APPENDIX B — NAVIGATOR™ DISPLAY TABLES (cont)

MODE — TEMPERATURE

ITEM

EXPANSION

UNITS

RANGE

COMMENT

WRITE

CCN TABLE

CCN POINT

PAGE

STATUS

NO.

 

 

 

 

 

 

 

UNIT

UNIT TEMPERATURES

 

 

 

 

 

 

 

CEWT

Cooler Entering Fluid

XXX.X

–40-245 F

 

 

STATEGEN

COOL_EWT

 

CLWT

 

(deg F/deg C)

(–40-118 C)

 

 

 

 

 

Cooler Leaving Fluid

XXX.X

–40-245 F

 

 

STATEGEN

COOL_LWT

 

CD.LT

 

(deg F/deg C)

(–40-118 C)

 

 

 

 

 

Condenser Entering Fluid

XXX.X

–40-245 F

Not supported.

 

 

COND_LWT

 

CD.ET

 

(deg F/deg C)

(–40-118 C)

Not supported.

 

 

 

 

Condenser Leaving Fluid

XXX.X

–40-245 F

 

 

 

COND_EWT

 

OAT

 

(deg F/deg C)

(–40-118 C)

 

 

 

 

 

Outside Air Temperature

XXX.X

–40-245 F

 

 

GENUNIT

OAT

 

CHWS

 

(deg F/deg C)

(–40-118 C)

 

 

 

 

 

Lead/Lag Leaving Fluid

XXX.X

–40-245 F

 

 

STATEGEN

CHWS

 

SPT

 

(deg F/deg C)

(–40-118 C)

 

 

 

 

 

Optional Space Temp

XXX.X

–40-245 F

 

 

STATEGEN

SPACETMP

 

THHR

 

(deg F/deg C)

(–40-118 C)

 

 

 

 

 

Cooler Heater Temp

XXX.X

–40-245 F

 

 

 

TH_HEATER

 

THR.C

 

(deg F/deg C)

(–40-118 C)

 

 

 

 

 

Cooler Heat Temp Cir C

XXX.X

–40-245 F

 

 

 

T_HEAT_C

 

 

 

(deg F/deg C)

(–40-118 C)

 

 

 

 

 

CIR.A

CIRCUIT A TEMPERATURES

 

 

 

 

 

 

 

SCT.A

Sat Cond Temp Circ A

XXX.X

–40-245 F

 

 

CIRCA_AN

SCT_A

 

SST.A

 

(deg F/deg C)

(–40-118 C)

 

 

 

 

 

Sat Suction Temp Circ A

XXX.X

–40-245 F

 

 

CIRCA_AN

SST_A

 

DGT.A

 

(deg F/deg C)

(–40-118 C)

 

 

 

 

 

Discharge Gas Temp Cir A

XXX.X

–40-245 F

 

 

 

DGT_A

 

SGT.A

 

(deg F/deg C)

(–40-118 C)

 

 

 

 

 

Suction Gas Temp Circ A

XXX.X

–40-245 F

 

 

CIRCA_AN

SUCT_T_A

 

SUP.A

 

(deg F/deg C)

(–40-118 C)

 

 

 

 

 

Superheat Temp Circ A

XXX.X (ΔF/ΔC)

 

 

 

CIRCA_AN

SH_A

 

ECT.A

Economizer Gas Temp A

XXX.X

–40-245 F

 

 

 

ECO_TP_A

 

ESH.A

 

(deg F/deg C)

(–40-118 C)

 

 

 

 

 

Economizer Superheat A

XXX.X

–40-245 F

 

 

 

ECO_SH_A

 

CTP.A

 

(deg F/deg C)

(–40-118 C)

 

 

 

 

 

Motor Temperature Cir A

XXX.X

–40-245 F

 

 

 

CP_TMP_A

 

 

 

(deg F/deg C)

(–40-118 C)

 

 

 

 

 

CIR.B

CIRCUIT B TEMPERATURES

 

 

 

 

 

 

 

SCT.B

Sat Cond Temp Circ B

XXX.X

–40-245 F

 

 

CIRCB_AN

SCT_B

 

SST.B

 

(deg F/deg C)

(–40-118 C)

 

 

 

 

 

Sat Suction Temp Circ B

XXX.X

–40-245 F

 

 

CIRCB_AN

SST_B

 

DGT.B

 

(deg F/deg C)

(–40-118 C)

 

 

 

 

 

Discharge Gas Temp Cir B

XXX.X

–40-245 F

 

 

 

DGT_B

 

SGT.B

 

(deg F/deg C)

(–40-118 C)

 

 

 

 

 

