APPENDIX A — TOUCH PILOT™ DISPLAY TABLES (cont)

102

TOUCH PILOT DESCRIPTION

TOUCH PILOT

TOUCH PILOT PATH

LINE

READ/

CCN TABLE NAME

POINT NAME

WRITE

 

 

 

 

Reclaim Deadband

hr_deadb

MAIN MENU\Setpoint\SETPOINT

37

RW

Setpoint Configuration Tables\SETPOINT

Reclaim Entering Fluid

HR_EWT

MAIN MENU\Status\RECLAIM

5

RO

Status Display Tables\RECLAIM

Reclaim Fluid Setpoint

RSP

MAIN MENU\Status\RECLAIM

7

RO

Status Display Tables\RECLAIM

Reclaim Leaving Fluid

HR_LWT

MAIN MENU\Status\RECLAIM

6

RO

Status Display Tables\RECLAIM

Reclaim NRCP2 Board

REC_NRCP

MAIN MENU\Maint\BOARD_PN

10

RO

Maintenance Display Tables\BOARD_PN

Reclaim Setpoint

rsp

MAIN MENU\Setpoint\SETPOINT

36

RW

Setpoint Configuration Tables\SETPOINT

Reclaim Status Circuit A

hrstat_a

MAIN MENU\Status\RECLAIM

10

RO

Status Display Tables\RECLAIM

Reclaim Status Circuit B

hrstat_b

MAIN MENU\Status\RECLAIM

20

RO

Status Display Tables\RECLAIM

Reclaim Valve Position

hr_v_pos

MAIN MENU\Status\RECLAIM

8

RO

Status Display Tables\RECLAIM

Reference Number

RefNum

MAIN MENU\Config\Ctlr-ID

6

RO

Configuration Tables\!CtlrID\PD5_XAXQ

Refrigerant Charge Ctrl

charge_c

MAIN MENU\Service\MAINTCFG

3

RW

Service Configuration Tables\MAINTCFG

Remote Heat/Cool Switch

HC_SW

MAIN MENU\Status\STATEGEN

3

RO

Status Display Tables\STATEGEN

Remote Interlock Status

REM_LOCK

MAIN MENU\Status\STATEGEN

15

RO

Status Display Tables\STATEGEN

Remote Reclaim Switch

RECL_SW

MAIN MENU\Status\STATEGEN

5

RO

Status Display Tables\STATEGEN

Remote Setpoint Switch

SETP_SW

MAIN MENU\Status\STATEGEN

7

RO

Status Display Tables\STATEGEN

Requested Electric Stage

eh_stage

MAIN MENU\Maint\LOADFACT

23

RO

Maintenance Display Tables\LOADFACT

Reset Amount

reset

MAIN MENU\Maint\LOADFACT

6

RO

Maintenance Display Tables\LOADFACT

Reset in Effect

Mode_03

MAIN MENU\Status\MODES

4

RO

Status Display Tables\MODES

Reset Maintenance Alert

S_RESET

MAIN MENU\Maint\SERMAINT

1

RO

Maintenance Display Tables\SERMAINT

Reset/Setpnt 4-20mA Sgnl

SP_RESET

MAIN MENU\Status\STATEGEN

41

RO

Status Display Tables\STATEGEN

Reverse Alarms Relay

al_rever

MAIN MENU\Config\USER

43

RW

Configuration Tables\USER

Rotate Condenser Pumps?

ROTHPUMP

MAIN MENU\Status\STATEGEN

25

RO

Status Display Tables\STATEGEN

Rotate Cooler Pumps?

