Calculating Amperage/Overcurrent Protection
The boiler is factory wired for connection to three wire
A diagram of the wiring is furnished with the boiler for the electrician’s use. An amperage table is on page 4 of this manual. The boiler model and rating plate provides full load amperage data.
The rating of the overcurrent protection should be computed on the basis of 125 percent of the total connected load amperage. Where the standard ratings and settings do not correspond with this computation, the next higher standard rating or setting should be selected.
Boiler Circuits
The boiler’s electrical components are pictured and identified on page
5.The model and rating plate illustration on page 4 identifies the electrical characteristics. Basically, there are two electrical circuits:
•The control circuit, where the temperature control directly or indirectly operates the contactor coils.
•The power circuit, which is operated by the control circuit, carries the electrical load of the heating elements.
The following describes the circuits and includes typical wiring diagrams. All circuits are designed for 60 or 50 Hertz alternating current.
Refer to ELECTRICAL CONFIGURATION TABLE, below, and wiring diagram provided with your boiler before completing connections to electrical supply.
NOTE: Wiring diagrams in this manual are typical examples. The specific wiring diagram for your boiler is the one supplied with the boiler.
Control Circuit
All control circuits are operated on
Control circuit wiring is 14 Awg, THHN or THWN type, rated 600 volts, 105°C.
Seperate instructional literature is provided with the boiler for the modulating solid state step control.
Portion of Table | Portion of Table | |||
Allowable Ampacities of Insulated | Allowable Ampacities of | |||
Copper Conductors | Insulated Aluminum and Copper- | |||
Not more than three conductors in | Clad AluminumConductors | |||
Not more than three conductors | ||||
raceway or cable or direct burial | ||||
(based on ambient temperature of | in raceway or cable or direct | |||
| 30°C, 86°F.) | burial (based on ambient | ||
|
| temperature of 30°C, 86°F.) | ||
|
|
| ||
| Temperature Rating of | Temperature Rating of | ||
| Conductor. See Table |
| Conductor. See Table | |
Size | Size | |||
AWG | 75°c | AWG | 75°C | |
MCM | (167°F) | MCM | (167°F) | |
| TYPES |
| TYPES | |
| RH, RHW, RUH |
| RH, RHW, RUH | |
|
| |||
| THW, THWN, |
| THW, THWN, | |
| XHHW, USE |
| XHHW, USE | |
18 | - - - - - | 12 | 15 | |
16 | - - - - - | 10 | 25 | |
14 | 15 | 8 | 40 | |
12 | 20 | 6 | 50 | |
10 | 30 | 4 | 65 | |
8 | 45 | 3 | 75 | |
6 | 65 | 2 | 90 | |
4 | 85 | 1 | 100 | |
3 | 100 | 1/0 | 120 | |
2 | 115 | 2/0 | 135 | |
1 | 130 | 3/0 | 155 | |
1/0 | 150 | 4/0 | 180 | |
2/0 | 175 | 250 | 205 | |
3/0 | 200 | 300 | 230 | |
4/0 | 230 | 350 | 250 | |
250 | 255 | 400 | 270 | |
300 | 285 | 500 | 310 | |
350 | 310 | 600 | 340 | |
400 | 335 | 700 | 375 | |
500 | 380 | 750 | 385 | |
600 | 420 | 800 | 395 | |
700 | 460 | 900 | 425 | |
750 | 475 | 1000 | 445 | |
800 | 490 | 1250 | 485 | |
900 | 520 | 1500 | 520 | |
1000 | 545 | 1750 | 545 | |
1250 | 590 | 2000 | 560 | |
1500 | 625 | These capacities relate only to conductors | ||
1750 | 650 | described in Table | ||
2000 | 665 | For ambient temperatures over 30°C, see | ||
|
| Correction Factors, Note 13 in Code |
Power Circuit
The boiler is equipped with one of the power circuit configurations shown in the table.
Power circuit wiring is type THHN, rated 600 volts, 105°C, sized as necessary.
7