Carrier 30XW150-400 specifications 4 to 20 mA Set Point Control

Models: 30XW150-400

1 148
Download 148 pages 52.93 Kb
Page 27
Image 27
Fig. 18 — 4 to 20 mA Set Point Control

 

90

 

 

 

 

 

 

 

 

 

 

 

80

 

 

 

 

 

 

 

 

 

 

 

70

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Max LWT

 

 

60

 

 

 

 

 

 

 

 

 

 

Point

50

 

 

 

 

 

 

 

 

 

 

 

Min LWT, Cooler Fluid Type = 1, FLUD=Water

 

 

 

 

 

 

Set

 

 

 

 

 

 

 

40

 

 

 

 

 

 

 

 

 

 

 

30

 

 

 

 

 

 

 

 

 

 

 

20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Min LWT, Cooler Fluid Type = 1, FLUD=Brine

 

 

 

 

10

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

0

2

4

6

8

10

12

14

16

18

20

 

 

 

 

 

 

mA Signal

 

 

 

 

A30-4830

Fig. 18 — 4 to 20 mA Set Point Control

To configure this option while using a Navigator display:

ITEM

ITEM EXPANSION

PATH

VALUE

SP.SE

Setpoint Select

Operating ModesSLCT

4-20 mA Setp

Dual Switch — When Set Point Select (Setpoint Select, SP.SE) is configured to 4 (Dual Setp Sw), the unit’s active set point is based on Cooling Set Point 1 (Cooling Setpoint 1, CSP.1) when the Dual Set Point switch contact is open and Cooling Set Point 2 (Cooling Setpoint 2, CSP.2) when it is closed.

To configure this option while using a Touch Pilot display:

DISPLAY NAME

PATH

LINE

VALUE

NO.

 

 

 

Setpoint Select

StatusGENUNIT

25

4 (Dual

Setpoint Switch)

 

 

 

To change this value, a Control Point Force must be applied. When configured correctly, Setpoint Control will indicate Setp Sw.

To configure this option while using a Navigator display:

ITEM

ITEM EXPANSION

PATH

VALUE

SP.SE

Setpoint Select

Operating ModesSLCT

Dual

Setp Sw

 

 

 

Chilled Water Fluid Type Selection — The chilled water fluid must be configured. The fluid type must be config- ured to obtain the proper leaving water set point control range and freeze protection. The Cooler Fluid Type (Cooler Fluid Type, FLUD) can be set to water or brine.

FRESH WATER — Configure the unit for Cooler Fluid Type (Cooler Fluid Type, FLUD) to water for units without brine or glycol installed in the chilled water loop. The factory default fluid type is fresh water. Use this option for fresh water sys- tems. This will allow for a water temperature set point of 38 to 60 F (3.3 to 15.5 C). With water as the selection, the Freeze Point is fixed at 34 F (1.1 C).

To configure this option with the Touch Pilot display:

DISPLAY

 

PATH

LINE

VALUE

NAME

 

 

NO.

 

 

 

 

 

Cooler

 

Main MenuServiceSERVICE1

1

1 = Water

Fluid Type

To configure this option with the Navigator display:

 

 

 

 

 

ITEM

 

ITEM EXPANSION

PATH

 

VALUE

FLUD

 

Cooler Fluid Type

 

ConfigurationSERV

Water

BRINE OR GLYCOL OPERATION — Configure the unit for Cooler Fluid Type (Cooler Fluid Type, FLUD) to brine for brine or glycol chilled water loops. This option will allow for a set point temperature range of 14 to 60 F (–10.0 to 15.5 C). Before configuring this selection, confirm that a suitable anti- freeze has been added and is at a sufficient concentration to protect the loop. Additionally, the Brine Freeze Set Point (Brine Freeze Setpoint, LOSP) must be set for proper freeze protection operation. Set the Brine Freeze Set Point to the burst protection provided by the glycol concentration. This value will be Freeze Point for the fluid.

To configure this option with the Touch Pilot display:

DISPLAY

PATH

LINE

VALUE

NAME

NO.

 

 

Cooler Fluid

Main Menu

1

2 = Brine

Type

ServiceSERVICE1

 

 

Brine Freeze

Main Menu

3

Dependent on

Setpoint

ServiceSERVICE1

fluid concentration

 

To configure this option with the Navigator display:

ITEM

ITEM EXPANSION

PATH

VALUE

FLUD

Cooler Fluid Type

ConfigurationSERV

Brine

LOSP

Brine Freeze

ConfigurationSERV

Dependent on

 

Setpoint

 

fluid concentration

27

Page 27
Image 27
Carrier 30XW150-400 specifications 4 to 20 mA Set Point Control, To configure this option with the Navigator display