APPENDIX A — TOUCH PILOT™ DISPLAY TABLES (cont)
88
TOUCH PILOT DESCRIPTION | TOUCH PILOT | TOUCH PILOT PATH | LINE | READ/ | CCN TABLE NAME | |
POINT NAME | WRITE | |||||
|
|
|
| |||
Compressor Output |
|
|
|
|
| |
Circuit A | COMP_A | MAIN MENU\Status\CIRCA_D | 2 | RO | Status Display Tables\CIRCA_D | |
Circuit B | COMP_B | MAIN MENU\Status\CIRCB_D | 2 | RO | Status Display Tables\CIRCB_D | |
Circuit C | COMP_C | MAIN MENU\Status\CIRCC_D | 2 | RO | Status Display Tables\CIRCC_D | |
Compressor Suction Temp |
|
|
|
|
| |
Circuit A | SUCT_T_A | MAIN MENU\Status\CIRCA_AN | 14 | RO | Status Display Tables\CIRCA_AN | |
Circuit B | SUCT_T_B | MAIN MENU\Status\CIRCB_AN | 14 | RO | Status Display Tables\CIRCB_AN | |
Circuit C | SUCT_T_C | MAIN MENU\Status\CIRCC_AN | 14 | RO | Status Display Tables\CIRCC_AN | |
Condenser Entering Fluid | COND_EWT | MAIN MENU\Status\STATEGEN | 35 | RO | Status Display Tables\STATEGEN | |
Condenser Flow Status | CONDFLOW | MAIN MENU\Status\STATEGEN | 14 | RO | Status Display Tables\STATEGEN | |
Condenser Fluid Type | cond_typ | MAIN MENU\Service\SERVICE1 | 4 | RW | Service Configuration Tables\SERVICE1 | |
Condenser Leaving Fluid | COND_LWT | MAIN MENU\Status\STATEGEN | 36 | RO | Status Display Tables\STATEGEN | |
Condenser Pump #1 Command | HPUMP_1 | MAIN MENU\Status\STATEGEN | 23 | RO | Status Display Tables\STATEGEN | |
Condenser Pump #1 Hours | hr_hpum1 | MAIN MENU\Service\UPDTHOUR | 15 | RW | Service Configuration Tables\UPDTHOUR | |
Condenser Pump #1 Hours | hr_hpum1 | MAIN MENU\Status\STRTHOUR | 11 | RO | Status Display Tables\STRTHOUR | |
Condenser Pump #2 Command | HPUMP_2 | MAIN MENU\Status\STATEGEN | 24 | RO | Status Display Tables\STATEGEN | |
Condenser Pump #2 Hours | hr_hpum2 | MAIN MENU\Service\UPDTHOUR | 16 | RW | Service Configuration Tables\UPDTHOUR | |
Condenser Pump #2 Hours | hr_hpum2 | MAIN MENU\Status\STRTHOUR | 12 | RO | Status Display Tables\STRTHOUR | |
Condenser Pump 1 | Q_HPMP1 | MAIN MENU\Status\QCK_TST1 | 39 | RW | Status Display Tables\QCK_TST1 | |
Condenser Pump 2 | Q_HPMP2 | MAIN MENU\Status\QCK_TST1 | 40 | RW | Status Display Tables\QCK_TST1 | |
Condenser Pumps Rotation | Mode_17 | MAIN MENU\Status\MODES | 18 | RO | Status Display Tables\MODES | |
Condenser Pumps Sequence | hpump_seq | MAIN MENU\Config\USER | 7 | RW | Configuration Tables\USER | |
Condenser Water Val Sel | cond_val | MAIN MENU\Service\FACTORY | 13 | RW | Service Configuration Tables\FACTORY | |
Control Point | CTRL_PNT | MAIN MENU\Maint\LOADFACT | 5 | RO | Maintenance Display Tables\LOADFACT | |
Control Point | CTRL_PNT | MAIN MENU\Status\GENUNIT | 28 | RO | Status Display Tables\GENUNIT | |
Control Type | ctr_type | MAIN MENU\Status\GENUNIT | 3 | RO | Status Display Tables\GENUNIT | |
Controlled Temp Error | tp_error | MAIN MENU\Maint\LOADFACT | 7 | RO | Maintenance Display Tables\LOADFACT | |
