Machine Start Delay — An option to delay the start of the machine is also available. This parameter is useful in keep- ing multiple machines from starting at the same time in case of a power failure. The parameter has a factory default of 1 minute. This parameter also has a role in the timing for a chilled water flow switch alarm. The flow switch status is not checked until the delay time has elapsed.

To configure this option with the Touch Pilot display:

DISPLAY NAME

PATH

LINE

 

VALUE

NO.

 

 

 

 

 

 

 

 

Unit Off to

Main Menu

 

6

Default = 1 Minute

On Delay

ConfigUSER

 

 

 

 

To configure this option with the Navigator display:

 

 

 

 

 

 

ITEM

ITEM EXPANSION

 

PATH

 

VALUE

DELY

Minutes Off Time

ConfigurationOPTN

 

Default =

 

1 Minute

 

 

 

 

 

 

 

Circuit/Compressor Staging and Loading —

The AquaForce® 30XW chillers employ one compressor per circuit. As a result, circuit and compressor staging are the same. The control has several control option parameters to load the compressors. The circuit/compressor start can be config- ured as well as the loading of each circuit/compressor.

CIRCUIT/COMPRESSOR STAGING — The control can be configured to decide which circuit/compressor starts first, by configuring Lead/Lag Circuit Select (Staged Loading Sequence, LLCS). Three options for this variable are allowed: Automatic Lead-Lag, Circuit A Leads or Circuit B Leads. The factory default is Automatic Lead-Lag.

The automatic lead-lag function determines which circuit/ compressor starts. When enabled, the control will determine which circuit/compressor starts to even the wear of the com- pressor. The compressor wear factor (combination of starts and run hours) is used to determine which compressor starts.

Compressor Wear Factor = (Compressor Starts) + 0.1 (Com- pressor Run Hours)

The circuit/compressor with the lowest compressor wear factor is the circuit that starts first.

If starting a particular circuit/compressor first is desired, that can also be configured with the same variable.

To configure this option with the Touch Pilot display:

DISPLAY NAME

PATH

LINE

 

VALUE

NO.

 

 

 

 

 

 

 

 

0

(Automatic Lead-lag)

Circuit Loading

Main Menu

 

1

(Circuit A Leads)

1

2

(Circuit B Leads)

Sequence

ConfigUSER

 

Default = 0

 

 

 

 

 

 

(Automatic Lead-lag)

To configure this option with the Navigator display:

ITEM

ITEM EXPANSION

PATH

VALUE

 

 

 

Range: Automatic,

LLCS

Lead/Lag

Configuration

Cir A Leads,

Cir B Leads,

Circuit Select

OPTN

 

Cir C Leads

 

 

 

 

 

 

Default – Automatic

CIRCUIT/COMPRESSOR LOADING — The control can be configured to stage the circuit/compressors. The Loading Sequence Select (Circuit Loading Sequence, LOAD) setting determines how the control will perform loading. The configu- ration can be set to Equal or Staged.

Equal Loading — With Equal loading, the circuit which starts first will maintain the minimum stage of capacity with the slide valve fully unloaded. When additional capacity is required, the next circuit with the lowest compressor wear factor is started with its slide valve at minimum position. As additional capaci- ty is required, the slide valve for a circuit will be adjusted in approximately 5% increments to match capacity requirements.

The control will alternate between circuits to maintain the same percentage of capacity on each circuit.

Staged Loading — If staged loading is selected, the circuit which starts first will gradually load its slide valve to match capacity requirements until the circuit is fully loaded. Once the circuit is fully loaded and additional capacity is required, the control will start an additional circuit fully unloaded. The con- trol will gradually unload the circuit which was fully loaded to match capacity requirements.

To configure this option with the Touch Pilot™ display:

DISPLAY NAME

 

PATH

LINE

 

VALUE

 

NO.

 

 

 

 

 

 

 

Staged Loading

Main

 

 

 

Default = No

 

4

 

No (Equal)

Sequence

MenuConfigUSER

 

 

 

Yes (Staged)

 

 

 

 

 

 

To configure this option with the Navigator™ display:

 

 

 

 

 

 

ITEM

ITEM EXPANSION

PATH

 

 

VALUE

LOAD

Loading Sequence

ConfigurationOPTN

Default = Equal

Equal

 

Select

 

 

 

Staged

 

 

 

 

 

Minimum Load Control — Minimum Load Control can be a factory-installed option or a field-installed accessory. If installed, and its operation is desired, the Minimum Load Control must be enabled. Once enabled, the valve will be oper- ational only during the first stage of cooling.

