AM-753

Universal

Mounting

Clamps

1

AM-676 Universal Shaft Extension

V-clamp

Duct

Actuator

Anti-rotation Bracket (included with actuator)

Mounting Surface

1The AM-676 extends the damper shaft approximately 9" (229 mm).

Damper Shaft

 

Figure-13 Installation of Universal Shaft Extension.

Wiring Requirements

Control and Power Leads

 

Remove blue plastic thread protectors before installing conduit fittings. See Figure-1through

 

Figure 8 for typical wiring applications and Table-3for maximum wire lengths.

 

 

 

Caution: The 24 Vac model contains a half-wave rectifier power supply and must not be

 

powered by transformers used to power other devices utilizing non-isolated full-wave

 

rectifier power supplies. Refer to EN-206 Guidelines for Powering Multiple Full-Wave and

 

Half-Wave Rectifier Devices from a Common Transformer, F-26363, for further information.

 

 

 

Note: Class 2 control and power lead wiring must be routed separately from line voltage

 

wiring and any other non-class 2 circuits.

 

 

Table-3 Control and Power Wiring Data.

Actuator

Part

Maximum Wire Run in ft. (m)

 

(5% Voltage Drop)

 

Voltage

Number

 

 

14 AWG

 

16 AWG

 

18 AWG

 

 

 

 

24 Vac and

MS40-7173

 

 

 

 

 

22-30 Vdc

981

 

617

 

388

 

 

 

120 Vac

MS40-7170

(299)

 

(188)

 

(118)

240 Vac

MS40-7171

 

 

 

 

 

Table-4 Wire Color Codes for Models Manufactured before December, 2007.

Part Number

Power

L1

L2

Ground

24 H

24 G

Analog

500 Ohms

Common

Voltage

Input

 

 

 

 

 

 

 

 

MS40-7173-0-0-0

24 Vac

N/A

N/A

Green/Yellow

Black

Black/Blue

White

Red

Black

Old Design

 

 

 

 

 

 

 

 

 

MS40-7170-0-0-0

120 Vac

Black

White

Green/Yellow

N/A

N/A

White

Red

Black

Old Design

 

 

 

 

 

 

 

 

 

MS40-7171-0-0-0

240 Vac

Brown

Light

Green/Yellow

N/A

N/A

White

Red

Black

Old Design

 

 

Blue

 

 

 

 

 

 

N/A: Not Applicable

14

Copyright 2010 Schneider Electric All Rights Reserved.

F-26748-6

Page 14
Image 14
3Com MS40-717X warranty Wiring Requirements, Control and Power Leads, Control and Power Wiring Data