3002503 | 11.06 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| The figure below shows typical installation arrangements: |
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||||||
|
| Fig. 3 | Vertical |
|
|
| |||||||||||||||||||||||||
|
|
|
| ||||||||||||||||||||||||||||
|
|
|
|
|
| Sidewall |
|
|
| ||||||||||||||||||||||
|
|
|
|
|
| Venting | Venting |
|
|
| |||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
3.3 Mounting of Power Venter
The power venter can be installed in a variety of positions. It can be suspended from a ceiling or placed on a shelf/floor. Placement on a shelf requires special hardware and vibration dampers.
Suspension from a ceiling does not require any special hardware other than threaded rods, nuts, and hangers.
Fig. 4
Threaded rod
Follow Fig. 4 and 5. when suspending the power venter from a ceiling. Fig. 4 shows which mounting legs to use when installing the power venter in its normal position with inlet in the back and outlet on the top (installation between horizontal and vertical chimney). Fig. 5 shows which mounting legs to use when installing the power venter with inlet on the bottom and outlet on the side (installation for sidewall venting).
1.Once the position has been determined, hang four threaded
rods from hangers above, and slide the rods through the mounting holes in the mounting legs.
2.Level the power venter.
3.Secure the legs with washers and nuts.
Warning! Never install the power venter so the motor points down. This will shorten the life. The min. clearance to combustibles is 24 inches.
Mounting legs
Fig. 5
Mounting legs
UP
Nuts
Threaded rods
UP
Nuts