Carrier 30XW150-400 specifications Reset Method

Models: 30XW150-400

1 148
Download 148 pages 52.93 Kb
Page 75
Image 75

Criteria for Trip — The criteria are tested whether the circuit is ON or OFF. The alarm is generated if one of the following criteria is met:

1. If the voltage as sensed by the MBB is 0 vdc, which corresponds to the Navigator™ display of –7 psi (–48.3 kPa).

2.The circuit is ON in cooling mode and the Saturated Suction Temperature (Saturated Suction Temp, SST) for the circuit is greater than the Entering Water Tempera- ture and EXV opening is less than 50% for more than 60 seconds.

Action to be Taken — The circuit is shut down immediately, or not allowed to start.

Reset Method

1.Automatic, once the transducer voltage is greater than 0 vdc, which corresponds to the Navigator display of a value greater than –7 psi (–48.3 kPa).

2.Automatic once the circuit’s saturated suction tempera- ture is lower than the Entering Water Temperature by 3° F (1.6° C). If this criterion trips the alarm 3 times within a 24-hour period, the alarm changes to a manual reset.

Possible Causes — If this condition is encountered, check the following items:

sensor wiring to Main Base Board

board for a faulty channel

faulty transducer

faulty entering water temperature sensor

Reclaim Pumpdown Pressure Transducer

Alarm 32 — Circuit A (Pr.07)

Alarm 33 — Circuit B (Pr.08)

NOTE: Alarms 30 and 31 are not used or supported. If this condition is encountered, confirm machine configuration.

Oil Pressure Transducer

Alarm 34 — Circuit A (Pr.10)

Alarm 35 — Circuit B (Pr.11)

Criteria for Trip — The criteria are tested whether the circuit is ON or OFF. The alarm is generated if one of the following cri- teria is met:

1.If the voltage as sensed by the CPM board is 0 vdc, which corresponds to the Navigator display of –7 psi (–48.3 kPa).

2.The circuit is OFF and outside air temperature is below 35.6 F (2 C).

3.The circuit is OFF and the fluid type is brine.

Action to be Taken — The circuit is shut down immediately, or not allowed to start.

Reset Method — Automatic, once the transducer voltage is greater than 0 vdc.

Possible Causes — If this condition is encountered, check the following items:

sensor wiring to CPM board

board for a faulty channel

faulty transducer

plugged oil filter

faulty oil solenoid valve coil

stuck oil solenoid valve

confirm unit configuration

Economizer Pressure Transducer Failure (sizes 175,200,350,400 only)

Alarm 37 — Circuit A (Pr. 13)

Alarm 38 — Circuit B (Pr. 14)

Criteria for Trip — The criteria are tested whether the circuit is ON or OFF. The alarm is generated if the voltage as sensed by the MBB or Fan Board C is 0 vdc, which corresponds to the Navigator display of –7 psi (–48.3 kPa).

Action to be Taken — The circuit is shut down immediately, or not allowed to start.

Reset Method — Automatic, once the transducer voltage is greater than 0 vdc, which corresponds to the Navigator display of a value greater than –7 psi (–48.3 kPa).

Possible Causes — If this condition is encountered, check the following items:

sensor wiring to EXV Board

EXV board for a faulty channel

faulty transducer

faulty economizer EXV or EXV wiring

faulty economizer EXV channel on the board

closed or partially closed suction service valve

confirm unit configuration

Loss of Communication with Compressor Board

Alarm 53 — Compressor Board A (Co.A1)

Alarm 54 — Compressor Board B (Co.B1)

Criteria for Trip — The alarm criterion is tested whether the unit is ON or OFF. If communication with the Compressor Protection Module Board (CPM) is lost for a period of 10 sec- onds, the alarm will be generated.

Action to be Taken — The affected compressor will be shut down.

Reset Method — Automatic, if communication is established. If called for, the compressor will start normally.

Possible Causes — If this condition is encountered, check the following items:

power supply to the affected CPM board

address of the CPM

local equipment network (LEN) wiring

confirm unit configuration

Loss of Communication with EXV Board

Alarm 56 — Circuit A, EXV Board 1 (Co.E1) Alarm 57 — Circuit B, EXV Board 2 (Co.E2)

Criteria for Trip — The alarm criterion is tested whether the unit is ON or OFF. If communication with EXV1 or 2 is lost for a period of 10 seconds, the alarm will be triggered.

Action to be Taken — If running, Circuit A or B will shut down normally. If Circuit A or B is not operating, it will not be allowed to start.

Reset Method — Automatic, if communication is established, the unit will start normally.

Possible Causes — If this condition is encountered, check the following items:

power supply to EXV1 or 2

address of the EXV board

local equipment network (LEN) wiring

confirm unit configuration

75

Page 75
Image 75
Carrier 30XW150-400 specifications Reset Method