DUAL CHILLER PUMP CONTROL FOR PARALLEL CHILLER APPLICATIONS — It is recommended that a dedicated pump be used for each unit. The chiller must start and stop its own water pump located on its own piping. If pumps are not dedicated for each chiller, chiller isolation valves are required and each chiller must open and close its own isolation valve.

DUAL CHILLER CONTROL FOR SERIES APPLICA- TIONS — To configure the master chiller for series applica- tions using the Touch Pilot™ display, see Table 28. To

configure the master chiller for series applications using the Navigator™ display, see Table 29. A power cycle is required for the values to take effect.

To configure the slave chiller for series applications using the Touch Pilot™ display, see Table 30. To configure the slave chiller for series applications using the Navigator™ display, see Table 31.

Table 27 — Dual Slave Chiller Control Parameters for Parallel Applications with Navigator™ Display

ITEM

ITEM EXPANSION

PATH

VALUE

MSSL

Master/Slave Select

ConfigurationRSET

Slave

Default: Disable

 

 

 

 

 

 

Must be set to the Slave Chiller’s address.

SLVA

 

ConfigurationRSET

The master and slave chiller must have

Slave Address

different addresses and be on the same

 

 

 

Bus Number

 

 

 

Default: 2

LLBL

Master Lead Lag Select

ConfigurationRSET

Range: Always Lead, Lag if Fail, Runtime Sel

Default: Always Lead

 

 

 

LLBD

Lead/Lag Balance Delta

ConfigurationRSET

Range: 40 to 400 hours

Default: 168 hours

 

 

 

LLDY

Lag Start Delay

ConfigurationRSET

Range: 2 to 30 minutes

Default: 10 minutes

 

 

 

LL.ER

Start If Error Higher

ConfigurationRSET

Range: 3.0 to 18 ΔF (1.7 to 10.0 ΔC)

Default: 4.0 ΔF (2.2 ΔC)

 

 

 

LAG.M

Lag Unit Pump Select

ConfigurationRSET

Range: Off If U Stp, On If U Stop

Default: Off If U Stp

 

 

 

LPUL

Lead Pulldown Time

ConfigurationRSET

Range: 0 to 60 minutes

Default: 0 minutes

 

 

 

SERI

Chillers in Series

ConfigurationRSET

No,

Default: No

 

 

 

OPER

Operating Control Type

Operating ModesSLCT

CCN Control

Table 28 — Dual Master Chiller Control Parameters for Series Applications with Touch Pilot Display

DISPLAY NAME

PATH

LINE NO.

 

VALUE

Master/Slave Select

Main MenuConfigMST_SLV

3

1

(Master)

Default: 0 (Disable)

 

 

 

 

 

 

1

(Local Control)

Master Control Type

Main MenuConfigMST_SLV

 

2

(Remote Control)

7

3

(CCN Control)

 

 

 

Default: 1 (Local Control)

 

 

 

Value: Configure for proper control type.

 

 

 

Must be set to the Slave Chiller’s address.

Slave Address

Main MenuConfigMST_SLV

 

The master and slave chiller must have

11

different addresses and be on the same

 

 

 

Bus Number

 

 

 

Default: 2

 

 

 

0

(Master Always Leads)

Lead Lag Select

Main MenuConfigMST_SLV

12

1

(Lag Once Failed Only)

2

(Lead/Lag Runtime Select)

 

 

 

 

 

 

Default: 0 (Master Always Leads)

Lead/Lag Balance Delta

Main MenuConfigMST_SLV

16

Range: 40 to 400 hours

Default: 168 hours

 

 

 

Lag Start Timer

Main MenuConfigMST_SLV

17

Range: 2 to 30 minutes

Default: 10 minutes

 

 

 

Lead Pulldown Time

Main MenuConfigMST_SLV

18

Range: 0 to 60 minutes

Default: 0 minutes

 

 

 

Start If Error Higher

Main MenuConfigMST_SLV

19

Range: 3.0 to 18 ΔF (1.7 to 10.0 ΔC)

Default: 4.0Δ F (2.2 ΔC)

 

 

 

Lag Minimum Running Time

Main MenuConfigMST_SLV

20

Range: 0 to 150 minutes

Default: 0 minutes

 

 

 

Lag Unit Pump Control

Main MenuConfigMST_SLV

21

0

(Stop If Unit Stops)

1

(Run If Unit Stops)

 

 

 

Default: 0 (Stop If Unit Stops)

Chiller In Series

Main MenuConfigMST_SLV

22

Yes

Default: No

 

 

 

33