Suction Gas Temp Circ B

XXX.X

–40-245 F

 

 

CIRCB_AN

SUCT_T_B

 

SUP.B

 

(deg F/deg C)

(–40-118 C)

 

 

 

 

 

Superheat Temp Circ B

XXX.X (ΔF/ΔC)

 

 

 

CIRCB_AN

SH_B

 

ECT.B

Economizer Gas Temp B

XXX.X

–40-245 F

 

 

 

ECO_TP_B

 

ESH.B

 

(deg F/deg C)

(–40-118 C)

 

 

 

 

 

Economizer Superheat B

XXX.X

–40-245 F

 

 

 

ECO_SH_B

 

CTP.B

 

(deg F/deg C)

(–40-118 C)

 

 

 

 

 

Motor Temperature Cir B

XXX.X

–40-245 F

 

 

 

CP_TMP_B

 

 

 

(deg F/deg C)

(–40-118 C)

 

 

 

 

 

CIR.C

CIRCUIT C TEMPERATURES

 

 

 

 

CIRCC_AN

 

 

SCT.C

Sat Cond Temp Circ C

XXX.X

–45-245 F

 

 

CIRCC_AN

SCT_C

 

SST.C

 

(deg F/deg C)

(–43-118 C)

 

 

 

 

 

Sat Suction Temp Circ C

XXX.X

–45-245 F

 

 

CIRCC_AN

SST_C

 

DGT.C

 

(deg F/deg C)

(–43-118 C)

 

 

 

 

 

Discharge Gas Temp Cir C

XXX.X

–40-245 F

 

 

 

DGT_C

 

SGT.C

 

(deg F/deg C)

(–40-118 C)

 

 

 

 

 

Suction Gas Temp Circ C

XXX.X

–45-245 F

 

 

CIRCC_AN

SUCT_T_C

 

SUP.C

 

(deg F/deg C)

(–43-118 C)

 

 

 

 

 

Superheat Temp Circ C

XXX.X (ΔF/ΔC)

 

 

 

CIRCC_AN

SH_C

 

ECT.C

Economizer Gas Temp C

XXX.X

 

 

 

 

ECO_TP_C

 

ESH.C

 

(deg F/deg C)

 

 

 

 

 

 

Economizer Superheat C

XXX.X

 

 

 

 

ECO_SH_C

 

CTP.C

 

(deg F/deg C)

 

 

 

 

 

 

Motor Temperature Cir C

XXX.X

 

 

 

 

CP_TMP_C

 

 

 

(deg F/deg C)

 

 

 

 

 

 

108

Page 108
Image 108
Carrier 30XW150-400 specifications 108, Mode Temperature

30XW150-400 specifications

The Carrier 30XW150-400 series is a line of water-cooled chillers that exemplifies innovation, efficiency, and reliability in commercial cooling solutions. Designed for medium to large-scale applications, this series is ideal for a variety of settings, including commercial buildings, industrial processes, and chilled water systems.

One of the standout features of the Carrier 30XW series is its efficiency. The chillers utilize advanced variable-speed compressor technology, which allows the units to adapt to varying cooling loads while minimizing energy consumption. This technology not only reduces operational costs but also contributes to better environmental sustainability by lowering greenhouse gas emissions.

The 30XW series chillers are equipped with high-efficiency, scroll compressors that operate quietly and provide significant energy savings. By utilizing enhanced economizer controls, these units can achieve higher efficiency ratings, especially in part-load conditions. The result is an impressive Energy Efficiency Ratio (EER) and Seasonal Energy Efficiency Ratio (SEER), making these units a smart choice for energy-conscious businesses.

In terms of reliability, the Carrier 30XW150-400 series features robust construction and an array of safety and monitoring systems. The units come with advanced diagnostics that help in quickly identifying and addressing any operational issues. This proactive approach ensures reliability and minimizes downtime, which is crucial for maintaining optimal temperature controls in critical environments.

Additionally, the chillers incorporate environmentally friendly refrigerants that comply with the latest regulations, making them a sustainable choice for modern commercial applications. Their compact design allows for flexible installation options, and the integrated control systems provide the ability to optimize performance based on specific building management demands.

User-friendly interfaces and remote monitoring capabilities further enhance the ease of operation, allowing facility managers to have real-time insight into performance metrics and system health. This level of control contributes to better maintenance planning and maximizes the lifespan of the equipment.

In summary, the Carrier 30XW150-400 series of water-cooled chillers combines advanced technology, energy efficiency, and reliable performance, making it an ideal solution for various commercial and industrial cooling needs. With its commitment to innovation and sustainability, Carrier continues to set the standard in the HVAC industry.