16 78-8113-5098-8 Rev F
16.0 Install Termination
16.1 Slide the termination body onto the cable and remove core. Pull while unwinding, counter-clockwise, starting
with the loose end (Figure 23). Make sure the termination body (not the core) is butted up to the edge of the
vinyl tape marker previously applied (Figure 23).
NOTE: Once the termination body makes contact over the mastic seal area, there is no need to continue
supporting the assembly. DO NOT PUSH OR PULL ON THE TERMINATION ASSEMBLY WHILE
UNWINDING THE CORE.
The material being removed at this step is mixed polymersNOTE:
waste.and can be recycled with
Vinyl Tape Marker
Counter-Clockwise
Figure 23
16.2 Connect ground braid to system ground according to standard practice.
Ridge at End of Stress
Controlling Compound
Semi-Con
Ridge at End of Cable
Insulation Shield (Semi-Con)

Correct Installation of Termination on UniShield® Cable

Vinyl Tape
Marker
Environmental Top
Seal
Stress Controlling Compound
Conductor
Cable Insulation