COMMERCIAL 30 kW
COMMERCIAL SERIES
OPERATING DATA
|
|
| COMMERCIAL 30 kW | |
KW RATING |
|
| 30 LP / 29 NG |
|
|
|
|
|
|
ENGINE SIZE |
|
| 1.6 Liter 4 cyl. inline |
|
|
|
|
| |
GENERATOR OUTPUT VOLTAGE/KW - 60Hz | KW | AMP | CB Size | |
120/208V, three phase, 0.8 pf |
| 30 LP / 29 NG | 104.2 LP / 100.7 NG | 125 |
120/240V, three phase, 0.8 pf |
| 30 LP / 29 NG | 90.3 LP / 87.3 NG | 100 |
277/480V, three phase, 0.8 pf |
| 30 LP / 29 NG | 45.1 LP / 43.6 NG | 50 |
|
|
|
|
|
GENERATOR LOCKED ROTOR KVA |
|
|
|
|
AVAILABLE @ VOLTAGE DIP OF 35% |
|
|
|
|
208 or 240V three phase |
|
| 56 |
|
480V three phase |
|
| 62 |
|
|
|
|
| |
ENGINE FUEL CONSUMPTION (Natural Gas) (Propane) | Natural Gas |
| Propane | |
|
| (ft3/hr.) | (gal/hr.) | cu ft/hr |
Exercise cycle |
| 60 | 0.65 | 24 |
25% of rated load |
| 193 | 2.1 | 76 |
50% of rated load |
| 300 | 3.3 | 120 |
75% of rated load |
| 415 | 4.5 | 165 |
100% of rated load |
| 525 | 5.7 | 209 |
|
|
|
|
|
ENGINE COOLING |
| ft3/min. |
|
|
Air flow (inlet air including alternator and combustion air) | 1,800 |
| ||
System coolant capacity |
| US gal. | 2.0 |
|
Heat rejection to coolant |
| BTU/hr. | 131,000 |
|
Max. operating air temp. on radiator |
| °C (°F) | 60 (150) |
|
Max. ambient temperature |
| °C (°F) | 50 (140) |
|
|
|
|
|
|
COMBUSTION AIR REQUIREMENTS |
|
|
|
|
Flow at rated power 60 Hz |
| cfm | 95 |
|
|
|
|
|
|
SOUND EMISSIONS IN DBA |
|
|
|
|
db(A) @ 23 feet in exercise mode |
|
| 62 |
|
db(A) @ 23 feet at normal operating load |
| 75 |
| |
|
|
|
|
|
EXHAUST |
|
|
|
|
Exhaust flow at rated output 60 Hz |
| cfm | 260 |
|
Exhaust temp. at muffler outlet |
| °F | 1025 |
|
|
|
|
|
|
ENGINE PARAMETERS |
|
|
|
|
Rated synchronous RPM |
| 60 Hz | 3600 |
|
HP at rated KW |
| 60 Hz | 48 |
|
|
|
|
| |
POWER ADJUSTMENT FOR AMBIENT CONDITIONS |
|
|
| |
Temperature Deration | 3% for every 10 °C above - °C | 25 |
| |
1.65% for every 10 °F above - °F | 77 |
| ||
Altitude Deration | 1% for every 100 m above - m | 183 |
| |
| 3% for every 1000 ft. above - ft. | 600 |
| |
|
|
|
|
|
RATING: All three phases units are rated at 0.8 power factor. All single phase units are rated at 1.0 power factor. STANDBY RATING: Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance with