Table 49 — Alarm Codes (cont)

PREFIX

SUFFIX

ALARM

ALARM DESCRIPTION

REASON FOR ALARM

ACTION TAKEN

RESET

PROBABLE CAUSE

CODE

CODE

NUMBER

BY CONTROL

TYPE

 

 

 

 

 

Co

 

A1

53

Loss of communication with

No communication

Affected

Automatic

Wrong CPM address,

 

 

 

 

Compressor Board A

 

with CPM board

compressor shut

 

wrong unit configura-

 

 

 

 

 

 

 

 

down

 

tion, wiring error, power

 

 

B1

54

Loss of communication with

 

 

 

 

 

 

 

loss, failed

 

 

 

 

Compressor Board B

 

 

 

 

 

 

 

 

 

 

 

 

CPM board

 

 

 

 

 

 

 

 

 

 

 

 

E1

56

Loss of communication with

No communication with

Affected

Automatic

Wrong EXV board

 

 

 

 

EXV Board 1

 

 

EXV board

compressor

 

address, wrong unit

 

 

E2

57

Loss of communication with

 

shut down

 

configuration, wiring

 

 

 

 

 

error, power loss,

 

 

 

 

EXV Board 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

failed EXV board

 

 

 

 

 

 

 

 

 

 

 

 

03

64

Loss of communication with

No communication with

Disable or not allow

Automatic

Wrong board

 

 

 

 

Energy Management Board

EMM board

EMM functions

 

address, wrong unit

 

 

 

 

 

 

 

 

3 step and 4-20 mA

 

configuration, wiring

 

 

 

 

 

 

 

 

and space tempera-

 

error, power loss to

 

 

 

 

 

 

 

 

ture reset, occu-

 

module, failed module

 

 

 

 

 

 

 

 

pancy override and

 

 

 

 

 

 

 

 

 

 

ice build)

 

 

 

 

05

66

Loss of communication with

No communication

Unit shut down or

Automatic

Wrong board

 

 

 

 

AUX Board 6

 

 

with MLV/COND Board

not allowed to start

 

address, wrong unit

 

 

 

 

 

 

 

 

configuration, wiring

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

error, power loss to

 

 

 

 

 

 

 

 

 

 

module, failed module

P

 

01

67

Cooler Freeze Protection

Entering or leaving therm-

Unit shut down or

Automatic, first

Faulty thermistor, faulty

 

 

 

 

 

 

 

istor sensed a tempera-

not allowed to start

occurrence in

wiring, low water flow,

 

 

 

 

 

 

 

ture at or below freeze

 

24 hours;

low loop volume, fouled

 

 

 

 

 

 

 

point

 

manual if

cooler, or freeze

 

 

 

 

 

 

 

 

 

multiple alarms

conditions

 

 

 

 

 

 

 

 

 

within 24 hours

 

 

 

02

68

Condenser Freeze Protection

None

Automatic

Configuration error

 

 

 

 

Circuit A

 

 

 

 

 

 

 

 

03

69

Condenser Freeze Protection

 

 

 

 

 

 

 

 

Circuit B

 

 

 

 

 

 

 

 

05

71

Circuit A Low Suction

 

Low saturated suction

Circuit shut down

Automatic, first

Faulty thermistor, faulty

 

 

 

 

Temperature

 

 

temperatures detected for

 

occurrence in

wiring, low water flow,

 

 

 

 

 

 

 

a period of time

 

24 hours;

low loop volume, fouled

 

 

06

72

Circuit B Low Suction

 

 

 

 

 

 

 

manual if

cooler, or freeze

 

 

 

 

Temperature

 

 

 

 

 

 

 

 

 

 

 

 

multiple alarms

conditions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

within 24 hours

 

 

 

08

74

Circuit A High Suction

 

EXV>98%,

Circuit shut down

Manual

Faulty transducer,

 

 

 

 

Superheat

 

 

suction superheat > 30 F,

 

 

faulty wiring, faulty

 

 

09

75

Circuit B High Suction

 

and SST<MOP for more

 

 

thermistor, faulty EXV,

 

 

 

than 5 minutes

 

 

low refrigerant charge,

 

 

 

 

Superheat

 

 

 

 

 

 

 

 

 

 

 

 

 

plugged or restricted

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

liquid line

 

 

 

 

LEGEND

 

 

 

 

 

 

CCN

Carrier Comfort Network®

MLV

Minimum Load Valve

 

 

 

CPM

Compressor Protection Module

MOP

Maximum Operating Pressure

 

 

 

EMM

Energy Management Module

MTA

Must Trip Amps

 

 

 

EWT

Entering Water Temperature

SST

Saturated Suction Temperature

 

 

EXV

Electronic Expansion Valve

UL

Underwriters Laboratories

 

 

 

HPS

High Pressure Switch

 

 

 

 

 

 

 

70

Page 70
Image 70
Carrier 30XW150-400 specifications Loss of communication with

30XW150-400 specifications

The Carrier 30XW150-400 series is a line of water-cooled chillers that exemplifies innovation, efficiency, and reliability in commercial cooling solutions. Designed for medium to large-scale applications, this series is ideal for a variety of settings, including commercial buildings, industrial processes, and chilled water systems.

One of the standout features of the Carrier 30XW series is its efficiency. The chillers utilize advanced variable-speed compressor technology, which allows the units to adapt to varying cooling loads while minimizing energy consumption. This technology not only reduces operational costs but also contributes to better environmental sustainability by lowering greenhouse gas emissions.

The 30XW series chillers are equipped with high-efficiency, scroll compressors that operate quietly and provide significant energy savings. By utilizing enhanced economizer controls, these units can achieve higher efficiency ratings, especially in part-load conditions. The result is an impressive Energy Efficiency Ratio (EER) and Seasonal Energy Efficiency Ratio (SEER), making these units a smart choice for energy-conscious businesses.

In terms of reliability, the Carrier 30XW150-400 series features robust construction and an array of safety and monitoring systems. The units come with advanced diagnostics that help in quickly identifying and addressing any operational issues. This proactive approach ensures reliability and minimizes downtime, which is crucial for maintaining optimal temperature controls in critical environments.

Additionally, the chillers incorporate environmentally friendly refrigerants that comply with the latest regulations, making them a sustainable choice for modern commercial applications. Their compact design allows for flexible installation options, and the integrated control systems provide the ability to optimize performance based on specific building management demands.

User-friendly interfaces and remote monitoring capabilities further enhance the ease of operation, allowing facility managers to have real-time insight into performance metrics and system health. This level of control contributes to better maintenance planning and maximizes the lifespan of the equipment.

In summary, the Carrier 30XW150-400 series of water-cooled chillers combines advanced technology, energy efficiency, and reliable performance, making it an ideal solution for various commercial and industrial cooling needs. With its commitment to innovation and sustainability, Carrier continues to set the standard in the HVAC industry.