In the following example, 2-step demand limit based on capacity is desired with the first switch closure limiting the capacity to 60%. The second switch closure is to limit the capacity to 40%. Demand Limit Switch 1 is 60% and Demand Limit Switch 2 is 40%.

TOUCH PILOT DISPLAY

 

 

NAVIGATOR DISPLAY

Display Name

Value

 

Item

Value

Demand Limit Type Select

1

 

DMDC

SWITCH

Switch Limit Setpoint 1

60%

 

DSL1

60%

Switch Limit Setpoint 2

40%

 

DSL2

40%

Current Limit Select

No

 

CUR.S

NO

Switch Controlled (Current Based) — If using 2-step de- mand limit control, an energy management module must be installed. One-step demand limit control does not require the energy management module. Four parameters for 1-step switch control must be configured. For 2-step control, five parameters must be configured. The parameters are: the type of Demand Limit Selection (Demand Limit Type Select, DMDC), the setting for Switch Limit Set Point 1 (Switch Limit Setpoint 1, DLS1), the setting for Switch Limit Set Point 2 (Switch Limit Setpoint 2, DLS2), the Current Limit Select (Current Limit Select, CUR.S), and the Compressor Current limit at 100% signal, (Current Limit at 100%, CUR.F).

To configure this option with the Touch Pilot display:

DISPLAY NAME

 

PATH

 

LINE

 

VALUE

 

 

NO.

 

 

 

 

 

 

 

 

 

Demand Limit

ConfigUSER

 

 

1 (Switch Control)

 

24

Default = 0

Type Select

 

 

 

 

 

 

(None)

 

 

 

 

 

 

 

Switch Limit

SetpointsSETPOINT

 

33

Default = 100%

Setpoint 1

 

 

 

 

 

 

 

 

Switch Limit

SetpointsSETPOINT

 

 

(Not required

 

34

for 1-Step)

Setpoint 2

 

 

 

 

 

 

Default = 100%

 

 

 

 

 

 

 

Current Limit

ConfigUSER

 

30

Yes

Select

 

 

Default = No

 

 

 

 

 

 

Current Limit

ConfigUSER

 

31

Default =

at 100%

 

 

2000.0 Amps

 

 

 

 

 

 

To configure this option with the Navigator™ display:

 

 

 

 

 

 

 

ITEM

ITEM EXPANSION

 

PATH

 

 

VALUE

DMDC

Demand Limit

 

ConfigurationRSET

 

SWITCH

 

 

Default =

Select

 

 

 

 

 

 

 

 

 

 

NONE

 

 

 

 

 

 

 

 

DSL1

Switch Limit

 

SetpointsMISC

 

Default =

Setpoint 1

 

 

 

100%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Not required

DSL2

Switch Limit

 

SetpointsMISC

 

for 1-Step)

Setpoint 2

 

 

 

Default =

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100%

CUR.S

Current Limit

 

ConfigurationOPTN

 

NO

 

Select

 

 

 

 

 

 

Default: NO

CUR.F

Current Limit

 

ConfigurationOPTN

 

Default =

 

at 100%

 

 

 

 

 

 

2000

EXTERNALLY POWERED (4 to 20 mA) CAPACITY BASED DEMAND LIMIT — The energy management module is required for 4 to 20 mA demand limit control. An externally powered 4 to 20 mA signal must be connected to TB6-1 and TB6-2. To configure demand limit for 4 to 20 mA control based on unit capacity, four parameters must be config- ured. The parameters are: the type of Demand Limit Selection (Demand Limit Type Select, DMDC), the current at which 100% capacity limit takes place (mA For 100% Demand Limit, DMMX), the current at which 0% capacity limit takes place (mA For 0% Demand Limit, DMZE), and the Current Limit Selection (Current Limit Select, CUR.S).

CAUTION

Care should be taken when interfacing with other control systems due to possible power supply differences such as a full wave bridge versus a half wave rectification. Connec- tion of control devices with different power supplies may result in permanent damage. ComfortLink™ controls incorporate power supplies with half wave rectification. A signal isolation device should be utilized if the signal gen- erator incorporates a full wave bridge rectifier.

To configure this option with the Touch Pilot™ display:

DISPLAY NAME

PATH

LINE NO.

