimum Running Time

Main MenuConfigMST_SLV

20

Range: 0 to 150 minutes

Default: 0 minutes

 

 

 

Lag Unit Pump Control

Main MenuConfigMST_SLV

 

0 (Stop If Unit Stops)

21

1 (Run If Unit Stops)

 

 

 

Default: 0 (Stop If Unit Stops)

Chiller In Series

Main MenuConfigMST_SLV

22

Default: No

Value: No

 

 

 

31