JOBAID
AC/DC POWER SUPPLY AND BATTERY CHARGER | PRICING AN D AVAILA BILITY | 800 | .827.0887 |
RETURN FO R R EPAIR | 256 | .963.8722 | |
| TECHNICAL SUPPOR T | 888 | .4ADTRAN |
|
|
AC/DC POWER
SUPPLY AND BATTERY CHARGERP/N: 1175043L1CLEI: SIMPAAAARA
P/N: 1175043L2
CLEI: SIMPAADARA
P/N: 1175043L3CLEI: SIMPAAEARA
Note: The AC/DC Power Supplyand Battery Charger is
designed for use with theTotal Access 750 and 850.
| MOUNTING INSTRUCTIONS |
1 | Remove the Total Access 750/850 AC/DC Power Supply |
(ADTRAN P/N 1175043Lx) from the box and inspect for | |
| damage. If damage is apparent, contact your carrier or |
| supplier. |
3 Use four #6 x 3/8" machine screws (supplied) to mount the power supply to either side of the Total Access 750/850 shelf.
Note: Threaded mounting holes are provided on both sides of the shelf.
Note: For battery backup installations, it is recommended to mount the power supply on the left side of the Total Access 750/850 shelf, next to the battery cover hinge.
Note: Alternatively, the power supply can be mounted to the backboard with four #6 x 1" wood screws (not supplied).
STATUS LEDS
AC Power Operation (AC power only) | Battery Operation (AC power supply or battery backup) | ||
GREEN | OK | GREEN | OK (charging) |
YELLOW | Power Fail | YELLOW | Discharging |
RED | Power Fail | RED | Low |
OFF | Power Fail | OFF | Disconnected |
RELAYS
Alarm Relay■Provided for customer use
Condition | Alarm Relay |
|
|
Normal | Open |
|
|
AC Power Failure/ | Cycles open/closed once per second if AC voltage <88 Vrms at full load and battery |
Battery Backup engaged | backup is connected |
|
|
Battery voltage | Stays closed if voltage |
|
|
■Disconnects battery pack from the system if the battery voltage falls below
■Prevents damage to batteries
It is not used with the Total Access 612/616/624 units.
CIRCUIT BREAKER
C A U T I O N !
SUBJECT TO ELECTROSTATIC DAMAGE
OR DECREASE IN RELIABILITY.
HANDLING PRECAUTIONS REQUIRED.
The device complies with Part 15 of the FCC rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
Changes or modifications not expressly approved by ADTRAN could void the user's authority to operate this equipment.
WARRANTY
Warranty for Carrier Network products manufactured by ADTRAN and supplied under Buyer's order for use in the U.S. is ten (10) years. For a complete copy of ADTRAN's U.S. Carrier Networks Equipment Warranty: (877)
■3- amp circuit breaker
■Protects unit from over - current
■Rocker button extends out from front panel when tripped
■Reset by pushing in on the rocker button
GROUNDING
■An 18 AWG or larger ground wire is required to connect additional ground connector to "ground bus" in customer equipment room.
ELECTRICAL SPECIFICATIONS | TELECOMMUNICATIONS CODES | |||||
■ | AC input: 115 V nominal |
|
|
|
| |
| Code | Input | Output | |||
| ||||||
■ Range: 90 to 132 VAC |
| |||||
|
|
|
| |||
| PC | F | C | |||
■ | DC output: |
| ||||
|
|
|
| |||
| TC | — | — | |||
■ | Battery charging: 16 hr nominal, 24 hr maximum | |||||
|
|
| ||||
| E | — | ||||
|
|
| IC |
■ Battery discharge: Up to 8 hours
JOBAid, | Technical Support | Copyright 2002 ADTRAN, All Rights Reserved |