RE-ALARM TIME — This variable specifies the amount of time that will be allowed to elapse between re-alarms. A re- alarm occurs when the conditions that caused the initial alarm continue to persist for the number of minutes specified in this decision. Re-alarming will continue to occur at the specified in- terval until the condition causing the alarm is corrected. This variable can only be changed with the Touch Pilot display, ComfortVIEW, or Network Service Tool. This variable cannot be changed with the Navigator display. To configure this option with the Touch Pilot display:

DISPLAY

PATH

LINE NO.

VALUE

NAME

 

 

 

Realarm

ConfigALARMDEF

 

Range = 1 to 254 minutes

4

255 = Re-Alarm Disabled

Time

 

 

Default = 30 minutes

 

 

 

ALARM SYSTEM NAME — This variable specifies the system element name that will appear in the alarms generated by the unit control. The name can be up to 8 alphanumeric characters in length. This variable can only be changed when using the Touch Pilot display, ComfortVIEW, or Network Service Tool. This variable cannot be changed with the Navigator display.

To configure this option with the Touch Pilot display:

DISPLAY NAME

PATH

LINE NO.

VALUE

Alarm System

ConfigALARMDEF

5

Default =

Name

PRO_XAXQ

 

 

Daylight Saving Time Configuration — The 30XW chiller control contains software which can automati- cally correct for daylight saving time. This software is accessi- ble from the Touch Pilot display, ComfortVIEW, or Network Service Tool. It is not accessible through the Navigator display.

To enable this feature, Daylight Saving Select must be set to

1.The start of Daylight Saving must be configured by setting the Month, Day of Week, and Week of Month. The end for Daylight Saving must also be configured. To configure this op- tion with the Touch Pilot display, see Table 32.

Table 32 — Daylight Savings Time Configuration

DISPLAY NAME

PATH

LINE NO.

VALUE

Activate

ConfigBRODEFS

1

1 or 2

Default = 2

 

 

 

Daylight

ConfigBRODEFS

7

Enable

Saving Select

Default = Dsble

 

 

Entering

ConfigBRODEFS

8

 

Month

ConfigBRODEFS

 

Enter Starting

9

Month for

 

 

 

Daylight Saving

Day of Week

ConfigBRODEFS

 

Enter the Day of

10

the Week Daylight

(1=Monday)

 

 

Saving Starts

 

 

 

Week of Month

ConfigBRODEFS

 

Enter Week of

11

the Month Daylight

 

 

 

Saving Starts

Leaving

ConfigBRODEFS

12

 

Month

ConfigBRODEFS

 

Enter Ending

13

Month for

 

 

 

Daylight Saving

Day of Week

ConfigBRODEFS

 

Enter the Day of

14

the Week Daylight

(1=Monday)

 

 

Saving ends

 

 

 

Week of Month

ConfigBRODEFS

 

Enter Week of

15

the Month Daylight

 

 

 

Saving ends

Capacity Control Overrides — The following ca- pacity control overrides (Active Capacity Override, CAP.S) will modify the normal operation routine. If any of the override conditions listed below are satisfied, the override will deter- mine the capacity change instead of the normal control. Over- rides are listed by priority order and are often linked to unit op- erating modes. See Table 33 for a list of overrides. See the Op- erating Modes section on page 54 for more information regarding operating modes.

Override #1: Cooler Freeze Protection — This override at- tempts to avoid the freeze protection alarm. If the Leaving Water Temperature is less than Brine Freeze Set Point (Brine Freeze Setpoint, LOSP) + 2.0° F (1.1º C) then a stage of capacity is removed.

NOTE: The freeze set point is 34 F (1.1 C) for fresh water systems (Cooler Fluid Type, FLUD=1). The freeze set point is Brine Freeze Set Point (Brine Freeze Setpoint, LOSP), for Medium Temperature Brine systems (Cooler Fluid Type, FLUD=2).

DESCRIPTION

 

 

 

 

 

 

STATUS

 

 

 

 

 

 

POINT

Alarm Routing

0

0

0

0

0

0

0

0

ALRM_CNT

ComfortView™, or ComfortWorks®

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TeLink

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unused

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BacLink or DataLink™

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unused

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

a30-4485

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 26 — Alarm Routing Control

43

Page 43
Image 43
Carrier 30XW150-400 Daylight Savings Time Configuration, Description Status Point, Display Path Line no Value Name

30XW150-400 specifications

The Carrier 30XW150-400 series is a line of water-cooled chillers that exemplifies innovation, efficiency, and reliability in commercial cooling solutions. Designed for medium to large-scale applications, this series is ideal for a variety of settings, including commercial buildings, industrial processes, and chilled water systems.

One of the standout features of the Carrier 30XW series is its efficiency. The chillers utilize advanced variable-speed compressor technology, which allows the units to adapt to varying cooling loads while minimizing energy consumption. This technology not only reduces operational costs but also contributes to better environmental sustainability by lowering greenhouse gas emissions.

The 30XW series chillers are equipped with high-efficiency, scroll compressors that operate quietly and provide significant energy savings. By utilizing enhanced economizer controls, these units can achieve higher efficiency ratings, especially in part-load conditions. The result is an impressive Energy Efficiency Ratio (EER) and Seasonal Energy Efficiency Ratio (SEER), making these units a smart choice for energy-conscious businesses.

In terms of reliability, the Carrier 30XW150-400 series features robust construction and an array of safety and monitoring systems. The units come with advanced diagnostics that help in quickly identifying and addressing any operational issues. This proactive approach ensures reliability and minimizes downtime, which is crucial for maintaining optimal temperature controls in critical environments.

Additionally, the chillers incorporate environmentally friendly refrigerants that comply with the latest regulations, making them a sustainable choice for modern commercial applications. Their compact design allows for flexible installation options, and the integrated control systems provide the ability to optimize performance based on specific building management demands.

User-friendly interfaces and remote monitoring capabilities further enhance the ease of operation, allowing facility managers to have real-time insight into performance metrics and system health. This level of control contributes to better maintenance planning and maximizes the lifespan of the equipment.

In summary, the Carrier 30XW150-400 series of water-cooled chillers combines advanced technology, energy efficiency, and reliable performance, making it an ideal solution for various commercial and industrial cooling needs. With its commitment to innovation and sustainability, Carrier continues to set the standard in the HVAC industry.