Generac Power Systems 04758-0, 04759-0 Before Initial START-UP, Check Transfer Switch Operation

Page 12

Section 2 — Post Installation Start-up and Adjustments

Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators

The following procedures are to be observed:

Wear full eye protection and protective clothing;

Where electrolyte contacts the skin, wash it off immediately with water;

Where electrolyte contacts the eyes, immediately flush thoroughly with water and seek medical attention; and

Spilled electrolyte is to be washed down with an acid neutralizing agent. A common practice is to use a solution of 1 pound (500 grams) bicarbonate of soda to 1 gallon (4 liters) or water. The bicar- bonate of soda solution is to be added until the evidence of reaction (foaming) has ceased. The resulting liquid is to be flushed with water and the area dried.

Lead-acid batteries present a risk of fire because they generate hydrogen gas. The following procedures are to be followed:

DO NOT SMOKE when near the battery;

DO NOT cause flame or spark in battery area; and

Discharge static electricity from your body before touching the battery by first touching a grounded metal surface.

Be sure the Auto/Off/Manual switch is set to ! the OFF position before connecting the battery

cables. If the switch is set to AUTO or MANUAL, the generator can crank and start as soon as the battery cables are connected.

Be sure the utility power supply is turned off, or sparking may occur at the battery posts as you attach the cables and cause an explosion.

2.1BEFORE INITIAL START-UP

Before starting, complete the following:

1.Set the generator’s main circuit breaker to its OFF (or open) position.

2.Set the generator's Auto/Off/Manual switch to the OFF position.

3.Turn OFF the utility power supply to the transfer switch using the means provided (such as the utility main line circuit breaker).

4.Check the engine crankcase oil level and, if nec- essary, fill to the dipstick FULL mark with the recommended oil. Do not fill above the FULL mark.

5.Check the fuel supply. Gaseous fuel lines must have been properly purged and leak tested in accordance with applicable fuel-gas codes. All fuel shutoff valves in the fuel supply lines must be open.

Never operate the engine with the oil level

!below the “Add” mark on the dipstick. Doing this could damage the engine.

2.2CHECK TRANSFER SWITCH

OPERATION

Refer to Section 3.5 (Page 15), of the owner’s manual for manual operation procedures.

DANGER

Do not attempt manual transfer switch opera- tion until all power voltage supplies to the transfer switch have been positively turned off. Failure to turn off all power voltage supplies will result in extremely hazardous and possibly fatal electrical shock.

2.3ELECTRICAL CHECKS

Complete electrical checks as follows:

1.Turn on the utility power supply to the transfer switch using the means provided (such as a utili- ty main line circuit breaker).

DANGER

The transfer switch is now electrically “hot.” Contact with “hot” parts will result in extreme- ly hazardous and possibly fatal electrical shock. Proceed with caution.

2.Use an accurate AC voltmeter to check utility power source voltage across terminals N1 and N2. Nominal line-to-line voltage should be 240 volts AC.

3.Check utility power source voltage across termi- nals N1 and the transfer switch neutral lug; then across terminal N2 and neutral. Nominal line-to- neutral voltage should be 120 volts AC.

4.When certain that utility supply voltage is com- patible with transfer switch and load circuit rat- ings, turn OFF the utility power supply to the transfer switch.

5.Set the generator's main circuit breaker to its OFF (or open) position. Initial tests will be con- ducted at no-load condition.

6.On the generator panel, set the Auto/Off/Manual switch to MANUAL. The engine should crank and start.

7.Let the engine warm up for about five minutes to allow internal temperatures to stabilize. Then, set the generator’s main circuit breaker to its ON (or closed) position.

DANGER

Proceed with caution! Generator power voltage is now supplied to the transfer switch. Contact with live transfer switch parts will result in dangerous and possibly fatal electrical shock.

