Installation Requirements - Commonwealth of Massachusetts

Commonwealth of Massachusetts

For all side wall terminated, horizontally vented power vent, direct vent, and power direct vent gas fueled water heaters installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:

INSTALLATION OF CARBON MONOXIDE DETECTORS

At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the sidewall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors.

In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.

In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements provided that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.

APPROVED CARBON MONOXIDE DETECTORS

Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and CSA certified.

SIGNAGE

A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, “gas vent directly below. Keep clear of all obstructions.”Inspection The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector

observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a) 1 through 4.

EXEMPTIONS

The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:

1.The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and

2.Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building, or structure used in whole or in part for residential purposes.

MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED

When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:

1.Detailed instructions for the installation of the venting system design or the venting system components; and

2.A complete parts list for the venting system design or venting system.

MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED

When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies “special venting systems,” the following requirements shall be satisfied by the manufacturer:

1.The referenced “special venting system” instructions shall be included with the appliance or equipment installation instructions; and

2.The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.

A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.

22

Page 22
Image 22
A.O. Smith 317443-000 Installation Requirements Commonwealth of Massachusetts, Installation of Carbon Monoxide Detectors

100 Power Vent DV Series 120, 317443-000 specifications

The A.O. Smith 317443-000,100 Power Vent DV Series 120 is an advanced water heating solution designed to enhance efficiency and performance for residential applications. As part of A.O. Smith's renowned lineup, this model embodies the company's commitment to innovation and energy conservation.

One of the main features of the DV Series 120 is its power venting capability. This technology allows for flexible installation options, as it can vent vertically or horizontally, accommodating various home configurations. It utilizes a fan-assisted venting system, which efficiently expels exhaust gases, ensuring safe operation even in tight spaces.

The unit's energy efficiency is another standout characteristic. Equipped with a high-efficiency gas burner, the DV Series 120 optimizes fuel consumption, resulting in lower utility bills while providing reliable hot water when needed. Its impressive Energy Factor (EF) ratings make it an environmentally friendly choice, aligning with modern standards for green building practices.

Durability is also a significant focus of the A.O. Smith 317443-000,100 Power Vent model. Constructed with a glass-lined tank and a robust anode rod, this water heater is designed to resist corrosion and extend its lifespan. This construction enhances performance reliability while minimizing maintenance needs, making it a smart investment for homeowners.

Smart technologies are integrated into the DV Series 120, featuring an intelligent control system that provides various operational insights. The built-in diagnostic features allow homeowners to monitor performance and identify potential issues early, reducing the likelihood of unexpected failures. This control system can also enable more precise temperature management, enhancing both comfort and efficiency.

Safety is paramount in the design of the A.O. Smith 317443-000,100. The unit comes equipped with safety features such as a built-in flame rollout sensor and an automatic shut-off system to protect against potential hazards. These features ensure peace of mind for users, allowing them to confidently rely on their hot water supply.

In summary, the A.O. Smith 317443-000,100 Power Vent DV Series 120 stands out as a high-efficiency water heating solution, combining innovative venting technologies, durability, smart features, and safety mechanisms. This model is an ideal choice for homeowners seeking a reliable and efficient hot water system that meets modern energy standards.