
COMMERCIAL 30 kW
COMMERCIAL SERIES
OPERATING DATA
  | 
  | 
  | COMMERCIAL 30 kW  | |
KW RATING | 
  | 
  | 30 LP / 29 NG  | 
  | 
  | 
  | 
  | 
  | 
  | 
ENGINE SIZE | 
  | 
  | 1.6 Liter 4 cyl. inline  | 
  | 
  | 
  | 
  | 
  | |
GENERATOR OUTPUT VOLTAGE/KW - 60Hz  | KW  | AMP  | CB Size  | |
120/208V, three phase, 0.8 pf  | 
  | 30 LP / 29 NG  | 104.2 LP / 100.7 NG  | 125  | 
120/240V, three phase, 0.8 pf  | 
  | 30 LP / 29 NG  | 90.3 LP / 87.3 NG  | 100  | 
277/480V, three phase, 0.8 pf  | 
  | 30 LP / 29 NG  | 45.1 LP / 43.6 NG  | 50  | 
  | 
  | 
  | 
  | 
  | 
GENERATOR LOCKED ROTOR KVA  | 
  | 
  | 
  | 
  | 
AVAILABLE @ VOLTAGE DIP OF 35%  | 
  | 
  | 
  | 
  | 
208 or 240V three phase  | 
  | 
  | 56  | 
  | 
480V three phase  | 
  | 
  | 62  | 
  | 
  | 
  | 
  | 
  | |
ENGINE FUEL CONSUMPTION (Natural Gas) (Propane)  | Natural Gas  | 
  | Propane  | |
  | 
  | (ft3/hr.)  | (gal/hr.)  | cu ft/hr  | 
Exercise cycle  | 
  | 60  | 0.65  | 24  | 
25% of rated load  | 
  | 193  | 2.1  | 76  | 
50% of rated load  | 
  | 300  | 3.3  | 120  | 
75% of rated load  | 
  | 415  | 4.5  | 165  | 
100% of rated load  | 
  | 525  | 5.7  | 209  | 
  | 
  | 
  | 
  | 
  | 
ENGINE COOLING | 
  | ft3/min.  | 
  | 
  | 
Air flow (inlet air including alternator and combustion air)  | 1,800  | 
  | ||
System coolant capacity  | 
  | US gal.  | 2.0  | 
  | 
Heat rejection to coolant  | 
  | BTU/hr.  | 131,000  | 
  | 
Max. operating air temp. on radiator  | 
  | °C (°F)  | 60 (150)  | 
  | 
Max. ambient temperature  | 
  | °C (°F)  | 50 (140)  | 
  | 
  | 
  | 
  | 
  | 
  | 
COMBUSTION AIR REQUIREMENTS  | 
  | 
  | 
  | 
  | 
Flow at rated power 60 Hz  | 
  | cfm  | 95  | 
  | 
  | 
  | 
  | 
  | 
  | 
SOUND EMISSIONS IN DBA | 
  | 
  | 
  | 
  | 
db(A) @ 23 feet in exercise mode  | 
  | 
  | 62  | 
  | 
db(A) @ 23 feet at normal operating load  | 
  | 75  | 
  | |
  | 
  | 
  | 
  | 
  | 
EXHAUST | 
  | 
  | 
  | 
  | 
Exhaust flow at rated output 60 Hz  | 
  | cfm  | 260  | 
  | 
Exhaust temp. at muffler outlet  | 
  | °F  | 1025  | 
  | 
  | 
  | 
  | 
  | 
  | 
ENGINE PARAMETERS | 
  | 
  | 
  | 
  | 
Rated synchronous RPM  | 
  | 60 Hz  | 3600  | 
  | 
HP at rated KW  | 
  | 60 Hz  | 48  | 
  | 
  | 
  | 
  | 
  | |
POWER ADJUSTMENT FOR AMBIENT CONDITIONS  | 
  | 
  | 
  | |
Temperature Deration  | 3% for every 10 °C above - °C  | 25  | 
  | |
1.65% for every 10 °F above - °F | 77  | 
  | ||
Altitude Deration | 1% for every 100 m above - m  | 183  | 
  | |
  | 3% for every 1000 ft. above - ft.  | 600  | 
  | |
  | 
  | 
  | 
  | 
  | 
RATING: All three phases units are rated at 0.8 power factor. All single phase units are rated at 1.0 power factor. STANDBY RATING: Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance with