A.O. Smith VB/VW- 750, VB/VW- 1000 Venting Supports, Vertical Installation Requirements

Models: VB/VW- 1000 VB/VW- 750

1 52
Download 52 pages 29.51 Kb
Page 17
Image 17

Venting Supports

Care must be taken in the installation of the venting system that adequate support is maintained throughout the installation process. When extending more than 10 feet (3.0m) vertically, vertical support kits are required once every 10 feet (3.0m) of vertical run. Vertical support is also required­ immedi­ately after any transition­ (elbow, tee, etc.) to vertical of over 10 feet (3.0m) of run and after any offset in the vertical run.

The support brackets (supplied in the Vertical Support Kit) are to be secure­ly fastened to a solid vertical member of the building using the appropriate fasteners; i.e., wood screws for wood framing, machine or tapping screws for structural steel or masonry anchors for solid masonry. The bracket should be located so that it will not interfere with any joints of the venting system. The bottom most support bracket should be located directly above the first transition from horizontal to vertical, see Figure 10. Refer to Figures 12, 12A, 12B and 12C.

If a means of support for the brackets are not available and horizontal vent sections are present, install hanger straps (made from non-combustible material) as close to the points of transition as possible. If the horizontal portions of the vent and/or vent connector are longer than 6 feet (2.0m), then install hanger straps every 6 feet (2.0m) to support the connector.

DO NOT rivet or screw the straps to the conduit or other­wise puncture the conduit wall. Instead, wrap an extra loop of strap around the conduit to hold it in position, or attach the strap to the center screw of the double wall AL 29-4C®vent coupling, if applica­ble.

Vertical Installation Requirements

1.The vent system must terminate at least 3 feet (1.0m) and no more than 6 feet (2.0m) above the roof line and no closer than 10 feet (3.0m) from any wall or vertical­ structure. If the exhaust vent terminal is within 10 feet

(3.0m) of a wall or parapet, it must extend a minimum of 2 feet (610mm) above the wall or parapet, see Figures

11 and 12A.

2.For direct vent installations, the total distance of the vent system from the boiler vent connector to the vertical vent termination shall not exceed 70 equivalent feet (21.3m). A maximum of three 90° elbows can be used. Minimum vertical vent is 7 equivalent feet

(2.1m) for direct vent installations. Standard minimum vertical vent length is 7 feet (2.1m), plus Boot-Tee. See Figures 11, 12A, 12B, and

12C for differences between standard and direct vent installations.

3.An AL 29-C®Vent Vertical Vent Terminal must be used at the termination.

4.Maintain a minimum of 6 feet (2.0m) separation between the air intake and the exhaust terminals.

Horizontal Installtion Requirements

1.The vent system must terminate with a AL 29-4C®Vent

Through-the-Wall Termination (TWT). Plan the terminal location based on the dimensions shown in Figure 9. Do not locate the terminal within 8 feet (2.5m) of an inside corner of a building or adjacent to outside walls, shrubs or other such objects that may cause adverse wind conditions in the immediate area.

2.The TWT shall be located not less than 12 inches (305mm) above grade or, in geographical areas where snow accumulates,­ no less than 12 inches (305mm) above the anticipated­ snow line. Ensure that the TWT is protected against blockage which may occur during ice buildup­ or snowstorms.

The TWT shall terminate at least 3 feet (1.0m) above any forced air inlet within 10 feet (3.0m), except when the forced air inlet is the combustion air intake of a direct vent appliance. The TWT shall terminate at least

4 feet (1.2m) below, 4 feet (1.2m) horizontally from or 1 foot (305mm) above any door, window or gravity air inlet into any building as provided in the current edition of the NATIONAL­ FUEL GAS CODE ANSI Z223.1, see Figure 9.

In addition, a minimum clearance of 4 feet (1.2m) hori­ zontally from, and in NO CASE ABOVE OR BELOW, unless the 4 feet (1.2m) of horizontal distance is main­ tained from electric meters, gas meters, regulators and relief equipment.

3.This horizontal exhaust vent system must pitch upward toward the termination at 1/4 inch per foot (21mm per meter).

4.The TWT is designed such that the building is protected from degradation by flue gas and condensate. However,­ if additional protection is desired, install against the wall a non-corrosive metal sheet under the TWT.

5.Due to the normal formation of water vapor in the combus­ tion process, horizontal­ terminations must not be located over areas of pedestrian or vehicular traffic, (i.e., public walkways or over areas where condensate could create a nuisance or hazard). This is especially true in colder climates where ice buildup is likely to occur. A.O. Smith Corporation will not be held liable for any personal injury or property damage due to any dislodging­ of ice.

17

Page 17
Image 17
A.O. Smith VB/VW- 750 Venting Supports, Vertical Installation Requirements, Horizontal Installtion Requirements

VB/VW- 1000, VB/VW- 750 specifications

A.O. Smith is a renowned name in the water heating industry, and their VB/VW-750 and VB/VW-1000 models reflect the cutting-edge advancements in both design and functionality. These commercial water heaters stand out due to their innovative features and robust characteristics, making them ideal solutions for various applications in commercial settings.

The VB/VW-750 and VB/VW-1000 models are designed with high efficiency in mind. They utilize advanced heat transfer technology that maximizes energy use, translating to significant savings on utility bills. These units are engineered to deliver consistent hot water supply, essential for businesses such as restaurants, hotels, and manufacturing facilities where extensive hot water demands are necessary.

One of the standout features of the VB/VW models is their high recovery rate. This means they can produce a large volume of hot water within a short period, catering to peak demand times without compromising performance. Additionally, the units come equipped with a durable tank made from high-quality materials to resist corrosion, which ensures a long lifespan and reliability in service.

The VB/VW-750 and VB/VW-1000 are also equipped with advanced control systems. These systems provide precise temperature regulation, improving safety and energy efficiency. The smart pumping system further enhances performance by optimizing water flow and reducing energy consumption during operation.

Maintenance and serviceability are key characteristics of these models. They feature easy access to critical components, allowing for quick inspections and repairs. This design consideration minimizes downtime, which is crucial for any business reliant on continuous hot water supply.

Both models are compliant with various industry standards, including energy efficiency regulations. A.O. Smith has focused on ensuring these water heaters not only meet but exceed these requirements, contributing to sustainability efforts.

In summary, the A.O. Smith VB/VW-750 and VB/VW-1000 models combine efficiency, reliability, and ease of maintenance. Their advanced features and cutting-edge technologies make them a top choice for commercial hot water applications, positioning A.O. Smith as a leader in the water heating industry. With their strong performance and durability, these models are designed to meet the demands of modern businesses while providing peace of mind regarding hot water availability.