Page 2 of 5
1.The fibers should have been placed in the rack when the chassis was installed. Route the fibers through the fiber management baffle into the top of the chassis to the ODS2 module locations. Protective covers must be in place on the fiber connectors to prevent dust and damage to the connections. The fibers should be tagged to identify the circuit and the transmission direction.
2.Select the ODS2 module. If the module is not already installed, remove the module from the protective ESD packaging. If ODS2 module is installed, remove it and inspect for physical damage.
3.Refer to Figure
Reference:
4.Insert the working ODS2 module first. Align the module with the slots and slide module into the chassis until the two fiber connectors protrude about three inches out from the front of the chassis. Do not seat module in connector at this time.
5.Remove the protective dust caps from the transmit and receive connectors on the ODS2 module.
6.Remove the protective covers from the fibers.
7.Clean fiber optic connectors and adapters.
Reference:
Instructions
8.Connect a fiber optic patch cord between the transmit and receive connector on the ODS2 module. See Figure
9.Using the ODS2 module ejector, press the module into the chassis until it is properly seated.
10.On the APU, press LMPTST/APS switch. Did all ODS2 indicators light?
•If Yes, continue to Step 11.
•If No, replace ODS2 module and go to Step 4.
11.Is the STATUS indicator on the ODS2 module lighted green?
•If Yes, continue to Step 12.
•If No, replace ODS2 module and go to Step 4.