Evacuating the indoor unit

The indoor unit is supplied with inert gas (nitrogen).

Before installing the unit, check if nitrogen gas flows out of indoor unit.

If this one isn’t true, DO NOT INSTALL THE UNIT since leakage could be inside the indoor unit.

1.Unscrew the caps at the end of each pipe.

All inert gas exhausts from the indoor unit.

• To prevent dirt or foreign substances from getting into the pipes during

 

 

installation, do NOT remove the caps completely until you are ready to

 

 

connect the pipes.

 

 

• The remaining air in the Refrigeration cycle, which contains moisture,

 

 

may cause malfunction on the compressor.

 

 

• Always contact the service center or a professional installation agency

Pipes

Unscrew the

for product installation.

 

caps

 

 

Cutting or extending the pipe

The length of the pipe can be:

Extended up to : see table page 33

Shorten up to: see page 33

If you need a pipe longer than 4 meters (24) or 5 meters (12/18):

• You must add refrigerant to the pipes; otherwise, the indoor unit may freeze.

1.Make sure that you have all the required tools (pipe cutter, reamer, flaring tool and pipe holder).

2.If you want to shorten the pipe, cut it using a pipe cutter, ensuring that the cut edge remains at 90° with the side of the pipe (see below examples of correct and incorrect cut edges).

Pipe

Oblique

Rough

Burr

cutter

 

 

 

Pipe

3. To prevent a gas leak, remove all burrs at the cut edge of the pipe using a reamer.

• Face the pipe down while removing the burrs to make sure that burrs do not get in to the pipe.

4. Put a flare nut slightly into the pipe and modify the flare.

 

90°±2°

 

Outer Diameter (D)

Depth (A)

Flaring Size (B)

 

 

ø6.35 mm

1.3 mm

8.7

- 9.1 mm

 

 

4

 

 

 

 

 

 

 

 

 

 

5°±

 

 

 

 

 

B

 

ø9.52 mm

1.8 mm

12.8

- 13.2 mm

 

 

 

 

 

 

 

ø12.70 mm

2.0 mm

16.2

- 16.6 mm

 

 

R0.4~0.8

ø15.88 mm

2.2 mm

19.3

- 19.7 mm

 

 

 

 

 

 

Pipe

Flare

 

 

 

 

 

 

atio nall Inst07

English-43

MG_GOOD_R-410A_A3050_IB&IM_EN_DB68-04540A.indd 43

 

 