Generac Power Systems 005219-0 owner manual Maintenance Owner Operator can Perform

Page 17

Standby Generator Sets

Maintenance

‹ENGINE COOLANT

Check coolant level in coolant recovery bottle. See the “Specifications” section.

Add recommended coolant mixture as necessary.

Periodically remove radiator pressure cap to make sure the coolant recovery system is functioning properly. Coolant should be at bottom of radiator filler neck. If coolant level is low, inspect gasket in radiator pressure cap. Replace cap, if necessary. To have pressure cap tested, contact an Authorized Service Dealer. Inspect cooling system and coolant recovery system for leaks.

MAINTENANCE OWNER/

OPERATOR CAN PERFORM

‹CHECK ENGINE OIL LEVEL

Refer to the “Checking Fluid Levels” section.

‹CHECK BATTERY

Check battery fluid level each week as outlined under “Check Fluid Levels”.

Check battery cables for condition, tightness, cor- rosion or damage. Clean, tighten or replace as necessary.

‹EXERCISE SYSTEM

Start the generator engine at least once every seven days and let it run at least 20 minutes. See the “Weekly Exercise Cycle” section.

‹INSPECT COOLING SYSTEM

Inspect engine cooling system at least once each month.

Check hoses for damage, deterioration, leaks, etc. Correct any discrepancies found.

Check hose clamps for tightness.

‹CHECK ENGINE COOLANT LEVEL

See the “Checking Fluid Levels” section.

‹PERFORM VISUAL INSPECTION

Complete a thorough visual inspection of the entire engine-generator monthly. Look for obvious damage, loose, missing or corroded nuts, bolts and other fas- teners. Look for fuel, oil or coolant leaks.

‹CHECK FAN BELT

Inspect fan belts every three months. Replace any damaged, deteriorated, worn or otherwise defec- tive belt.

Check fan belt tension. Thumb pressure, exerted midway between pulleys, should deflect about 3/8 to 5/8 inch. Adjust belt tension as required.

‹INSPECT ENGINE GOVERNOR

Visually inspect electronic governor.

DANGER

Do not attempt to adjust the governor. Only qualified service facilities should adjust the governor. Excessively high operating speeds are dangerous and increase the risk of personal injury. Low speeds impose a heavy load on the engine when adequate engine power is not available and may shorten engine life. Correct rated frequency and voltage are supplied only at the proper governed speed. Some connected electrical load devices may be damaged by incor- rect frequency and/or voltage. Only qualified service technicians should adjust the governed speed.

‹CHANGING ENGINE OIL

Refer to maintenance performed by authorized service facilities for engine oil and filter change frequencies.

Drain the oil while the engine is still warm from run- ning. This means warm up the engine, shut it down and drain immediately as follows:

1.Remove OIL DRAIN HOSE from its retaining clip.

2.Loosen and remove OIL DRAIN HOSE CAP. Drain oil completely into suitable container.

3.When all oil has drained, install and tighten OIL DRAIN HOSE CAP, and re-install into its retaining clip.

4.Turn OIL FILTER (Figure 10.2) counterclockwise and remove. Dispose of old filter.

5.Apply light coating of new engine oil to seal of new oil filter.-Install FILTER and tighten by hand only.

DO NOT OVERTIGHTEN.

6.Remove OIL FILL CAP. Add recommended oil (see

SPECIFICATIONS). DO NOT FILL ABOVE THE DIPSTICK “FULL” MARK. Crankcase oil capacity is 4.0 U.S. quarts (3.8 liters).

‹INSPECT EXHAUST SYSTEM

Inspect the exhaust system at least once every three months. Check all exhaust system pipes, mufflers, clamps, etc. for condition, tightness, leaks, security, damage.

After refilling the crankcase with oil, always check oil level on dipstick. NEVER OPERATE ENGINE WITH OIL BELOW THE DIPSTICK “ADD” MARK.

08/05

0 .Rev Maint001

10-2

Image 17
Contents Model Standby Generator Sets Table of Contents  Warning   Electrical Hazards  ‹ HOW to Obtain Service ‹ Operation and MaintenanceAuthorized Service Dealer Location Introduction‹ Data Label Identification RecordCoolant Recommendations Equipment DescriptionEngine OIL Recommendations Engine Protective Devices ‹ Fuel Requirements Fuel System‹ Natural GAS Fuel System ‹ LP Fuel SystemSpecifications ‹ Cold Weather KIT ‹ Reconfiguring the Fuel System‹ FOUR-LEAD, SINGLE-PHASE Stator Alternator Power Winding Connections‹ 3-PHASE Alternators Generator AC Lead ConnectionsInitial Inspection for QT Genset Startup InstallationPreparation Before START-UP ‹ START-UP Inspection START-UP Checklist‹ Preparation for START-UP Generator Control Operation Operating Unit with Manual Transfer Switch‹ Engine START-UP and Transfer ‹ Retransfer and ShutdownChecking Fluid Levels Cooling SystemMaintenance Owner Operator can Perform Miscellaneous Maintenance ‹ Battery Replacement Repair Parts‹ Battery Maintenance KW 150 KW Standby GAS Engine Driven Generator Sets Service ScheduleMaintenance Level 11-3 11-4 Problem Cause Correction Troubleshooting GuideStandby Generator Sets Page PAN CB Conn BOX Page Assy RTR 390 30KD1 CPL Page Components Included in 01827E Page MTG Base 3.0L 30KW C2 Page Tray Battery Page Plate AIR Cleaner Adapter Page Engine 3.0L Ford FD Make CPL Page Weldment RAD Support 3.0L C2 Page Page Page Flange Fuel Inlet Page Pipe Exhaust Muffler Page Rear Wrap C2 Page Page Page Page Page Page Page Page Page Page Standby Generator Sets Warranty

005219-0 specifications

Generac Power Systems 005219-0 is a robust and versatile backup power generator designed for residential and commercial applications. Known for its reliability and advanced features, this generator ensures that you have a dependable power source when you need it the most, particularly during unexpected outages.

One of the standout features of the Generac 005219-0 is its powerful engine. It is equipped with a 22 kW capacity, which is sufficient to power essential appliances and systems in your home or business. This power allows for the simultaneous operation of multiple devices, such as refrigerators, air conditioning units, and electronics, without the worry of overloading the system.

Generac’s patented Quiet-Test Technology is another significant characteristic of the 005219-0, which enables the generator to run at a lower RPM during weekly self-tests. This feature not only ensures that the generator is in optimal condition but also minimizes noise, making it less intrusive for homeowners while providing peace of mind that the generator is ready when needed.

The generator utilizes an automatic transfer switch, which instantly switches your home's power source from the grid to the generator in the event of a power failure. This seamless transition prevents any disruption in your daily activities and protects sensitive electronics from power surges.

Additionally, Generac is known for its tough design and weather-resistant features. The generator is constructed with durable materials to withstand various weather conditions, making it suitable for outdoor placement. Furthermore, the unit typically comes with a corrosion-resistant aluminum enclosure, ensuring longevity and reduced maintenance.

The 005219-0 also includes user-friendly control options, which are facilitated by a digital controller that provides easy monitoring and management of the generator’s functions. This capability allows users to track power consumption, manage maintenance schedules, and diagnose any potential issues quickly.

Lastly, Generac stands behind its products with comprehensive warranties, providing customers with assurance and confidence in their investment. With excellent customer service and support, owning a Generac generator like the 005219-0 means you are investing in a reliable power solution that meets your energy needs effectively.