Generac Power Systems 005324-1, 005325-1 ‹ Battery Fluid, ‹ Exercise System, ‹ Check FAN Belt

Page 17

Standby Generator Sets

Maintenance

Figure 10.1 - Oil Dipstick and Oil Fill Cap

OIL FILL CAP

OIL

DIPSTICK

‹BATTERY FLUID

Check battery electrolyte fluid based on the Maintenance Schedule. Fluid should cover separa- tors in all battery cells. If fluid level is low, add dis- tilled water to cover tops of separators. DO NOT USE TAP WATER IN BATTERY.

‹ENGINE COOLANT

Check coolant level in coolant recovery bottle. See Specifications.

Add recommended coolant mixture as necessary.

Periodically remove radiator pressure cap (only when engine has cooled down) to make sure the coolant recovery system is functioning properly. Coolant should be at bottom of radiator filler neck. If coolant level is low, inspect gasket in radiator pressure cap. Replace cap, if necessary. To have pressure cap tested, contact a Service Dealer. Inspect cooling system and coolant recovery sys- tem for leaks.

‹EXERCISE SYSTEM

Start the generator engine at least once every seven days and let it run at least 20 minutes. For more detailed exercise information, see the respective sec- tions in the Control Panel Technical Manual that is supplied with the unit.

‹INSPECT COOLING SYSTEM

Inspect engine cooling system. See “Maintenance Schedule”.

Check hoses for damage, deterioration, leaks, etc. Correct any discrepancies found.

Check hose clamps for tightness.

‹CHECK ENGINE COOLANT LEVEL

See “Checking Fluid Levels”.

‹PERFORM VISUAL INSPECTION

Complete a thorough visual inspection of the entire engine-generator monthly. Look for obvious damage, loose, missing or corroded nuts, bolts and other fas- teners. Look for fuel, oil or coolant leaks.

‹INSPECT EXHAUST SYSTEM

Inspect the exhaust system at least once every three months. Check all exhaust system pipes, mufflers, clamps, etc. for condition, tightness, leaks, security, damage.

‹CHECK FAN BELT

Inspect fan belts every three months. Replace any damaged, deteriorated, worn or otherwise defec- tive belt.

Check fan belt tension. Thumb pressure, exerted midway between pulleys, should deflect about 3/8 to 5/8 of an inch. Adjust belt tension as required.

‹INSPECT ENGINE GOVERNOR

Visually inspect electronic governor.

MAINTENANCE OWNER/OPERATOR CAN PERFORM

‹CHECK ENGINE OIL LEVEL

Refer to “Checking Fluid Levels”.

‹CHECK BATTERY

See “Checking Fluid Levels”.

Check battery cables for condition, tightness, cor- rosion or damage. Clean, tighten or replace as necessary.

DANGER

Do not attempt to adjust the governor. Only qualified service facilities should adjust the governor. Excessively high operating speeds are dangerous and increase the risk of personal injury. Low speeds impose a heavy load on the engine when adequate engine power is not available and may shorten engine life. Correct rated frequency and voltage are supplied only at the proper governed speed. Some connected electrical load devices may be damaged by incor- rect frequency and/or voltage. Only qualified service technicians should adjust the governed speed.

06/07 D .Rev Maint011

10-2

Image 17
Contents 25kW Models 005324-1 Standby Generator Sets Table of Contents  Warning   Electrical Hazards  ‹ HOW to Obtain Service ‹ Operation and MaintenanceAuthorized Service Dealer Location Introduction‹ Data Label Identification RecordCoolant Recommendations Equipment DescriptionEngine OIL Recommendations Engine Protective Devices ‹ Fuel Requirements Fuel System‹ Natural GAS Fuel System ‹ LP Fuel SystemSpecifications ‹ Cold Weather KIT ‹ Reconfiguring the Fuel System‹ FOUR-LEAD, SINGLE-PHASE Stator Alternator Power Winding Connections‹ 3-PHASE Alternators Generator AC Lead ConnectionsInitial Inspection for QT Genset Startup InstallationPreparation Before START-UP ‹ START-UP Inspection START-UP Checklist‹ Preparation for START-UP Generator Control Operation Operating Unit with Manual Transfer Switch‹ Engine START-UP and Transfer ‹ Retransfer and ShutdownChecking Fluid Levels Maintenance Performed by Service FacilitiesCooling System ‹ Check Battery ‹ Battery Fluid‹ Exercise System ‹ Inspect Cooling System‹ Spark Plugs ‹ Changing the Engine AIR Cleaner ‹ Coolant Change‹ Changing Engine OIL Miscellaneous Maintenance Service Maintenance Interval Information Service ScheduleLevel Maintenance Level Problem Cause Correction Troubleshooting GuideStandby Generator Sets Standby Generator Sets Standby Generator Sets Standby Generator Sets Page Breaker Tray BACK/BOTTOM Page Assy RTR 20KW 2PH for Units Built Before February Page Components Included in 0G3365E Page Support Radiator LH Side Page Battery Tray C1 CPL Page Mounting Base 1.6L Page ASM Motor Stepper Page Engine Generac 1.6L NG Page Elbow 90D 3/4 NPT Page Roof C1 CPL Page Muffler C1 Page Page Page Page Page Page Page Page Page Page Page Page Page Page Standby Generator Sets Warranty

005324-1, 005325-1 specifications

Generac Power Systems has long been a leader in backup power solutions, and their Generac Power Systems 005324-1 and 005325-1 models epitomize the brand's commitment to reliability and innovation. These advanced systems are engineered to provide seamless power during outages, ensuring that homes and businesses remain operational even during prolonged power disruptions.

The Generac 005324-1 model is designed for maximum efficiency and performance, boasting a robust 22 kW output, which can power essential appliances, HVAC systems, and more. Its tri-fuel capability allows it to run on natural gas, propane, or gasoline, offering flexibility and convenience depending on the availability and user preferences. This versatility is a significant advantage, as it ensures that users can maintain their power supply regardless of fuel availability during emergencies.

On the other hand, the Generac 005325-1 model is slightly more powerful, delivering 24 kW of output. This model is particularly suited for larger homes or facilities that require additional capacity to support multiple high-demand appliances. Similar to the 005324-1, the 005325-1 features the same tri-fuel capability, allowing users to choose their preferred fuel source.

Both models are outfitted with Generac’s innovative G-Force engine, designed for high performance and long-lasting durability. This engine is engineered specifically for generator use, ensuring that it provides reliable power without the wear and tear associated with typical automotive engines. The G-Force engine is backed by a comprehensive 5-year limited warranty, demonstrating Generac’s commitment to product quality and customer assurance.

In addition to their robust performance, both generator models come equipped with Smart Management Modules, which optimize power usage by allowing homeowners to manage their energy consumption more effectively. This feature prevents overloading the generator, ensuring an uninterrupted power supply even when multiple devices are in use.

Furthermore, the intuitive mobile app allows users to monitor their generator’s performance, receive real-time alerts, and schedule maintenance, enhancing user convenience. Generac has also integrated a quiet operation feature, making these models some of the quieter alternatives in the market, which is particularly important for residential areas.

In summary, the Generac Power Systems 005324-1 and 005325-1 models are powerful, versatile, and reliable generators, perfect for anyone in need of consistent backup power during outages. Their unique features, advanced technologies, and user-friendly characteristics make them a smart investment for long-term peace of mind.