VALUE

Demand Limit

ConfigUSER

24

2 (4-20mA Control)

Type Select

Default = 0 (None)

 

 

mA For 100%

ConfigUSER

28

Default = 0.0 mA

Demand Limit

 

 

 

mA For 0%

ConfigUSER

29

Default = 10.0 mA

Demand Limit

 

 

 

Current Limit

ConfigUSER

30

No

Select

Default = No

 

 

To configure this option with the Navigator display:

ITEM

ITEM EXPANSION

PATH

VALUE

DMDC

Demand Limit

ConfigurationRSET

4-20MA INPUT

 

Select

 

Default = NONE

DMMX

mA for 100%

ConfigurationRSET

Default =

 

Demand Lim

 

0.0 mA

DMZE

mA for 0%

ConfigurationRSET

Default =

Demand Limit

10.0 mA

 

 

CUR.S

Current Limit

ConfigurationOPTN

NO

 

Select

 

Default: NO

In the following example, a 4 mA signal is Demand Limit 100% and a 20 mA Demand Limit signal is 0%. The 4 to 20 mA signal is connected to TB6-1 and TB6-2. The demand limit is a linear interpolation between the two values entered. In Fig. 24, if the machine receives a 12 mA signal, the machine controls will limit the capacity to 50%.

EXTERNALLY POWERED (4 to 20 mA) CURRENT BASED DEMAND LIMIT — The energy management module is required for 4 to 20 mA demand limit control. An externally powered 4 to 20 mA signal must be connected to TB6-1 and TB6-2. To configure demand limit for 4 to 20 mA control based on compressor current, five parameters must be configured. The parameters are: the type of Demand Limit Selection (Demand Limit Type Select, DMDC), the current at which 100% capacity limit takes place (mA For 100% Demand Limit, DMMX), the current at which 0% capacity limit takes place (mA For 0% Demand Limit, DMZE), the Current Limit Selection (Current Limit Select, CUR.S), and the Compressor Current limit at 100% signal (Current Limit at 100%, CUR.F).

To configure this option with the Touch Pilot display:

DISPLAY NAME

PATH

LINE NO.

VALUE

Demand Limit

ConfigUSER

24

2 (4-20mA Control)

Type Select

Default = 0 (None)

 

 

mA For 100%

ConfigUSER

28

Default = 0.0 mA

Demand Limit

 

 

 

mA For 0%

ConfigUSER

29

Default = 10.0 mA

Demand Limit

 

 

 

Current Limit

ConfigUSER

30

Yes

Select

Default = No

 

 

Current Limit

ConfigUSER

31

Default = 2000.0 Amps

at 100%

 

 

 

40

Page 40
Image 40
Carrier 30XW150-400 specifications Touch Pilot Display Navigator Display, Dmdc Switch, DSL1, DSL2, Cur.F, Dmmx, Dmze

30XW150-400 specifications

The Carrier 30XW150-400 series is a line of water-cooled chillers that exemplifies innovation, efficiency, and reliability in commercial cooling solutions. Designed for medium to large-scale applications, this series is ideal for a variety of settings, including commercial buildings, industrial processes, and chilled water systems.

One of the standout features of the Carrier 30XW series is its efficiency. The chillers utilize advanced variable-speed compressor technology, which allows the units to adapt to varying cooling loads while minimizing energy consumption. This technology not only reduces operational costs but also contributes to better environmental sustainability by lowering greenhouse gas emissions.

The 30XW series chillers are equipped with high-efficiency, scroll compressors that operate quietly and provide significant energy savings. By utilizing enhanced economizer controls, these units can achieve higher efficiency ratings, especially in part-load conditions. The result is an impressive Energy Efficiency Ratio (EER) and Seasonal Energy Efficiency Ratio (SEER), making these units a smart choice for energy-conscious businesses.

In terms of reliability, the Carrier 30XW150-400 series features robust construction and an array of safety and monitoring systems. The units come with advanced diagnostics that help in quickly identifying and addressing any operational issues. This proactive approach ensures reliability and minimizes downtime, which is crucial for maintaining optimal temperature controls in critical environments.

Additionally, the chillers incorporate environmentally friendly refrigerants that comply with the latest regulations, making them a sustainable choice for modern commercial applications. Their compact design allows for flexible installation options, and the integrated control systems provide the ability to optimize performance based on specific building management demands.

User-friendly interfaces and remote monitoring capabilities further enhance the ease of operation, allowing facility managers to have real-time insight into performance metrics and system health. This level of control contributes to better maintenance planning and maximizes the lifespan of the equipment.

In summary, the Carrier 30XW150-400 series of water-cooled chillers combines advanced technology, energy efficiency, and reliable performance, making it an ideal solution for various commercial and industrial cooling needs. With its commitment to innovation and sustainability, Carrier continues to set the standard in the HVAC industry.