Controlled Water Temp | CTRL_WT | MAIN MENU\Status\GENUNIT | 29 | RO | Status Display Tables\GENUNIT | |
Cool Changeover Setpt | cauto_sp | MAIN MENU\Setpoint\SETPOINT | 29 | RW | Setpoint Configuration Tables\SETPOINT | |
Cooler Entering Fluid | COOL_EWT | MAIN MENU\Status\STATEGEN | 33 | RO | Status Display Tables\STATEGEN | |
Cooler Entering Fluid | COOL_EWT | MAIN MENU\Status\STATEGEN | 33 | RO | Status Display Tables\STATEGEN | |
Cooler Exchange DT Cir A | pinch_a | MAIN MENU\Maint\EXV_CTRL | 6 | RO | Maintenance Display Tables\EXV_CTRL | |
Cooler Exchange DT Cir B | pinch_b | MAIN MENU\Maint\EXV_CTRL | 13 | RO | Maintenance Display Tables\EXV_CTRL | |
Cooler Exchange DT Cir C | pinch_c | MAIN MENU\Maint\EXV_CTRL | 20 | RO | Maintenance Display Tables\EXV_CTRL | |
Cooler Flow Setpoint Out | SET_FLOW | MAIN MENU\Status\STATEGEN | 18 | RO | Status Display Tables\STATEGEN | |
Cooler Flow Switch | FLOW_SW | MAIN MENU\Status\STATEGEN | 12 | RO | Status Display Tables\STATEGEN | |
Cooler Fluid Type | flui_typ | MAIN MENU\Service\SERVICE1 | 1 | RW | Service Configuration Tables\SERVICE1 | |
Cooler Heater Active | Mode_06 | MAIN MENU\Status\MODES | 7 | RO | Status Display Tables\MODES | |
Cooler Heater Command | COOLHEAT | MAIN MENU\Status\STATEGEN | 26 | RO | Status Display Tables\STATEGEN | |
Cooler Heater Delta Spt | heatersp | MAIN MENU\Service\SERVICE1 | 17 | RW | Service Configuration Tables\SERVICE1 | |
Cooler Heater Output | Q_CL_HT | MAIN MENU\Status\QCK_TST1 | 36 | RW | Status Display Tables\QCK_TST1 | |
Cooler Heater Select | heat_sel | MAIN MENU\Service\FACTORY | 12 | RW | Service Configuration Tables\FACTORY | |
Cooler Heater Temp | T_HEATER | MAIN MENU\Status\STATEGEN | 37 | RO | Status Display Tables\STATEGEN | |
Cooler Leaving Fluid | COOL_LWT | MAIN MENU\Status\STATEGEN | 34 | RO | Status Display Tables\STATEGEN | |
Cooler Leaving Fluid | COOL_LWT | MAIN MENU\Status\STATEGEN | 34 | RO | Status Display Tables\STATEGEN | |
Cooler Pinch Ctl Point A | pinch_spa | MAIN MENU\Maint\EXV_CTRL | 7 | RO | Maintenance Display Tables\EXV_CTRL | |
Cooler Pinch Ctl Point B | pinch_spb | MAIN MENU\Maint\EXV_CTRL | 14 | RO | Maintenance Display Tables\EXV_CTRL | |
Cooler Pinch Ctl Point C | pinch_spc | MAIN MENU\Maint\EXV_CTRL | 21 | RO | Maintenance Display Tables\EXV_CTRL | |
Cooler Pump #1 Command | CPUMP_1 | MAIN MENU\Status\STATEGEN | 20 | RO | Status Display Tables\STATEGEN | |
Cooler Pump #1 Hours | hr_cpum1 | MAIN MENU\Status\STRTHOUR | 9 | RO | Status Display Tables\STRTHOUR | |
Cooler Pump #2 Command | CPUMP_2 | MAIN MENU\Status\STATEGEN | 21 | RO | Status Display Tables\STATEGEN | |
Cooler Pump #2 Hours | hr_cpum2 | MAIN MENU\Status\STRTHOUR | 10 | RO | Status Display Tables\STRTHOUR |
LEGEND
RO — Read Only
RW — Read/Write