Motor Lead Pigtail Splice

for 5/8 kV Non-Shielded Cables
for 1000 Volts or less cables (heavy-duty and two-hole lug applications)

Instructions

78-8096-4634-8-F

Kit Contents (kit contains 3 splices):
3—Lug Covers
3—Locking Pins
3—Tubes Silicone Grease
3—Bag Solvent Cleaning Cloths
3—Mastic Sealing Strip(s)*
3— Strips Scotch® Linerless Rubber Splicing Tape 130C
3—Instruction Sheet
*Quantity varies with kit number.
Kit Cable
Size
Range
Cable
Max.
Number (AWG/kcmil) Insulation
Bolt
Feeder Motor
Lead O.D.
Range Length
5316 8–4 10–4 0.30–0.51
in. 12
in.
5317 2–1/0 4–1/0 0.43–0.65
in. 34
in.
5318 1/0–250 2–250 0.53–0.88
in. 114
in.
5319 250–500 4/0–500 0.75–1.12
in. 112
in.
3M

Motor Lead

Pigtail Splice Kits

for 5/8 kV or less Non-Shielded Cables
5316, 5317, 5318, 5319
Technical Information:
• For non-shielded cables
• Rated 5/8 kV
For cables rated 1000 Volts or less (heavy-duty and two
hole lug applications)
• Cable Size Range: Feeder: #8 AWG—500 kcmil
Motor Lead: #10 AWG—500 kcmil
• Copper Conductors
CSA Certified for
600V or Less
Table 1
Caution
Working around energized systems may cause serious
injury or death. Installation should be performed by
personnel familiar with good safety practice in handling
electrical equipment. De-energize and ground all
electrical systems before installing product.