Carrier 30XW150-400 Pds-Xaxqxw, Group Display Screen a30-4910.ep, Point Data Dialog Box a30-4471

Models: 30XW150-400

1 148
Download 148 pages 52.93 Kb
Page 4
Image 4
PDS-XAXQXW

“ALARM INDICATOR LIGHT” activates when a new alarm condition occurs. The alarm indicator light LED, located on the right side of the display, remains

activated until it is manually reset using the Reset button on the Main menu.

“START/STOP BUTTON” enables the user to start or stop the chiller from the Touch Pilot™ display. See Enable-Off-Remote Contact Switch (SW1) on

page 16 for additional information.

Several items are password protected. When required, a Password dialog box will be displayed for field input of the password. The default password is 3333. The password can be changed if desired.

Power-Up Display — When the Touch Pilot display is pow- ered up, it displays an initialization progress bar and attaches (initiates communication) to the Main Base Board. The Touch Pilot display then shows that controller’s default Group Dis- play screen. See Fig. 2. This is a user-configured display screen with up to 9 points on 8 separate screens. For more information on adding or removing points from the Group Display screen, see the Group Display Screens section on page 7.

Touch any of the screen point buttons and Point Data Dialog box will be displayed with expanded information. In the exam- ple shown, the CTRL_PNT button in the bottom left corner was selected. See Fig. 2 and 3.

To exit the box, press Fig. 2 — Group Display Screen a30-4910.ep .

Main Menu Display — The default screen for the Touch Pilot controller is the Group Display screen. To access the Main Menu, press the Fig. 3 — Point Data Dialog Box a30-4471 button. The screen shown in Fig. 4 will be displayed. Selecting a button will display the screens associat- ed with that category. The user can also access the login screen from the Main Menu if needed.

Touch Pilot Menu Structure — The user can navigate through the Touch Pilot display screens by selecting the buttons that ap- pear on the screen. When a button is selected, either a sub- menu or a list of point names and values will be shown. Sub- menus will display a list of associated point names. See Fig. 5 for the Touch Pilot menu structure.

If the list of point names and values are shown, the top line of the display is the table name. The line and total line counter is displayed in the upper right corner of the display. Selecting an item will cause a Point Data dialog box to appear.

Setup Menu Screen — The Setup Menu screen, shown in Fig. 6, is accessed by pressing the Setup button from the Main Menu. This configuration allows the user to configure the basic operation and look of the display. Table 1 summarizes the Set- up Menu functions.

PDS-XAXQXW

Fig. 2 — Group Display Screen a30-4910.ep

Fig. 3 — Point Data Dialog Box a30-4471

Fig. 4 — Main Menu Display a30-4472

4