Carrier 30XW150-400 specifications Carrier Comfort Network CCN Interface, Configuration, a30-4706

Models: 30XW150-400

1 148
Download 148 pages 52.93 Kb
Page 18
Image 18
Carrier Comfort Network® (CCN) Interface —

Carrier Comfort Network® (CCN) Interface —

All 30XW units can be connected to a CCN system, if desired. The communication bus wiring is a shielded, 3-conductor cable with drain wire and is field supplied and installed. The system elements are connected to the communication bus in a daisy chain arrangement. The positive pin of each system element communication connector must be wired to the positive pins of the system elements on either side of it. The negative and sig- nal ground pins of each system element must also be wired in the same manner. Wiring connections for CCN should be made at TB3. Consult the CCN Contractor’s Manual for further in- formation. See Fig. 14.

NOTE: Conductors and drain wire must be 20 AWG (Ameri- can Wire Gage) minimum stranded, tinned copper. Individual conductors must be insulated with PVC, PVC/nylon, vinyl, Teflon, or polyethylene. An aluminum/polyester 100% foil shield and an outer jacket of PVC, PVC/nylon, chrome vinyl, or Teflon with a minimum operating temperature range of –20 C to 60 C is required. See Table 11 for recommended wire manufacturers and part numbers.

Table 11 — CCN Communication Bus Wiring

MANUFACTURER

PART NUMBER

Regular Wiring

Plenum Wiring

 

Alpha

1895

American

A21451

A48301

Belden

8205

884421

Columbia

D6451

Manhattan

M13402

M64430

Quabik

6130

It is important when connecting to a CCN communication bus that a color-coding scheme be used for the entire network to simplify the installation. It is recommended that red be used for the signal positive, black for the signal negative, and white for the signal ground. Use a similar scheme for cables contain- ing different colored wires.

At each system element, the shields of its communication bus cables must be tied together. If the communication bus is entirely within one building, the resulting continuous shield must be connected to a ground at one point only. If the commu- nication bus cable exits from one building and enters another, the shields must be connected to grounds at the lightning suppressor in each building where the cable enters or exits the building (one point per building only). To connect the unit to the network:

1.Turn off power to the control box.

2.Cut the CCN wire and strip the ends of the red (+), white (ground), and black (–) conductors. (Substitute appropri- ate colors for different colored cables.)

3.Connect the red wire to (+) terminal on TB3 of the plug, the white wire to COM terminal, and the black wire to the

(–) terminal.

4.The RJ14 CCN connector on TB3 can also be used, but is only intended for temporary connection (for example, a laptop computer running Service Tool).

IMPORTANT: A shorted CCN bus cable will prevent some routines from running and may prevent the unit from starting. If abnormal conditions occur, discon- nect the CCN bus. If conditions return to normal, check the CCN connector and cable. Run new cable if necessary. A short in one section of the bus can cause problems with all system elements on the bus.

Remote Alarm and Alert Relays — The 30XW chiller can be equipped with a remote alert and remote alarm annunciator contacts. Both relays connected to these contacts must be rated for a maximum power draw of 10 va sealed, 25 va inrush at 24 volts. The alarm relay, indicating that the complete unit has been shut down, can be connected to TB5-12 and TB5-13. Refer to unit wiring diagrams. For an alert relay, indicating that at least 1 circuit is off due to the alert, a field- supplied and installed relay must be connected between MBB- J3-CH25-3 and TB5-13. The action of the alarm and alert re- lays can be reversed from normally open to normally closed by using the Reverse Alarms Relay configuration (Reverse Alarms Relay, RV.AL).

CONFIGURATION

Touch Pilot™ Operation Configuration Tables — The Touch Pilot display operation is controlled by configuration information entered in the following configura- tion tables. These tables are accessible by using Network Ser- vice Tool or ComfortVIEW™ software. The tables are the CtrlID (Controller Identification) configuration table and the USERCONF (User Configuration) table. See Tables 12 and 13.

NOTE: Always perform an Upload to obtain the latest config- uration before making configuration table changes.

(+) (COM) (-) SHIELD

(+) (COM) (-) SHIELD

 

 

 

 

 

 

 

LEN

CCN

CCN

LEN

CCN

CCN

LEN

CCN

RED

WHT

BLK

SHIELD

RED

WHT

BLK

 

 

 

 

 

 

(+)(COM) (-) SHIELD Table 11 — CCN Communication Bus Wiring CCN CONFIGURATION

RED

WHT

BLK

TO NEXT

DEVICE

LEGEND

CCN — Carrier Comfort Network®

LEN — Local Equipment Network

a30-4706

Fig. 14 — ComfortLink™ CCN Communication Wiring

18

Page 18
Image 18
Carrier 30XW150-400 Carrier Comfort Network CCN Interface, Configuration, CCN Communication Bus Wiring, a30-4706