Generac Power Systems QT036 Application & Engineering Data, Engine Specifications, Fuel System

Page 2

APPLICATION & ENGINEERING DATA

COMMERCIAL 30 kW

GENERATOR SPECIFICATIONS

TYPE

Synchronous

ROTOR INSULATION

Class F

STATOR INSULATION

Class F

TOTAL HARMONIC DISTORTION

<5%

TELEPHONE INTERFERENCE FACTOR (TIF)

<50

ALTERNATOR OUTPUT LEADS 3 PHASE

4 wire

BEARINGS

Sealed Ball

COUPLING

Flexible Disc

LOAD CAPACITY (STANDBY RATING)

30 kW

EXCITATION SYSTEM

Direct

ENGINE SPECIFICATIONS

MAKE

Generac

MODEL

In line

CYLINDERS

4

DISPLACEMENT

1.6 Liter

BORE

3.15

STROKE

3.13

COMPRESSION RATIO

9.75:1

INTAKE AIR SYSTEM

Naturally Aspirated

VALVE SEATS

Replaceable

LIFTER TYPE

Hydraulic

NOTE: Generator rating and performance in accordance with ISO8528-5, BS5514, SAE J1349, ISO3046, and DIN6271 standards.

VOLTAGE REGULATOR

TYPE

Electronic

SENSING

Single Phase

REGULATION

± 1%

FEATURES

V/F Adjustable

 

Adjustable Voltage and Gain

 

LED Indicators

GOVERNOR SPECIFICATIONS

TYPE

Electronic

FREQUENCY REGULATION

Isochronous

STEADY STATE REGULATION

± 0.25

ENGINE LUBRICATION SYSTEM

OIL PUMP

Gear

OIL FILTER

Full flow spin-on cartridge

CRANKCASE CAPACITY

4 Quarts

GENERATOR FEATURES

Revolving field heavy duty generator

Directly connected to the engine

Operating temperature rise 120 °C above a 40 °C ambient Insulation is Class F rated at 130 °C rise

All models are fully prototyped tested

ENGINE COOLING SYSTEM

 

TYPE

Closed

WATER PUMP

Belt driven

FAN SPEED

2550

FAN DIAMETER

15 inches

FAN MODE

Pusher

CONTROL PANEL FEATURES

SEVEN LED INDICATOR LIGHTS

ADDITIONAL FUNCTIONS

• System ready

• Utility sensing

• Low fuel pressure

• Delay on utility failure for engine start

• Low battery

• Engine warm-up before transfer

• Low oil pressure

• Delay to retransfer to utility

• High coolant temp/low coolant temp

• Engine cooldown timer

• Overspeed

• Exerciser not set

• Overcrank

 

FUEL SYSTEM

FUEL TYPE

Natural gas, propane vapor

CARBURETOR

Down Draft

SECONDARY FUEL REGULATOR

Standard

FUEL SHUT OFF SOLENOID

Standard

OPERATING FUEL PRESSURE

5” - 14” H2O

INTERNAL FUNCTIONS:

3 position switch (auto, off and manual)

2 wire start for any transfer switch

Communicates with the Generac RTS transfer switch

Built-in 7 day exerciser

Selectable engine speed at exercise

Governor controller is built into the master control board

Temperature range -40 °C to 70 °C

ELECTRICAL SYSTEM

BATTERY CHARGE ALTERNATOR

.............................................................12V 30 Amp

STATIC BATTERY CHARGER

2 Amp

RECOMMENDED BATTERY

Group 26, 525 CCA

SYSTEM VOLTAGE

12 Volts

Rating definitions - Standby: Applicable for supplying emergency power for the duration of the utility power outage. No overload capability is available for this rating. (All ratings in accordance with BS5514, ISO3046 and DIN6271). (All ratings in accordance with BS5514, ISO3046, ISO8528 and DIN6271).

Image 2