To configure this option with the Touch Pilot display:

DISPLAY NAME

PATH

LINE

VALUE

NO.

 

 

 

 

 

 

Default = No

Hot Gas

Main

 

No (No Minimum

MenuService

14

Load Control)

Bypass Select

FACTORY

 

Yes (Minimum Load

 

 

 

 

 

Control Installed)

A power cycle is required for the values to take effect. To configure this option with the Navigator display:

ITEM

ITEM

PATH

VALUE

EXPANSION

 

 

 

 

 

 

No = No Minimum

HGBP

Hot Gas

ConfigurationUNIT

Load Control

 

Bypass Select

 

Yes = Minimum Load

 

 

 

Control Installed

A power cycle is required for the values to take effect.

Dual Chiller Control — The dual chiller routine is available for the control of two units installed in series or paral- lel supplying chilled fluid on a common loop. One chiller must be configured as the master chiller, the other as the slave chill- er. An additional leaving fluid temperature thermistor (dual chiller LWT) must be installed in the common chilled water piping as described in the Installation Instructions for both the master and slave chillers. See the Field Wiring section in the 30XW Installation Instructions for dual chiller LWT sensor control wiring.

The control algorithm relies on several parameters that must be field configured for operation. Both chillers must be on the same Carrier Comfort Network® bus with different addresses. On both chillers, Master/Slave Select (Master/Slave Select, MSSL) must be enabled. The water piping arrangement, Chill- ers in Series (Chiller in Series, SERI), must be configured. The master chiller must be programmed with the Slave Chiller Address (Slave Address, SLVA). Additional optional pro- gramming parameters may be configured to meet application requirements.

Lead/Lag Balance Select (Lead Lag Select, LLBL) deter- mines which chiller is the lead machine. The options are Al- ways Lead, Lag if Fail, and Runtime Select. Under Runtime Select control, the lead chiller will change based on the time in- crement selected in the Lead/Lag Balance Delta configuration (Lead/Lag Balance Data, LLBD). If the run hour difference

29

Page 29
Image 29
Carrier 30XW150-400 specifications Circuit/Compressor Staging and Loading

30XW150-400 specifications

The Carrier 30XW150-400 series is a line of water-cooled chillers that exemplifies innovation, efficiency, and reliability in commercial cooling solutions. Designed for medium to large-scale applications, this series is ideal for a variety of settings, including commercial buildings, industrial processes, and chilled water systems.

One of the standout features of the Carrier 30XW series is its efficiency. The chillers utilize advanced variable-speed compressor technology, which allows the units to adapt to varying cooling loads while minimizing energy consumption. This technology not only reduces operational costs but also contributes to better environmental sustainability by lowering greenhouse gas emissions.

The 30XW series chillers are equipped with high-efficiency, scroll compressors that operate quietly and provide significant energy savings. By utilizing enhanced economizer controls, these units can achieve higher efficiency ratings, especially in part-load conditions. The result is an impressive Energy Efficiency Ratio (EER) and Seasonal Energy Efficiency Ratio (SEER), making these units a smart choice for energy-conscious businesses.

In terms of reliability, the Carrier 30XW150-400 series features robust construction and an array of safety and monitoring systems. The units come with advanced diagnostics that help in quickly identifying and addressing any operational issues. This proactive approach ensures reliability and minimizes downtime, which is crucial for maintaining optimal temperature controls in critical environments.

Additionally, the chillers incorporate environmentally friendly refrigerants that comply with the latest regulations, making them a sustainable choice for modern commercial applications. Their compact design allows for flexible installation options, and the integrated control systems provide the ability to optimize performance based on specific building management demands.

User-friendly interfaces and remote monitoring capabilities further enhance the ease of operation, allowing facility managers to have real-time insight into performance metrics and system health. This level of control contributes to better maintenance planning and maximizes the lifespan of the equipment.

In summary, the Carrier 30XW150-400 series of water-cooled chillers combines advanced technology, energy efficiency, and reliable performance, making it an ideal solution for various commercial and industrial cooling needs. With its commitment to innovation and sustainability, Carrier continues to set the standard in the HVAC industry.