ROTCPUMP

MAIN MENU\Status\STATEGEN

22

RO

Status Display Tables\STATEGEN

Run Status

STATUS

MAIN MENU\Status\GENUNIT

4

RO

Status Display Tables\GENUNIT

Running Status

RUNNING

MAIN MENU\Status\STATEGEN

31

RO

Status Display Tables\STATEGEN

Reference Delta

 

 

 

 

 

Circuit A

delt_r_a

MAIN MENU\Maint\DEFROSTM

12

RO

Maintenance Display Tables\DEFROSTM

Circuit B

delt_r_b

MAIN MENU\Maint\DEFROSTM

29

RO

Maintenance Display Tables\DEFROSTM

Refrigerant Pump Out

 

 

 

 

 

Circuit A

FC_PMP_A

MAIN MENU\Status\FREECOOL

16

RO

Status Display Tables\FREECOOL

Circuit B

FC_PMP_B

MAIN MENU\Status\FREECOOL

26

RO

Status Display Tables\FREECOOL

Circuit C

FC_PMP_C

MAIN MENU\Status\FREECOOL

36

RO

Status Display Tables\FREECOOL

Running Output

 

 

 

 

 

Circuit A

Q_RUN_A

MAIN MENU\Status\QCK_TST1

43

RW

Status Display Tables\QCK_TST1

Circuit B

Q_RUN_B

MAIN MENU\Status\QCK_TST1

44

RW

Status Display Tables\QCK_TST1

Circuit C

Q_RUN_C

MAIN MENU\Status\QCK_TST1

45

RW

Status Display Tables\QCK_TST1

Saturated Condensing Tmp

 

 

 

 

 

Circuit A

SCT_A

MAIN MENU\Status\CIRCA_AN

12

RO

Status Display Tables\CIRCA_AN

Circuit B

SCT_B

MAIN MENU\Status\CIRCB_AN

12

RO

Status Display Tables\CIRCB_AN

Circuit C

SCT_C

MAIN MENU\Status\CIRCC_AN

12

RO

Status Display Tables\CIRCC_AN

Saturated Suction Temp

 

 

 

 

 

Circuit A

SST_A

MAIN MENU\Status\CIRCA_AN

13

RO

Status Display Tables\CIRCA_AN

Circuit B

SST_B

MAIN MENU\Status\CIRCB_AN

13

RO

Status Display Tables\CIRCB_AN

Circuit C

SST_C

MAIN MENU\Status\CIRCC_AN

13

RO

Status Display Tables\CIRCC_AN

Circuit C

Q_SLI_1C

MAIN MENU\Status\QCK_TST1

31

RW

Status Display Tables\QCK_TST1

LEGEND

RO — Read Only

RW — Read/Write

Page 102
Image 102
Carrier 30XW150-400 specifications 102

30XW150-400 specifications

The Carrier 30XW150-400 series is a line of water-cooled chillers that exemplifies innovation, efficiency, and reliability in commercial cooling solutions. Designed for medium to large-scale applications, this series is ideal for a variety of settings, including commercial buildings, industrial processes, and chilled water systems.

One of the standout features of the Carrier 30XW series is its efficiency. The chillers utilize advanced variable-speed compressor technology, which allows the units to adapt to varying cooling loads while minimizing energy consumption. This technology not only reduces operational costs but also contributes to better environmental sustainability by lowering greenhouse gas emissions.

The 30XW series chillers are equipped with high-efficiency, scroll compressors that operate quietly and provide significant energy savings. By utilizing enhanced economizer controls, these units can achieve higher efficiency ratings, especially in part-load conditions. The result is an impressive Energy Efficiency Ratio (EER) and Seasonal Energy Efficiency Ratio (SEER), making these units a smart choice for energy-conscious businesses.

In terms of reliability, the Carrier 30XW150-400 series features robust construction and an array of safety and monitoring systems. The units come with advanced diagnostics that help in quickly identifying and addressing any operational issues. This proactive approach ensures reliability and minimizes downtime, which is crucial for maintaining optimal temperature controls in critical environments.

Additionally, the chillers incorporate environmentally friendly refrigerants that comply with the latest regulations, making them a sustainable choice for modern commercial applications. Their compact design allows for flexible installation options, and the integrated control systems provide the ability to optimize performance based on specific building management demands.

User-friendly interfaces and remote monitoring capabilities further enhance the ease of operation, allowing facility managers to have real-time insight into performance metrics and system health. This level of control contributes to better maintenance planning and maximizes the lifespan of the equipment.

In summary, the Carrier 30XW150-400 series of water-cooled chillers combines advanced technology, energy efficiency, and reliable performance, making it an ideal solution for various commercial and industrial cooling needs. With its commitment to innovation and sustainability, Carrier continues to set the standard in the HVAC industry.