Samsung AR18JQFSBWKXMG Cutting or extending the pipe, Installing and connecting the drain hose of the indoor unit

AR12JQFNBWK/MG, AR12JQFNBWKNMG, AR12JQFNBWKXMG, AR12JRFNBWKNMG, AR12JRFNBWKXMG, AR18JQFNBWKNMG, AR18JQFNBWKXMG, AR18JQFSBWKNMG, AR18JQFSBWKXMG, AR18JQSDBWKNMG, AR18JQSDBWKXMG, AR18JRFNBWKNMG, AR18JRFNBWKXMG, AR18JRFSBWKNMG, AR18JRFSBWKXMG, AR24JQFNBWKNMG, AR24JQFSBWKNMG

1 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58
Download on canonical page 58 pages, 0 b

Cutting or extending the pipe

5. Check if you flared the pipe correctly (see examples of incorrectly flared pipes below).

Correct

Inclined

Damaged

Cracked

Uneven

 

 

Surface

 

Thickness

6.Align the pipes to connect them easily.Tighten the flare nuts first with your hands, and then with a torque wrench, applying the following torque:

 

Flare nut

Outer Diameter

 

Torque

 

 

N•m

kgf•cm

 

 

 

 

 

ø6.35 mm

14~18

140~180

 

 

ø9.52 mm

34~42

350~430

 

 

ø12.70 mm

49~61

500~620

Indoor outlet pipe

Connecting pipe

ø15.88 mm

68~82

690~830

• Excessive torque can be cause of gas leakage. If extending pipe by welding/brazing please ensure nitrogen is used

during welding/brazing process. The joint must be accessible and serviceable.

• The holder system is detachable as shown..

Holder system (detachable)

7. For further details on how to connect to the outdoor unit and evacuate the air, refer to page 47~49.

• Tighten the flare nut with torque wrench according to specified method.

If the flare nut is over-tightened, the flare may break and cause refrigerant gas leakage.

Installing and connecting the drain hose of the indoor unit

When installing the drain hose for the indoor unit, check if condensation draining is adequate. When passing the drain hose through the 65 mm hole drilled in the wall, check the followings:

Wall

Indoor unit

Drain hose

The drain hose must NOT slant upwards.

The end of the drain hose must NOT be placed under water.

The drain hose must not be bent.

English-44

MG_GOOD_R-410A_A3050_IB&IM_EN_DB68-04540A.indd 44

 

 

9/1/2014 5:12:00 PM

 

 

 

 

 

 