10

Image 12
Contents Installation Introduction Post Installation Start-up Adjustments MaintenanceTroubleshooting Introduction Inside Front CoverGeneral Hazards Electrical Hazards ‹ Standards IndexUNPACKING/INSPECTION Protection SystemsSystem SET LED Your Generator 7 kW, Single Cylinder GH-410 EngineSpecifications ‹ 1.5.1 Generator‹ 1.5.2 Engine Reconfiguring the Fuel System Fuel Requirements RecommendationsFuel Consumption 2 12KW and 15KW, 990CC EnginesTransfer Switch LocationGenerator 2.1 7 kW, 12 kW and 15 kW UnitsBattery Installation BatteryCheck Transfer Switch Operation Before Initial START-UPElectrical Checks Generator Tests Under Load Checking Automatic OperationAdjusting the Regulator Natural GAS only Engine Governor Adjustment1 7 KW Units Voltage Regulator Adjustment BREAK-IN Procedure2 12 KW and 15 KW Units Automatic Transfer Operation Sequence of Automatic Operation‹ 3.2.1 Auto Position ‹ 3.2.2 OFF Position‹ 3.5.2 Transfer Back to Utility Power Source Manual Transfer OperationSetting the Exercise Timer ‹ 3.7.1 LOW OIL Pressure Switch‹ 3.7.2 High Temperature Switch ‹ 3.7.3 OvercrankChecking the Engine OIL Level Changing the Engine OIL‹ 4.3.1 Engine OIL Recommendations ‹ 4.3.2 OIL Change Procedure Changing the OIL Filter‹ 4.5.1 7 KW, 12 KW and 15 KW Generators Battery Maintenance Spark PlugsAdjusting Valve Clearance Cooling SystemOUT of Service Procedure ‹ 4.12.2 Return to Service‹ 4.12.1 Removal from Service Corrosion ProtectionService Schedule Be performed by your nearest Generac Authorized DealerTroubleshooting Guide Problem Cause CorrectionElectrical Data Customer Connection SM Starter Motor 1VA Engine Wiring Control Panel BOX SP Spark Plug Customer Connections Exploded Views and Parts Lists Part NO. QTY Description Exploded Views and Parts Lists Part NO. QTY. Description Kit Contains QTY Description 122 138 125 139 136 135 123 120 137 124 133 119 117 114 121 QTY Description 45 30 ADAPTOR, Engine Exploded Views and Parts Lists Stator 12KW 40 22 ASSEMBLY, Connecting ROD Exploded Views and Parts Lists SCREW, Taptite M6-1.0X8 Yellow Chrome For GT 760 Engine only CASTING, Twin Regulator Housing Mounting Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators California and Federal Emission Control Warranty Statement Emission Control System Warranty Warranty Schedule This Warranty Shall not Apply to the Following

04760-0, 04759-0, 04758-0 specifications

Generac Power Systems is a leading manufacturer in the field of power generation, known for its innovative products that cater to both residential and commercial customers. Among its prominent offerings, the Generac models 04758-0, 04759-0, and 04760-0 stand out as essential solutions for backup energy needs. These units offer reliable power during outages, ensuring that homes and businesses remain operational regardless of external conditions.

The Generac 04758-0 is a robust standby generator designed for residential use. Featuring a powerful engine, it delivers a dependable power output when it is needed most. Key characteristics include an automatic transfer switch that detects power loss and activates the generator without user intervention. This means that homeowners can enjoy peace of mind knowing that their essential appliances and systems will continue to function seamlessly during outages. Additionally, its compact design allows for easy installation in most home settings.

Moving on to the Generac 04759-0, this model offers even greater power capacity, making it suitable for larger homes or small businesses. It incorporates advanced technologies such as digital power management, which optimizes fuel efficiency and reduces emissions. The O47-59-0 is also known for its durable construction, providing reliable performance in various weather conditions. Its user-friendly interface allows for straightforward operation and monitoring, ensuring users remain informed about their power status.

The Generac 04760-0 takes it a step further by enhancing its overall performance with innovations in noise reduction and fuel consumption. It is engineered with a leading-edge cooling system that minimizes operational noise, making it ideal for residential neighborhoods where sound regulations are a concern. This model is also compatible with a variety of fuels, giving users flexibility based on availability and cost. Its comprehensive warranty further underscores Generac's commitment to customer satisfaction and product reliability.

In summary, the Generac Power Systems models 04758-0, 04759-0, and 04760-0 exemplify technology and engineering excellence in the power generation industry. With features designed for efficiency, durability, and user convenience, these models provide steadfast support to users seeking dependable backup power solutions. Whether for a home or small business, Generac's offerings remain a trusted choice for managing unexpected power outages.